Plan Review Notes
Plan Review Notes For Permit 07030885
Permit Number 07030885
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-31 17:31:57* UNSAT **
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE MISSING SIGN CIRCUIT PER 600.5,
 PLEASE INDICATE MINIMUM LOADS REQUIRED. ADJUST LOAD
 CALCULATIONS.
  
 3) NOTE: PLEASE ALSO SEE 210.62 FOR MISSING WINDOW
 RECEPTACLES LOADS PER 220.43. PLEASE SEE LOADS ARE
 BASED ON THE 200VA PER LINEAR FOOT.
 PLEASE ADJUST.
  
 4) NOTE: PLEASE SEE THE 2004 FBC W/ 2006 REVISION AS
 THE NEW LIGHTING CONTROLS SHALL BE 13-415.1.ABC.1.1,
 .1.2 AND .1.3.
 PLEASE SEE THIS IS REQUIRED EVEN IF THE LIGHTING
 FIXTURES ARE BEING SHOWN AS EXISTING NEW WALLS/BUILD
 OUT AND CONTROLS ARE BEING INSTALLED.
 PLEASE SEE THAT DEPENDING ON THE TYPE OF CONTROL
 DEVICESOR SYSTEM INSTALLED PLEASE INDICATE TIMES ON
 DEVICES OF TIMERS, OC SENSORS, TYPES ETC.
  
 5) NOTE: PLEASE SEE PLANS APPEAR TO SHOW THE EMERGENCY
 AND EXIT LIGHTS BEING WIRED PER 700.12E, HOWEVER THE
 PANEL SCHEDULE SHOWS THESE ON A DEDICATED CIRCUIT.
 PLEASE COORDINATE CIRCUITING AND PANEL SCHEDULE. FBC
 106.1.2
  
 6) NOTE: PLEASE SEE RISER SHOWS PANEL AS 150AMP AND THE
 PANEL SCHEDULE SHOWS THIS AS 200AMPS.
 PLEASE CORRELATE.
 FBC 106.1.2
  
 7) NOTE: PLEASE SUBMIT A NEW UPDATE PERMIT APPLICATION
 WHEN PLANS ARE RESUBMITTED . PLEASE SEE THE PERMIT
 APPLICATION SUBMITTED IS DATED FROM 2001. THIS HAS
 SINCE BEEN REVISED. A NEW BLANK PERMIT APPLICATION IS
 BEING ATTACHED TO NOTES AS WELL AS THIS CAN BE
 DOWNLOADED FROM OUR ONLINE WEBSITE.
 THIS IS REQUIRED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]