2007-07-26 15:27:08*****DENIED*****
  
 THE FOLLOWIING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
 01.THE ACTUAL NUMERICAL ADDRESS OF THE PROJECT SITE
 SHALL BE IN TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
 NO ADDRESS SHOWN SHEET L-1, IR-1, IR-2, C-1, 1, 2,
 K1.0
  
 04.PLEASE SHOW LOCATION OF THE NEAREST FIRE
 HYDRANT(S) TO THIS PROJECT.PLEASE ACKNOWLEDGE
  
 05.THE ADDRESS AS SHOWN ON SHEET A2.0 IS ACCEPTABLE,
 HOWEVER IT IS HIGHLY RECOMMENDED THAT THE PLACEMENT OF
 THOSE NUMBERS BE ON THEBUILDING STRUCTURE ITSELF AS
 TO PROVIDE BETTER CONTRAST/VISIBILITY AND PREVENTS THE
 POSSIBILITY OF THE ADDRESS BEING COVERED BY THE
 INSTALLATION OF HURRICANE AND OR SECURITY SHUTTERS
  
 08.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 INSTALLATION OF THE COOKING HOOD AND THE COOKING HOOD'S
 SUPPRESSION SYSTEM.PLEASE ACKNOWLEDGE ON THE
 APPROPIATE PLAN SHEET(S)
  
 09.SHOW LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFIES THE 75' TRAVEL
 DISTANCE.PLEASE SHOW EXTINGUISHER LOCATIONS ON SHEET
 A1.6
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  