| Date |
Text |
| 2007-07-18 06:36:06 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | WEST PALM BEACH MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW**** |
| | |
| | 1. SHT 1 OF 1 SHALL BE SIGNED, SEALED, & DATED PER |
| | SECTION 106.1 AND SHALL COMPLY WITH FAC 61G1-16.004 AS |
| | WELL AS FS 481.219 & 481.2055. |
| | ****NO RESPONSE/NOT ADDRESSED. |
| | |
| | 2. SHT 2 OF 2 SHALL BE SIGNED, SEALED, & DATED PER |
| | SECTION 106.1 AND FS 472.025. |
| | ****NO RESPONSE/NOT ADDRESSED. |
| | |
| | 3. SHT C-1 THE BUSINESS NUMBER IS REQUIRED IN THE TITLE |
| | BLOCK OF THE DESIGN PROFESSIONAL. (SEE ATTACHED SHEET). |
| | FAC 61G15-23.002 & FS 471.025. |
| | ****NO RESPONSE/NOT ADDRESSED. |
| | |
| | 4. SHT C-1 SHEET INDEX INDICATES SHTS C-10, L-1, L-2, |
| | IRR-1 & S-3. THESE SHEETS HAVE NOT BEEN SUBMITTED. |
| | PLEASE CORRELATE THE SHEET INDEX WITH THE SHEETS |
| | SUBMITTED. |
| | ****RESPONSE NOTED, BUT SHEETS L-2, S-3 & C-11 WERE NOT |
| | FOUND AND SHEET IRR-2 IS NOT SHOWN ON THE SHEET INDEX. |
| | PLEASE CORRELATE INFORMATION ON THE SHEET INDEX AND |
| | SHEETS SUBMITTED. |
| | |
| | 5. SHTS C-1 THRU C-9B. THE ADDRESS IN THE TITLE BLOCK |
| | DOES NOT REFLECT THE ADDRESS OF RECORD ON FILE IN THE |
| | STATE DBPR WEBSITE. PLEASE UPDATE THE DBPR WEBSITE OR |
| | THE TITLE BLOCK. FAC 61G1-16.004(1). (SEE ATTACHED |
| | SHEET). |
| | ****NO RESPONSE/NOT ADDRESSED. - ALL C-SHTS SHALL HAVE |
| | AN ADDRESS THAT REFLECTS THE DBPR WEBSITE ADDRESS OF |
| | RECORD. |
| | |
| | 6. SHT C-7 2-WAY CLEANOUTS ARE REQUIRED PRIOR TO, |
| | BETWEEN & AT THE EXIT OF EACH GREASE INTERCEPTOR. |
| | UTILITY STANDARD. (SEE ATTACHED SHEET). |
| | ****NO RESPONSE/NOT ADDRESSED. |
| | |
| | 7.OK |
| | |
| | 8. SHTS C-1 THRU C-7 THE SIGNATURE OF THE ENGINEER OF |
| | RECORD IS REQUIRED ON EACH SHEET. IT APPEARS THAT |
| | INITIALS HAVE BEEN USED. IF THIS IS INDEED THE LEGAL |
| | SIGNATURE OF THE ENGINEER, A SIGNED, SEALED, DATED, |
| | NOTORIZED LETTER SHALL BE SUBMITTED INDICATING THE |
| | LEGAL SIGNATURE OF THE ENGINEER FOR OUR FILE. FAC |
| | 61G1-15.02(1)(2) & FS 471.025. |
| | ****NO RESPONSE/NOT ADDRESSED. |
| | |
| | 9, OK |
| | |
| | 10. ROUTE PLANS TO THE DEPT. OF BUSINESS REGULATION, |
| | HOTEL AND RESTURANT DIVISION FOR REVIEW PRIOR TO |
| | RESUBMITTING TO THE CITY. ATTACH THE TWO PAGE |
| | "WORKSHEET" TO EACH SET OF PLANS STAMPED BY DBPR. PHONE |
| | NUMBER (850)487-1395. SECTION 102.2.1. ****RESPONSE |
| | NOTED, BUT THE TWO PAGE "WORKSHEETS" HAVE NOT BEEN |
| | ATTACHED TO THE STAMPED SHEET ON EACH SET OF PLAN AS |
| | REQUIRED. |
| | |
| | 11. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE |
| | ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE CONTACT RODNEY |
| | COMPO (561) 822-2272 OR CALVIN WILLIAMS (561) 822-2284. |
| | THEIR FAX NUMBER IS (561) 822-2287 AND THEIR E-MAILS |
| | ARE [email protected], OR [email protected]. |
| | ****NO RESPONSE. I HAVE SENT AN E-MAIL TO ENVIRONMENTAL |
| | COMPLIANCE TO GET DETERMINATION OF INTERCEPTOR SIZE |
| | REQUIRED. |
| | |
| | 12. OK |
| | 13. OK |
| | 14. OK |
| | 15. OK |
| | |
| | 16. SHT P2.0 INDICATES A FILTERED WATER SYSTEM. THE |
| | WATER FILTER SHALL COMPLY WITH SECTION 611.1 AND NSF |
| | 42. PLEASE SUBMIT MANUF. SPECIFICATION SHEETS SHOWING |
| | COMPLIANCE. |
| | ****RESPONSE NOTED, BUT MANUF. SPECS NOT SUBMITTED. |
| | |
| | 17. SHT P2.0 PLUMBING KEY NOTES #12. MORE INFORMATION |
| | IS REQUIRED. SECTION 106.1.2. PLEASE INDICATE HOW THE |
| | COLD WATER WILL BE TREATED. SUBMIT MANUF. SPECIFICATION |
| | SHEETS FOR THE PROCESS & SHOW COMPLIANCE WITH NSF. ALL |
| | POTABLE WATER LINES SHALL BE INSTALLED BY A LICENSED |
| | PLUMBER. |
| | ****RESPONSE NOTED, BUT MANUF. SPECS NOT SUBMITTED. |
| | |
| | 18. OK |
| | 19. OK |
| | 20. OK |
| | 21. OK |
| | 22. OK |
| | 23. OK |
| | 24. OK |
| | |
| | 25, SUBMIT A STORM PIPING RISER DIAGRAM IN ISOMETRIC |
| | FORM. SECTION 106..3.5.1.3(7)(13). |
| | ****RESPONSE NOTED, BUT MINIMUM 5" PIPE IS REQUIRED FOR |
| | 1738SF, (DOWNSTREAM OF FIRST TWO ROOF DRAINS). TABLE |
| | 1106.3. |
| | |
| | 26. OK |
| | 27. OK |
| | 28. OK |
| | 29. OK |
| | |
| | **********NEW COMMENT********** |
| | |
| | 1B. SEE ATTACHED COPY OF FS 553.80(2)(B) CONCERNING THE |
| | DESIGN PROFESSIONAL AND REPEAT COMMENTS. THIS IS GIVEN |
| | AS A NOTICE ONLY AT THIS TIME. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | AND RESUBMITTING 1 SET OF PLANS FROM THE |
| | PREVIOUS REVIEW WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |