| 2007-04-07 12:58:44 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | 1.)PROVIDE CALCULATIONS FOR THE CORNER AND PERIMETER |
| | FASTENING SHOWING VALUE PER FASTENER PER SQUARE.THIS |
| | WILL INCLUDE THE ROW AT THE LAP AS WELL AS THE FIELD |
| | ROWS. |
| | |
| | IT IS NOT CLEAR WHETHER THE ROW FASTENING IS COMPLIANT |
| | AS THEY WERE NOT ENHANCED IN THE SAME PROPORTION AS THE |
| | FIELD ROWS, BUT THE RAS117 TAKES ALL ROWS INTO ACCOUNT, |
| | NOT ONLY THE FIELD.THEREFORE, PROVIDE CALCULATIONS |
| | SHOWING THAT THE VALUE PER FASTENER EXCEEDS THE VALUE |
| | REQUIRED TO MEET THE PRESSURES SPECIFIED. |
| | |
| | 2.)PROVIDE SPECS FROM THE MANUFACTURER FOR THE BASE |
| | SHEET SPECIFIED.NOTE THAT THE NOA DOES NOT INCLUDE |
| | INFORMATION ON PRODUCTS THAT ARE NOT MANUFACTURED BY |
| | POLYGLASS.THE FIRST SET OF ENGINEERING STATED THAT |
| | THE SHEET HAD A 31INCH WIDTH, THIS ONE STATES THAT IT |
| | IS 36INCHES.TO MY KNOWLEDGE THIS HAS ALWAYS HAD A |
| | 39.4" SHEET WIDTH.PLEASE PROVIDE SPECIFICATIONS |
| | SHOWING THE 36" WIDTH AS REQUESTED. |
| | |