Plan Review Notes
Plan Review Notes For Permit 07030911
Permit Number 07030911
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-28 15:31:19 
  
 DENIED
  
 THE DESCRIPTION ON THE APPLICATION IS FOR A SERVICE
 RELOCATION., THERE ARE PLANS SUBMITTED FOR REWIRING THE
 UNIT(S).RMOVE PLANS THAT ARE NOT PERTINENT TO THE
 APPLICATION DESCRIPTION.
  
 SAME COMMENT AS PREVIOUS REVIEW
 1} PLEASE SUBMIT A SITE PLAN INDICATING THE LOCATION OF
 THE METER, MAIN DISCONNECT {WITH AIC RATING} ON THE
 RESIDENCE.215.5 NEC.
  
 NEW COMMENTS
 2} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE PER 215.5,LOAD CALCULATIONS PER 220,
 SERVICE EQUIPMENT AND PANEL LOCATIONS PER 106.3.5.4
 FBC..
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER