2008-01-04 15:08:42BUILDING PLAN REVIEW
 PERMIT: 07030902
 ADD: 700 S. ROSEMARY AVE.
 CONT: VENTURA
 TEL: (561)856-6655
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD
 ACTION: DENIED
  
 1)THE FOUNDATION REQUIREMENTS ARE OK, HOWEVER, THE
 SIGN, SEAL AND DATED ENGINEERED DRAWINGS FOR THE CANOPY
 IS REQUIRED SHOWING HOW THE REQUIREMENTS OF FBC SECTION
 3105 AND 1609 WILL BE ACHIEVED IN REGUARD TO ANCHORAGE
 AGAINST OVERTURNING, UPLIFT AND SLIDING.
  
 2)FBC 11-4.33.5 ACCESS TO PERFORMING AREAS.
 PROVIDE VERIFICATION THAT THE PORTABLE RAMP
 APPROVED FOR THE EXISTING STAGE WILL WORK FOR THE
 INCREASED HEIGHT OF THE NEW TEMPORARY WOODEN STAGE. THE
 ACCESSIBILITY RAMP MUST BE IN PLACE AT THE TIME OF
 INSPECTION.
  
 11.4.8.5. HANDRAILS: IF A RAMP HAS A RISE GREATER THAN
 6" OR A HORIZONTAL PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 11-4.8.2 SLOPE & RISE. THE LEAST POSSIBLE SLOPE SHALL
 BE USED FOR ANY RAMP. THE MAXIMUM SLOPE FOR A RAMP IN
 NEW CONSTRUCTION SHALL BE 1 TO 12. THE MAXIMUM RISE FOR
 RUN SHALL BE 30" (SEE FIGURE 16). FOR MORE INFORMATION
 SEE FBC 11-4.8
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]