| 2007-05-17 08:25:22 | ** UNSAT 2ND REVIEW ** |
| | |
| | ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA |
| | BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED |
| | BY THE CITY OF WEST PALM BEACH. |
| | |
| | * PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING. |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE ADDRESS AS APPLIED STILL |
| | INDICATES UNIT/SUITES 11&12, YET PLANS NOW CALL FOR |
| | THIS SPACE TO BE UNIT 10? THIS WILL NEED TO BE GONE |
| | OVER WITH THE ADDRESSING REVIEWER AND COORDINATE FINAL |
| | UNIT/SUITE # AND MAKE ANY ADJUSTMENTS AS NEEDED. |
| | |
| | 2) NOTE: PLEASE SEE THAT NOT ENOUGH INFORMATION WAS |
| | SUBMITTED FOR THE LIGHTING CONTROL PANEL. NO DETAILS, |
| | NO INDICATION ON OVER RIDES AND TYPES PER CHAPTER 13. |
| | PLEASE SEE 13-415.1.ABC.1.1 AS NO MORE THAN 30MINS IS |
| | PERMITTED ON OCCUPANCY TYPE DEVICES. |
| | PLEASE SEE PLANS CALL FOR ALL AT 4HRS WHICH IS NOT |
| | PERMITTED. |
| | PLEASE SEE NO SCHEDULING IS SHOWNON PLANS WHICH IS |
| | REQUIRED TO BE PART OF THE RECORD SETFOR PROPOSED |
| | SCOPE OF WORK. |
| | PLEASE SEE 13-415 |
| | |
| | 3) NOTE: PLEASE SEE OCCUPANCY IS NOW BEING STATED ON |
| | PLANS, HOWEVER EVEN AS NO PAINT SPRAY BOOTH IS SHOWN AT |
| | THIS TIME AND NOT MENTIONED, THE SPACE STILL FALLS |
| | UNDER 511 OF THE NEC. |
| | PLEASE SPECIFY AREAS FOR CLASS AND DIVISIONS ON PLANS. |
| | PLEASE INDICATE WIRING METHODS/INSTALLATIONS ETC PER |
| | MINIMUM REQUIREMENTS IN THE NEC. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |