2007-05-08 09:38:01*** DENIED ***
 1) 12"RETURN AIR TRANSFER DUCTS FROM WAITING ROOM NEEDS
 TO BE 14" AND 12" RETURN AIR TRANSFER DUCT FROM MANAGER
 OFFICE NEEDS TO BE 16", SEE 2004 FBC/M 601.4 (A),
 PLEASE CORRECT.
  
 *** 2004 FBC/M 601.4. BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND ONE HALF TIMES
 THE CROSS SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY
 DUCT ENTERING THE ROOM OR SPACE IT'S SERVING AND THE
 DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE PROPER RETURN
 AIR BALANCE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.