| Notes |
| Date |
Text |
| 2007-05-08 09:38:01 | *** DENIED *** | | | 1) 12"RETURN AIR TRANSFER DUCTS FROM WAITING ROOM NEEDS | | | TO BE 14" AND 12" RETURN AIR TRANSFER DUCT FROM MANAGER | | | OFFICE NEEDS TO BE 16", SEE 2004 FBC/M 601.4 (A), | | | PLEASE CORRECT. | | | | | | *** 2004 FBC/M 601.4. BALANCED RETURN AIR MAY BE | | | ACHIEVED BY. | | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | | INCREASING THE RETURN TRANSFER ONE AND ONE HALF TIMES | | | THE CROSS SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY | | | DUCT ENTERING THE ROOM OR SPACE IT'S SERVING AND THE | | | DOOR HAVING AT LEAST AN | | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE PROPER RETURN | | | AIR BALANCE. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|