| Date |
Text |
| 2007-04-05 16:31:51 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1.SHEET A-2TITLE BLOCK WAS SUBMITTED WITHOUT BEING |
| | SEALED: |
| | PER FAC-CODE-61G1-16001 ARCHITECT'S AND |
| | INTERIOR DESIGNER'S SEAL: |
| | EACH ARCHITECT AND INTERIOR DESIGNER |
| | SHALL ACQUIRE A SEAL WITH WHICH HE OR |
| | SHE SHALL IDENTIFY ALL PLANS, |
| | SPECIFICATIONS OR REPORTS PREPARED OR |
| | ISSUED BY HIM OR HER AND FILED FOR |
| | PUBLIC RECORD. THE SEAL SHALL BE OF A |
| | TYPE WHICH WILL MAKE AN IMPRESSION ON |
| | THE SURFACE OF PRINTS OR OTHER |
| | DUPLICATIONS OF DRAWINGS, AND AS |
| | APPROPRIATE, UPON SPECIFICATION PAGES, |
| | AND OTHER ARTICLES OF SERVICE. |
| | NOTE: RESUBMITTED SHEET A-2 NEEDS TO BE SIGNED AND |
| | SEALED BY THE DESIGN PROFESSIONAL KERMIT C. WHITE LIC. |
| | #AR-00017761 OR REMOVE THE TITLE BLOCK. |
| | |
| | 2. THE SUBMITTED ISOMETRIC GAS RISER DIAGRAM IS |
| | INDICATED AS A 2.0 PSI DELIVERY GAS SYSTEM, PER |
| | FBC-2004 FUEL GAS,A MP REGULATOR IS REQUIRED AND AS |
| | PER SECTION 409.4 MP REGULATOR VALVES, A LISTED SHUTOFF |
| | VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF EACH MP |
| | REGULATOR AND CLEARLY INDICATED ON THE RESUBMITTED |
| | DRAWINGS. |
| | |
| | 3. PER FBC-2004 FUEL GAS, SECTION 408.4 A SEDIMENT |
| | TRAP SHALL BE INDSTALLED DOWNSTREAM OF THE EQUIPMENT |
| | SHUTOFF VALVE AS CLOSE TO THE INLET OF THE EQUIPMENT AS |
| | PRACTICAL. |
| | |
| | 4.SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 |
| | NOTE: PLEASE SUBMIT MANUFACTURER SHEET OF THE 2.0 PSI |
| | MP REGULATOR INDICATING THE MAKE, MODEL NUMBER, AND |
| | SHOWING A LISTING FROM A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY (NRTL). |
| | ALSO THE SUBMITTED MANUFACTURER SHEET FOR THE BBQ ARE |
| | INCOMPLETE THE FOLLOWING INFORMATION IS REQUIRED. A} |
| | THE MANUFACTURER NAME OF THE BBQ. B} MANUFACTURER |
| | INSTALLATION INSTRUCTIONS INDICATING THAT BBQ CAN BE |
| | INSTALLED IN A COVERED PORCH OR IF AN EXHAUST FAN IS |
| | REQUIRED. C} MANUFACTURER SHEET FOR BBQ MUST SHOW |
| | LISTINGS FROM A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY (NRTL). |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |