Plan Review Notes
Plan Review Notes For Permit 07030860
Permit Number 07030860
Review Stop P
Sequence Number 2
Notes
Date Text
2007-07-18 06:36:06DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 WEST PALM BEACH MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW****
  
 1. SHT 1 OF 1 SHALL BE SIGNED, SEALED, & DATED PER
 SECTION 106.1 AND SHALL COMPLY WITH FAC 61G1-16.004 AS
 WELL AS FS 481.219 & 481.2055.
 ****NO RESPONSE/NOT ADDRESSED.
  
 2. SHT 2 OF 2 SHALL BE SIGNED, SEALED, & DATED PER
 SECTION 106.1 AND FS 472.025.
 ****NO RESPONSE/NOT ADDRESSED.
  
 3. SHT C-1 THE BUSINESS NUMBER IS REQUIRED IN THE TITLE
 BLOCK OF THE DESIGN PROFESSIONAL. (SEE ATTACHED SHEET).
 FAC 61G15-23.002 & FS 471.025.
 ****NO RESPONSE/NOT ADDRESSED.
  
 4. SHT C-1 SHEET INDEX INDICATES SHTS C-10, L-1, L-2,
 IRR-1 & S-3. THESE SHEETS HAVE NOT BEEN SUBMITTED.
 PLEASE CORRELATE THE SHEET INDEX WITH THE SHEETS
 SUBMITTED.
 ****RESPONSE NOTED, BUT SHEETS L-2, S-3 & C-11 WERE NOT
 FOUND AND SHEET IRR-2 IS NOT SHOWN ON THE SHEET INDEX.
 PLEASE CORRELATE INFORMATION ON THE SHEET INDEX AND
 SHEETS SUBMITTED.
  
 5. SHTS C-1 THRU C-9B. THE ADDRESS IN THE TITLE BLOCK
 DOES NOT REFLECT THE ADDRESS OF RECORD ON FILE IN THE
 STATE DBPR WEBSITE. PLEASE UPDATE THE DBPR WEBSITE OR
 THE TITLE BLOCK. FAC 61G1-16.004(1). (SEE ATTACHED
 SHEET).
 ****NO RESPONSE/NOT ADDRESSED. - ALL C-SHTS SHALL HAVE
 AN ADDRESS THAT REFLECTS THE DBPR WEBSITE ADDRESS OF
 RECORD.
  
 6. SHT C-7 2-WAY CLEANOUTS ARE REQUIRED PRIOR TO,
 BETWEEN & AT THE EXIT OF EACH GREASE INTERCEPTOR.
 UTILITY STANDARD. (SEE ATTACHED SHEET).
 ****NO RESPONSE/NOT ADDRESSED.
  
 7.OK
  
 8. SHTS C-1 THRU C-7 THE SIGNATURE OF THE ENGINEER OF
 RECORD IS REQUIRED ON EACH SHEET. IT APPEARS THAT
 INITIALS HAVE BEEN USED. IF THIS IS INDEED THE LEGAL
 SIGNATURE OF THE ENGINEER, A SIGNED, SEALED, DATED,
 NOTORIZED LETTER SHALL BE SUBMITTED INDICATING THE
 LEGAL SIGNATURE OF THE ENGINEER FOR OUR FILE. FAC
 61G1-15.02(1)(2) & FS 471.025.
 ****NO RESPONSE/NOT ADDRESSED.
  
 9, OK
  
 10. ROUTE PLANS TO THE DEPT. OF BUSINESS REGULATION,
 HOTEL AND RESTURANT DIVISION FOR REVIEW PRIOR TO
 RESUBMITTING TO THE CITY. ATTACH THE TWO PAGE
 "WORKSHEET" TO EACH SET OF PLANS STAMPED BY DBPR. PHONE
 NUMBER (850)487-1395. SECTION 102.2.1. ****RESPONSE
 NOTED, BUT THE TWO PAGE "WORKSHEETS" HAVE NOT BEEN
 ATTACHED TO THE STAMPED SHEET ON EACH SET OF PLAN AS
 REQUIRED.
  
 11. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE
 ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE CONTACT RODNEY
 COMPO (561) 822-2272 OR CALVIN WILLIAMS (561) 822-2284.
 THEIR FAX NUMBER IS (561) 822-2287 AND THEIR E-MAILS
 ARE [email protected], OR [email protected].
 ****NO RESPONSE. I HAVE SENT AN E-MAIL TO ENVIRONMENTAL
 COMPLIANCE TO GET DETERMINATION OF INTERCEPTOR SIZE
 REQUIRED.
  
 12. OK
 13. OK
 14. OK
 15. OK
  
 16. SHT P2.0 INDICATES A FILTERED WATER SYSTEM. THE
 WATER FILTER SHALL COMPLY WITH SECTION 611.1 AND NSF
 42. PLEASE SUBMIT MANUF. SPECIFICATION SHEETS SHOWING
 COMPLIANCE.
 ****RESPONSE NOTED, BUT MANUF. SPECS NOT SUBMITTED.
  
 17. SHT P2.0 PLUMBING KEY NOTES #12. MORE INFORMATION
 IS REQUIRED. SECTION 106.1.2. PLEASE INDICATE HOW THE
 COLD WATER WILL BE TREATED. SUBMIT MANUF. SPECIFICATION
 SHEETS FOR THE PROCESS & SHOW COMPLIANCE WITH NSF. ALL
 POTABLE WATER LINES SHALL BE INSTALLED BY A LICENSED
 PLUMBER.
 ****RESPONSE NOTED, BUT MANUF. SPECS NOT SUBMITTED.
  
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
 24. OK
  
 25, SUBMIT A STORM PIPING RISER DIAGRAM IN ISOMETRIC
 FORM. SECTION 106..3.5.1.3(7)(13).
 ****RESPONSE NOTED, BUT MINIMUM 5" PIPE IS REQUIRED FOR
 1738SF, (DOWNSTREAM OF FIRST TWO ROOF DRAINS). TABLE
 1106.3.
  
 26. OK
 27. OK
 28. OK
 29. OK
  
 **********NEW COMMENT**********
  
 1B. SEE ATTACHED COPY OF FS 553.80(2)(B) CONCERNING THE
 DESIGN PROFESSIONAL AND REPEAT COMMENTS. THIS IS GIVEN
 AS A NOTICE ONLY AT THIS TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 AND RESUBMITTING 1 SET OF PLANS FROM THE
 PREVIOUS REVIEW WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS