| 2007-05-10 12:20:43 | *****DENIED***** | | | | | | THE FOLLWING COMMENTS TAKEN FROM THE PREVIOUS PLAN | | | REVIEW STILL NEED TO BE ADDRESSED: | | | | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | | | | 2.THE DEMOLITION OF EXISTING AND/OR THE STOCKING OF | | | NEW BUILDING SUPPLIES & MATERIALS SHALL NOT INTERFERE | | | OR HINDER WITH ACCESS TO OR EGRESS FROM THE PROPERTY OR | | | VICINITY THEREOF (INCLUDING STREETS, ROADS, AND FIRE | | | LANES). | | | | | | 3.WILL THE INSTALLATION OF THE NEW PARTITION WALLS | | | AND DOORS IMPACT THE DISTRIBUTION PATTERN OF THE FIRE | | | SPRINKLER HEADS?IF SO, SEPARATE PLANS AND PERMIT WILL | | | BE REQUIRED FOR THE FIRE SPRINKLER REMODEL. | | | | | | 4.WHEN/IF IT IS NECESSARY TO SHUT DOWN THE FIRE | | | PROTECTION SYSTEM, THE FIRE DEPARTMENT WILL BE NOTIFIED | | | WHEN IT IS SHUT DOWN AND WHEN IT IS RETURNED TO | | | SERVICE. | | | | | | 5.INDICATE THE INTERIOR FINISH CLASSIFICATION FOR THE | | | NEW WALLS AND CEILING TILES AS CLASS A, CLASS B, OR | | | CLASS C.BE SPECIFIC | | | | | | 6.ALL REQUIRED EXIT COMPONENTS WITHIN THE STRUCTURE | | | SHALL BE MAINTAINED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE (ON THE PLANS) EACH ITEM | | | WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|