Plan Review Notes
Plan Review Notes For Permit 07030911
Permit Number 07030911
Review Stop E
Sequence Number 3
Notes
Date Text
2007-07-24 10:18:28 
  
  
  
 DENIED
  
 THE DESCRIPTION ON THE APPLICATION IS FOR A SERVICE
 RELOCATION, THERE ARE PLANS SUBMITTED FOR REWIRING THE
 UNIT(S).REMOVE PLANS THAT ARE NOT PERTINENT TO THE
 APPLICATION DESCRIPTION. IF THE UNITS ARE TO BE
 REWIRED, CHANGE THE DESCRIPTION AND INCREASE THE VALUE.
 THE CONTRACTOR OF RECORD MUST MAKE ALL CHANGES RELATING
 TO THESE DOCUMENTS.
  
 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS
 AMENDED.
  
 A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED
 UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID.
 108.1 FBC.
  
 ADJUST THE VALUE AT THE PERMIT CLERKS DESK, AND PAY THE
 DIFFERENCE IN FEES PRIOR TO RESUBMITTING.
  
 THERE WILL BE NO REVIEW DONE FOR THE UNITS UNTILL THEY
 ARE PART OF THE DESCRIPTION OF WORK AND THE VALUE IS
 ADJUSTED TO REFLECT THE SAME.
  
 2} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE PER 215.5, SEE METER TO DISCONNECTS.
  
 3} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED.
  
 4} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.66. INDICATE THE SIZE ON THE RISER.
  
 5}PROVIDE A PANEL SCHEDULE PER 408.4. INCLUDE OCP AND
 CONDUCTOR SIZES. PLEASE SEE NEW VERBAGE FOR 2005 NEC:
 "THE IDENTIFICATION SHALL INCLUDE SUFFICIENT DETAIL TO
 ALLOW EACH CIRCUIT TO BE DISTINGUISHED FROM ALL
 OTHERS." ONE MUST BE SUBMITTED FOR BOTH UNITS IF BEING
 REWIRED.
  
 6} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 7}A GROUNDING ELECTRODE CONDUCTOR IS REQUIRED AT THE
 SEPARATE STRUCTURE PER 250.32, SIZED PER 250.66. SHOW
 ALL EQUIPMENT ON THE RISER.
  
 8} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE
 PLANS PER 106.1.1 FBC AS AMENDED.
  
 9} TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 REVIEW PER 106.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]