2007-03-31 10:40:01BUILDING PLAN REVIEW
 PERMIT: 07030885
 ADD: 8989 OKEECHOBEE BLVD
 CONT: KULKA CONST.
 TEL: (954)984-9293
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)110.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 OF THE BUILDING PERMIT.
 -------------------------------------
 ) NUMBER OF UNITS
 ) NUMBER OF FLOORS
 ) NUMBER OF ROOMS
 ) SQ. FT. FOOTPRINT
 ) SQ. FT. UNDER ROOF (TOTAL)
 ) OCCUPANT LOAD
  
  
 3)SEE 2004 FLORIDA EXISTING BUILDING CODE CH,3 AND
 INDICATE THE TYPE OF ALTERATION BASE ON THE SCOPE OF
 WORK.
  
 4)THE VALUE IS LOW. IF IN THE OPINION OF THE BUILDING
 OFFICIAL, THE CLAIMED VALUATION OF BUILDING ALTERATION,
 STRUCTURE,ELECTRICAL, GAS, MECHANICAL OR PLUMBING
 SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. FOR PERMITTING
 PURPOSES, INCLUDE THE TOTAL VALUE OF THE PROJECT
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 5)FBC 11-7.2(2)COUNTERS THAT MAY NOT HAVE A CASH
 REGISTER BUT AT WHICH GOODS OR SERVICES ARE SOLD OR
 DISTRIBUTED EITHER (1) A PORTION OF THE MAIN COUNTER IS
 A MINIMUM OF 36 INCHES IN LENGTH AND A MAXIMUM HEIGHT
 OF 36 INCHES OR ONE OF THE OTHER OPTIONS MENTION IN
 THIS SECTION. SHOW THE ELEVATION DETAIL COMPLYING WITH
 THIS SECTION.
  
 6)THE PARTITION LEGEND ON SHEET A-1.0DOES NOT
 CORRESPOND WITHE THE FLOOR PLAN. THE LEGEND HAS WALL
 TYPES 1 AND 2. HOWEVER, THE FLOOR PLAN SHOWS WALL TYPES
 1 AND 1A. INCATE CLEARLY ON THE DRAWINGS WHERE WALL
 DETAIL #3 WILL BE CONSTRUCTED.
 FBC.106.1.1CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE CODE AND RELEVANT LAWS,ORDINANCES,
 RULES AND REGULATIONS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 7) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 8)WILL THE LOW WALLS BE ATTATCHED TO THE CEILING OR
 WILL THEY BE FREE STANDING?
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  
  
  