| Plan Review Notes For Permit 07030860 |
| Permit Number |
07030860 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-07-26 15:27:08 | *****DENIED***** | | | | | | THE FOLLOWIING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 01.THE ACTUAL NUMERICAL ADDRESS OF THE PROJECT SITE | | | SHALL BE IN TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. | | | NO ADDRESS SHOWN SHEET L-1, IR-1, IR-2, C-1, 1, 2, | | | K1.0 | | | | | | 04.PLEASE SHOW LOCATION OF THE NEAREST FIRE | | | HYDRANT(S) TO THIS PROJECT.PLEASE ACKNOWLEDGE | | | | | | 05.THE ADDRESS AS SHOWN ON SHEET A2.0 IS ACCEPTABLE, | | | HOWEVER IT IS HIGHLY RECOMMENDED THAT THE PLACEMENT OF | | | THOSE NUMBERS BE ON THEBUILDING STRUCTURE ITSELF AS | | | TO PROVIDE BETTER CONTRAST/VISIBILITY AND PREVENTS THE | | | POSSIBILITY OF THE ADDRESS BEING COVERED BY THE | | | INSTALLATION OF HURRICANE AND OR SECURITY SHUTTERS | | | | | | 08.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE | | | INSTALLATION OF THE COOKING HOOD AND THE COOKING HOOD'S | | | SUPPRESSION SYSTEM.PLEASE ACKNOWLEDGE ON THE | | | APPROPIATE PLAN SHEET(S) | | | | | | 09.SHOW LOCATION OF THE 2A:10BC RATED FIRE | | | EXTINGUISHER(S) WHICH SATISFIES THE 75' TRAVEL | | | DISTANCE.PLEASE SHOW EXTINGUISHER LOCATIONS ON SHEET | | | A1.6 | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|