Plan Review Notes
Plan Review Notes For Permit 07030885
Permit Number 07030885
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-05-10 12:20:43*****DENIED*****
  
 THE FOLLWING COMMENTS TAKEN FROM THE PREVIOUS PLAN
 REVIEW STILL NEED TO BE ADDRESSED:
  
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
  
 2.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF
 NEW BUILDING SUPPLIES & MATERIALS SHALL NOT INTERFERE
 OR HINDER WITH ACCESS TO OR EGRESS FROM THE PROPERTY OR
 VICINITY THEREOF (INCLUDING STREETS, ROADS, AND FIRE
 LANES).
  
 3.WILL THE INSTALLATION OF THE NEW PARTITION WALLS
 AND DOORS IMPACT THE DISTRIBUTION PATTERN OF THE FIRE
 SPRINKLER HEADS?IF SO, SEPARATE PLANS AND PERMIT WILL
 BE REQUIRED FOR THE FIRE SPRINKLER REMODEL.
  
 4.WHEN/IF IT IS NECESSARY TO SHUT DOWN THE FIRE
 PROTECTION SYSTEM, THE FIRE DEPARTMENT WILL BE NOTIFIED
 WHEN IT IS SHUT DOWN AND WHEN IT IS RETURNED TO
 SERVICE.
  
 5.INDICATE THE INTERIOR FINISH CLASSIFICATION FOR THE
 NEW WALLS AND CEILING TILES AS CLASS A, CLASS B, OR
 CLASS C.BE SPECIFIC
  
 6.ALL REQUIRED EXIT COMPONENTS WITHIN THE STRUCTURE
 SHALL BE MAINTAINED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH ITEM
 WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722