| Notes |
| Date |
Text |
| 2007-06-04 09:59:38 | DENIED; | | | 1.EMERGENCY EYE WASH AND SHOWER SHALL COMPLY WITH | | | ISEA-Z358.1, PER SECTION 411.1 OF THE FBC PLUMBING | | | CODE. SEND IN MANUFACTURE'S CUT SHEET THAT SHOWS | | | COMPLIANCE TO ISEA STANDARDS. | | | 2. WATER RISER DIAGRAM; SHUT OFF VALVE REQUIRED FOR BAY | | | 10. WATER SUPPLY FOR EYE WASH AND EMERGENCY SHOWER ARE | | | NOT SHOWN. WATER SUPPLY TO MEET MANUFACTURE | | | INSTRUCTIONS. | | | 3.SERVICE SINK REQUIRES HOT WATER FOR BUILDING | | | MAINTENANCE. SECTION 607.1 | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|