| 2007-07-04 12:32:03 | 2007-07-04 12:32:03 |
| | ** UNSAT 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING. |
| | |
| | |
| | PROPOSED MCDONALDS |
| | 9835 OKEECHOBEE BLVD. |
| | |
| | 1) NOTE: PLEASE SEE THE RESPONSE LETTER FROM THE |
| | ENGINEER DOES NOT CORRELATE WITH THE REVIEW NOTES AS |
| | PREVIOUSLY GIVEN AND THEREFORE SOME OF THE RESPONSES |
| | AND NOTES DO NOT COORDINATE WITH THE ACTUAL NOTES |
| | PREVIOUSLY TYPED AND GIVEN BY THIS REVIEWER. PLEASE SEE |
| | FOR EXAMPLE, NOTE #5, NOTE #6, NOTE #7 ETC. |
| | |
| | 2) NOTE: 2ND TIME NOTED. |
| | PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED DO NOT |
| | CORRELATE WITH PLANS. |
| | PLEASE SEE THE ADDRESS AS LISTED ON ALL SHEETS OF THE |
| | ENERGY CALCULATIONS INCLUDING SUMMARY SHEETS INDICATES |
| | 2721 OKEECHOBEE BLVD WHICH IS NOT THE ADDRESS OF THE |
| | BUILDING BEING PROPOSED. |
| | PLEASE SEE THE SUMMARY SHEETS FOR EXTERIOR LIGHTING |
| | WHICH INDICATES A TOTAL OF 0 FOR DESIGN WATTAGE AND 0 |
| | FOR ALLOWANCE?HOW IS THIS POSSIBLE WHEN THERE ARE |
| | FIXTURES IN DESIGN OF PROJECT? |
| | PLEASE SEE THE INPUT DATA REPORT WHICH DOES NOT |
| | COORDINATE WITH THE LIGHTING AS SHOWN ON PLANS. PLEASE |
| | SEE THE EXTERIOR LIGHTING INPUT DATA, AS THE NUMBER OF |
| | FIXTURES, THE WATTAGE AND THE TYPES DO NOT CORRELATE |
| | WITH PLANS. |
| | PLEASE SEE THE INPUT DATA REPORT FOR INTERIOR LIGHTING |
| | AS THIS ALSO NEEDS TO CORRELATE WITH THE PLANS AND |
| | FIXTURE LEGEND AS SUBMITTED. PLEASE COORDINATE THE |
| | TYPES OF LUMINARIES, THE NUMBER OF LUMINARIES UNDER |
| | EACH AND THE WATTAGE OF EACH WITH THE FIXTURE LEGEND |
| | AND PLANS. |
| | ** PLEASE BE SURE THE CERTIFICATION SHEET IS SIGNED, |
| | DATED AND SEALED AS REQUIRED. |
| | PLEASE SEE 13-415.1.A |
| | 13-103.1.1.1 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 2004 FBC W/ 2006 REVISION FOR CHAPTER 13. |
| | PLEASE SEE 13-415.1.AB.1.1, 13-415.2 AS THE ENERGY |
| | CALCULATIONS DO NOT COORDINATE WITH THE ELECTRICAL |
| | PLANS FOR THE FIXTURES, AMOUNT OF FIXTURES, ETC. PLEASE |
| | SEE PLANS INDICATE OVER 100PLUS FIXTURES, AND |
| | CALCULATIONS ONLY INDICATE 30? |
| | PLEASE SEE NO INFORMATION ENTERED FOR EXTERIOR |
| | LIGHTING, YET PLANS INDICATE NUMEROUS EXTERIOR LIGHTS? |
| | PLEASE SEE THE WATTAGE AND FIXTURES DO NOT CORRELATE. |
| | ** THERE ARE SEVERAL ITEMS NOT LISTED AND A COMPLETE |
| | REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT THIS |
| | TIME. |
| | |
| | 3) NOTE: CHECK ALL EQUIPMENT AND OVER CURRENT |
| | PROTECTION AS NOTED ON EQUIPMENT SCHEDULE WITH THAT OF |
| | THE OVER CURRENT PROTECTION ON PANEL SCHEDULES. PLEASE |
| | ALSO CHECK FOR GFI PROTECTION. |
| | EXAMPLE: PLEASE SEE CIRCUITS AP1 9 AND 11, INDICATES |
| | 20AMP, YET EQUIPMENT SCHEDULE SHOWS 15AMP. |
| | PLEASE BE SURE TO INDICATE 210.8B2 |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE 2005 NEC 210.8B2 FOR ALL 15/20AMP, 120V |
| | RECEPTACLES IN KITCHEN/FOOD PREPARATION AREAS TO BE |
| | GFI/GFI PROTECTED. |
| | PLEASE SEE THE SECTION OF CODE NOTED ON PLANS IS NOT |
| | COMPLETE WITH THE SECTION AS NOTED. |
| | PLEASE ALSO SEE THAT NOT ALL CIRCUITS AS REQUIRED |
| | INDICATE THE PROTECTION. |
| | PLEASE SEE SOME CIRCUITS INDICATE PROTECTION WHERE NOT |
| | REQUIRED? |
| | PLEASE COORDINATE. |
| | |
| | 4) NOTE:THIS COMMENT REMAINS AS NO CHANGES WERE MADE |
| | TO PERMIT APPLICATION OR SCOPE. NO RESPONSE WAS MADE?? |
| | PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF WORK APPLIED |
| | FOR SHALL INCLUDE ALL LABOR, MATERIALS, PERMANENTLY |
| | INSTALLED EQUIPMENT, DESIGN COST ETC EVEN IF ANY OF |
| | THESE ITEMS ARE OWNER SUPPLIED. FBC ADMIN SECTION |
| | 108.3 |
| | |
| | ** PREVIOUS REVIEW NOTE**PLEASE SEE THE VALUE FOR THE |
| | COMPLETE SCOPE OF WORK FOR THIS NEW BUILDING SHALL |
| | INCLUDE ALL LABOR AND MATERIALS. PLEASE KNOW THAT EVEN |
| | EQUIPMENT SUCH AS KITCHEN, A/C ETC WHICH MAY BE OWNER |
| | SUPPLIED IS TO BE INCLUDED IN VALUE. |
| | FBC 108.3. |
| | |
| | 5) NOTE: PLEASE SEE PREVIOUS NOTE #7. THE EXCEPTION IN |
| | THE NEC UNDER 700.12F FOR ALLOWANCE OF CIRCUITING AS |
| | SHOWN MENTIONS 3 OR MORE CIRCUITS IN ANY SEPARATE AND |
| | UN-INTERRUPTED LOCATION. PLEASE SEE THE RESPONSE |
| | MENTIONS COMMENTS WITH RESPECT TO THE *INTENT* OF THE |
| | CODE WHICH IS UNDERSTOOD HOWEVER THE NUMBER OF CIRCUITS |
| | AND THE UN-INTERRUPTED SPACES IS NOT PRESENT ON PLANS |
| | IN SOME OF THESE AREAS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE COMPLETE CIRCUITING ON PLANS FOR ALL EMERGENCY |
| | LIGHTS AND EXIT LIGHTS. |
| | PLEASE SEE 700.12F AS THE EM/EXT LIGHTS SHALL BE |
| | CIRCUITED TO THE LOCAL LIGHTING IN ANY ONE AREA. PLEASE |
| | COMPLETE ON PLANS. |
| | THE NOTE ON E-3 FOR EMERGENCY NOTES #1 DOES NOT MEET |
| | THE CODE AND SECTION AS NOTED. |
| | PLEASE ADJUST PLANS AND NOTES. |
| | |
| | 6) NOTE: PLEASE SEE PREVIOUS NOTE #8 WHICH REQUESTED |
| | ADJUSTMENT FOR WATER HEATER. PLEASE SEE THE RESPONSE |
| | MENTIONS THE BRANCH CIRCUIT IS SIZED FOR 125% (TYPED AS |
| | 12% IN RESPONSE)(MISPRINT). PLEASE SEE THE NEC CHANGED |
| | AND THIS INCLUDE THE LOADS IN LOAD CALCULATIONS TO ALSO |
| | BE SHOWN AND FIGURED AT 125%. THE WATER HEATER LOAD IS |
| | SHOWN AS 18KW, (ENERGY CALCULATIONS DOES NOT CORRELATE) |
| | AND THE LOAD SUMMARY DOES NOT INDICATE IF THIS IS THE |
| | 125%. PLEASE SEE FOLLOWING TEXT WHICH HAS BEEN |
| | EXTRACTED FROM THE NEC COMMENTARY. |
| | **THE REVISION TO 422.13 SPECIFICALLY IDENTIFIES AN |
| | ELECTRIC WATER HEATER WITH A STORAGE CAPACITY OF 120 |
| | GAL OR LESS AS A CONTINUOUS LOAD. THIS REVISION |
| | REQUIRES THE BRANCH CIRCUIT OVERCURRENT DEVICE AND |
| | CONDUCTORS TO BE SIZED BASED ON 125 PERCENT OF THE |
| | WATER HEATER NAMEPLATE RATING UNLESS THE OVERCURRENT |
| | DEVICE AND THE ASSEMBLY IT IS INSTALLED IN ARE LISTED |
| | TO BE USED AT 100 PERCENT OF ITS CONTINUOUS CURRENT |
| | RATING. IN ADDITION, FEEDERS AND SERVICES THAT SUPPLY |
| | WATER HEATER BRANCH CIRCUITS ARE ALSO IMPACTED BY THE |
| | FACT THAT THIS TYPE OF EQUIPMENT IS CONSIDERED TO BE A |
| | CONTINUOUS LOAD.** |
| | |
| | PLEASE 422.13 AS THE CHANGES IN THE 2005 NEC REQUIRES |
| | THE WATER HEATER LOAD TO BE FIGURED IN THE CALCULATIONS |
| | AT 125%. |
| | PLEASE ADJUST CALCULATIONS. |
| | |
| | 7) NOTE:THIS NOTE REMAINS AS LOADS AND INFORMATION |
| | FOR NOTES ABOVE WILL NEED TO BE ADJUSTED. |
| | PLEASE SEE NO LOAD SUMMARY WAS SUBMITTED INDICATING HOW |
| | LOADS WERE DERIVED. |
| | EX: 12 RECEPTS AT 180VA ETC |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE MORE DETAIL ON THE LOAD SUMMARY FOR THE |
| | LOAD CALCULATIONS. |
| | PLEASE SEE NOTE ABOVE AS THIS WILL ALSO AFFECT THE |
| | LOAD. |
| | PLEASE KNOW AT THIS TIME THE LOADS ARE NOT CLEAR AS NOT |
| | ALL LOADS ARE FIGURED IN WITH KITCHEN EQUIPMENT AND NOT |
| | SURE WHERE AND HOW THE OTHER LOADS ARE BEING DONE OR |
| | FIGURED. |
| | FBC 106.1.3.5.1.2, 106.1.2. NEC 220. |
| | |
| | 8) NOTE:SAME NOTE AS NOTE #10 ON PREVIOUS REVIEW. NO |
| | RESPONSE TO THIS NOTE OR CHANGES TO NOTES ON |
| | PLANS/PANEL SCHEDULES. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW THAT ANY LOCK ON/OFF DEVICES WILL BE |
| | REQUIRED TO HAVE THE DEVICE BE AN INTEGRAL PART OF THE |
| | BREAKER. THE DEVICES WHICH *SNAP/CLIP* ON TO BREAKERS |
| | AND ARE READILY REMOVED OR FALL OF WHEN PANEL COVERS |
| | ARE REMOVED ARE NOT APPROVED BY THIS AHJ. PLEASE ADJUST |
| | NOTE TO STATE *THE DEVICE SHALL BE AN INTEGRAL PART OF |
| | THE BREAKER* OR WORDS TO THAT AFFECT. 110.3, 90.4. |
| | |
| | 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS. THIS IS ONLY A NOTICE GIVEN AT THIS |
| | TIME. |
| | ONE SET OF ELECTRICAL PLANS AND ENERGY CALCULATIONS ARE |
| | BEING RETAINED. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-07-04 10:44:44 | 2007-07-04 10:44:44 |
| | PLANS REMOVED FROM INCOMING. PLANS WILL BE RETURNED TO |
| | INCOMING WAITING FOR COMM BOARD ONCE ELECTRICLA REVIEW |
| | IS COMPLETED. |