| | BUILDING PLAN REVIEW |
| | PERMIT: 07030927 |
| | ADD: 1109 OKEECHOBEE BLVD |
| | CONT: RICHARD MC.DONALD CONST. |
| | TEL: (561)745-4736 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 2ND |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)THE LOCATION OF THE NEW DIMISING WALL ON SHEET A2.1 |
| | IS IN DIFFERENT LOCATION ON SHEET A3.1. THE WALL LAYOUT |
| | ON THE FLOOR PLAN SHALL MATCH THE CEILING PLAN. |
| | CLARIFY. |
| | |
| | 3)SHOW IN DETAIL HOW THE NEW SINK OUTSIDE THE WOMEN'S |
| | BATHROOM WILL MEET THE REQUIREMENTS OF SECTION 11-4.24. |
| | SHOW THE CLEAR FLOOR SPACE FOR THE SINK AND THE WATER |
| | COOLER PER SEC. 11-4.15.5. |
| | |
| | 4)FBC. 406.6.1 REPAIR GARAGES SHALL BE CONSTRUCTED IN |
| | ACCORDANCE WITH THE FLORIDA FIRE PREVENTION CODE AND |
| | THIS SECTION. |
| | |
| | 5)NOTE: IF THE ADDRESS HAS BEEN CHANGED ON THE |
| | DRAWINGS, THEN THE INFORMATION ON THE APPLICATION SHALL |
| | BE ALTERED AS WELL. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |