| Notes |
| Date |
Text |
| 2007-06-28 15:31:19 | | | | | | | DENIED | | | | | | THE DESCRIPTION ON THE APPLICATION IS FOR A SERVICE | | | RELOCATION., THERE ARE PLANS SUBMITTED FOR REWIRING THE | | | UNIT(S).RMOVE PLANS THAT ARE NOT PERTINENT TO THE | | | APPLICATION DESCRIPTION. | | | | | | SAME COMMENT AS PREVIOUS REVIEW | | | 1} PLEASE SUBMIT A SITE PLAN INDICATING THE LOCATION OF | | | THE METER, MAIN DISCONNECT {WITH AIC RATING} ON THE | | | RESIDENCE.215.5 NEC. | | | | | | NEW COMMENTS | | | 2} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT | | | SIZE AND TYPE PER 215.5,LOAD CALCULATIONS PER 220, | | | SERVICE EQUIPMENT AND PANEL LOCATIONS PER 106.3.5.4 | | | FBC.. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|