| Plan Review Notes For Permit 07030902 |
| Permit Number |
07030902 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-12-26 12:49:31 | THE PLANS DO NOT SHOW THE "TEMPORARY WOODEN STAGE" THAT | | | IS BEING USED FROM TIME TO TIME FOR THE PAST YEAR. | | | | | | PLEASE PROVIDE CONSTRUCTION DETAILS AND DESIGN LOADS | | | INCLUDING THE MEANS OF HANDICAP ACCESSIBILITY, (FBC | | | 11-4.33.5) FOR THE "TEMPORARY STAGE" DECLARED ON THE | | | PERMIT APPLICATION.SEE FBC 106.1. | | | | | | PROVIDE BETTER DETAILS FOR THE CANOPY AND DEMONSTRATE | | | COMPLIANCE WITH THE WIND RESISTANCE REQUIREMENTS OF FBC | | | 1609.1 AND 3105. | | | | | | PROVIDE COMPLETE DETAILS FOR THE ELECTRICAL | | | INSTALLATION.FBC 106.1 | | | | | | RE: ENGINEER GORDON BUCK'S INSPECTION OF THE | | | FOUNDATION.THE LETTER DOES NO DISCLOSE THE DEPTH, | | | WIDTH AND HEIGHT OF THE INSTALLED FOOTINGS WAS | | | INVESTIGATED.IT IS SILENT ON ASCERTAINING SOIL | | | BEARING CAPACITY.IT DOES NOT SPEAK TO THE | | | INSTALLATION OF THE ANCHOR BOLTS.PLEASE INCLUDE THAT | | | INFORMATION WITH YOUR INSPECTION REPORT. | | | | | | HAROLD H PISKURA | | | (561) 805-6711 |
|