| Date |
Text |
| 2007-06-08 19:55:38 | ** UNSAT 3RD REVIEW * |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS STILL |
| | NEED TO BE ADDRESSED. PLEASE SEE NEW COMMENTS BASED ON |
| | PLANS SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SEE COMPLIANCE WITH FBC 2004 CHAPTER |
| | 13, 13-415.1.ABC.1.1, AND .1.2 HAS NOT BEEN MET. |
| | PLEASE SEE NO TIMES ON DEVICES AS NOTED. |
| | PLEASE SEE NO TIMES ON SYSTEM OR OVER RIDES AS TIMER |
| | TYPE OF SYSTEM IS BEING NOTED AND SHOWN. |
| | PLEASE SEE THAT A STRAIGHT 7-DAY DIGITAL TIMERS WITH |
| | OUT OVER RIDE CONTROLS AND AUTOMATED SHUT OFF AT |
| | SPECIFIC TIMES DOES NOT MEET CODE. |
| | PLEASE SEE SPACES FOR DEVICES. |
| | PLEASE SEE QUOTING ASHAE IN LIEU OF DETAIL FOR CODE |
| | COMPLIANCE CAN NOT BE ACCEPTED. |
| | PLEASE SEE THE CODES AS QUOTED FOR ASHAE, AS THE 2004 |
| | FBC , W/2006 REVISIONS IS THE LATEST ADOPTED CODE. |
| | |
| | 2) NOTE: PLEASE SEE CODES AS QUOTED. PLANS INDICATE THE |
| | 2005 NFPA-72 (MISPRINT, SHOULD READ 2002). |
| | PLEASE SEE BOTH2002 AND 2005 NFPA-70 (NEC0 IS STATED |
| | ON PLANS. |
| | PLEASE ADJUST. |
| | |
| | 3) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE AS NOTED ABOVE IN |
| | NOTE #1. |
| | PLEASE SEE THE FLORIDA STATUTES REQUIRES A 4X FEE |
| | ASSESSED FOR PLAN REVIEW WHEN CODE COMMENTS ARE |
| | REPEATED. THIS FEE IS 30% OF THE BASE PERMIT FEE OF THE |
| | PORTION ATTRIBUTED TO PLAN REVIEW. THIS 30% OF THE BASE |
| | FEE OF $760 IS $228 TIMES FOUR, WHICH IS $912.00 IS DUE |
| | BEFORE PLANS CAN BE RE-SUBMITTED FOR REVIEW. |
| | PLEASE SEE THAT THE PHONE NUMBER AND E-MAIL ADDRESS HAS |
| | BEEN ON PREVIOUS NOTES ON REVIEWS FOR QUESTIONS OR |
| | COMMENTS. IT IS RECOMMENDED THAT IF THERE ARE ANY |
| | QUESTIONS OR COMMENTS, TO PLEASE CALL TO GO OVER |
| | PLANS. |
| | |
| | ** ONCE AGAIN, IF THERE ARE ANY QUESTIONS, COMMENTS OR |
| | NOTES ARE NOT TYPED IN ANY MANOR WHICH IS UNCLEAR, TO |
| | PLEASE CONTACT THIS OFFICE/REVIEWER. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |