Date Text
2007-07-04 12:32:032007-07-04 12:32:03
 ** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
  
 PROPOSED MCDONALDS
 9835 OKEECHOBEE BLVD.
  
 1) NOTE: PLEASE SEE THE RESPONSE LETTER FROM THE
 ENGINEER DOES NOT CORRELATE WITH THE REVIEW NOTES AS
 PREVIOUSLY GIVEN AND THEREFORE SOME OF THE RESPONSES
 AND NOTES DO NOT COORDINATE WITH THE ACTUAL NOTES
 PREVIOUSLY TYPED AND GIVEN BY THIS REVIEWER. PLEASE SEE
 FOR EXAMPLE, NOTE #5, NOTE #6, NOTE #7 ETC.
  
 2) NOTE: 2ND TIME NOTED.
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED DO NOT
 CORRELATE WITH PLANS.
 PLEASE SEE THE ADDRESS AS LISTED ON ALL SHEETS OF THE
 ENERGY CALCULATIONS INCLUDING SUMMARY SHEETS INDICATES
 2721 OKEECHOBEE BLVD WHICH IS NOT THE ADDRESS OF THE
 BUILDING BEING PROPOSED.
 PLEASE SEE THE SUMMARY SHEETS FOR EXTERIOR LIGHTING
 WHICH INDICATES A TOTAL OF 0 FOR DESIGN WATTAGE AND 0
 FOR ALLOWANCE?HOW IS THIS POSSIBLE WHEN THERE ARE
 FIXTURES IN DESIGN OF PROJECT?
 PLEASE SEE THE INPUT DATA REPORT WHICH DOES NOT
 COORDINATE WITH THE LIGHTING AS SHOWN ON PLANS. PLEASE
 SEE THE EXTERIOR LIGHTING INPUT DATA, AS THE NUMBER OF
 FIXTURES, THE WATTAGE AND THE TYPES DO NOT CORRELATE
 WITH PLANS.
 PLEASE SEE THE INPUT DATA REPORT FOR INTERIOR LIGHTING
 AS THIS ALSO NEEDS TO CORRELATE WITH THE PLANS AND
 FIXTURE LEGEND AS SUBMITTED. PLEASE COORDINATE THE
 TYPES OF LUMINARIES, THE NUMBER OF LUMINARIES UNDER
 EACH AND THE WATTAGE OF EACH WITH THE FIXTURE LEGEND
 AND PLANS.
 ** PLEASE BE SURE THE CERTIFICATION SHEET IS SIGNED,
 DATED AND SEALED AS REQUIRED.
 PLEASE SEE 13-415.1.A
 13-103.1.1.1
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 2004 FBC W/ 2006 REVISION FOR CHAPTER 13.
 PLEASE SEE 13-415.1.AB.1.1, 13-415.2 AS THE ENERGY
 CALCULATIONS DO NOT COORDINATE WITH THE ELECTRICAL
 PLANS FOR THE FIXTURES, AMOUNT OF FIXTURES, ETC. PLEASE
 SEE PLANS INDICATE OVER 100PLUS FIXTURES, AND
 CALCULATIONS ONLY INDICATE 30?
 PLEASE SEE NO INFORMATION ENTERED FOR EXTERIOR
 LIGHTING, YET PLANS INDICATE NUMEROUS EXTERIOR LIGHTS?
 PLEASE SEE THE WATTAGE AND FIXTURES DO NOT CORRELATE.
 ** THERE ARE SEVERAL ITEMS NOT LISTED AND A COMPLETE
 REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT THIS
 TIME.
  
 3) NOTE: CHECK ALL EQUIPMENT AND OVER CURRENT
 PROTECTION AS NOTED ON EQUIPMENT SCHEDULE WITH THAT OF
 THE OVER CURRENT PROTECTION ON PANEL SCHEDULES. PLEASE
 ALSO CHECK FOR GFI PROTECTION.
 EXAMPLE: PLEASE SEE CIRCUITS AP1 9 AND 11, INDICATES
 20AMP, YET EQUIPMENT SCHEDULE SHOWS 15AMP.
 PLEASE BE SURE TO INDICATE 210.8B2
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE 2005 NEC 210.8B2 FOR ALL 15/20AMP, 120V
 RECEPTACLES IN KITCHEN/FOOD PREPARATION AREAS TO BE
 GFI/GFI PROTECTED.
 PLEASE SEE THE SECTION OF CODE NOTED ON PLANS IS NOT
 COMPLETE WITH THE SECTION AS NOTED.
 PLEASE ALSO SEE THAT NOT ALL CIRCUITS AS REQUIRED
 INDICATE THE PROTECTION.
 PLEASE SEE SOME CIRCUITS INDICATE PROTECTION WHERE NOT
 REQUIRED?
 PLEASE COORDINATE.
  
 4) NOTE:THIS COMMENT REMAINS AS NO CHANGES WERE MADE
 TO PERMIT APPLICATION OR SCOPE. NO RESPONSE WAS MADE??
 PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF WORK APPLIED
 FOR SHALL INCLUDE ALL LABOR, MATERIALS, PERMANENTLY
 INSTALLED EQUIPMENT, DESIGN COST ETC EVEN IF ANY OF
 THESE ITEMS ARE OWNER SUPPLIED. FBC ADMIN SECTION
 108.3
  
 ** PREVIOUS REVIEW NOTE**PLEASE SEE THE VALUE FOR THE
 COMPLETE SCOPE OF WORK FOR THIS NEW BUILDING SHALL
 INCLUDE ALL LABOR AND MATERIALS. PLEASE KNOW THAT EVEN
 EQUIPMENT SUCH AS KITCHEN, A/C ETC WHICH MAY BE OWNER
 SUPPLIED IS TO BE INCLUDED IN VALUE.
 FBC 108.3.
  
 5) NOTE: PLEASE SEE PREVIOUS NOTE #7. THE EXCEPTION IN
 THE NEC UNDER 700.12F FOR ALLOWANCE OF CIRCUITING AS
 SHOWN MENTIONS 3 OR MORE CIRCUITS IN ANY SEPARATE AND
 UN-INTERRUPTED LOCATION. PLEASE SEE THE RESPONSE
 MENTIONS COMMENTS WITH RESPECT TO THE *INTENT* OF THE
 CODE WHICH IS UNDERSTOOD HOWEVER THE NUMBER OF CIRCUITS
 AND THE UN-INTERRUPTED SPACES IS NOT PRESENT ON PLANS
 IN SOME OF THESE AREAS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE CIRCUITING ON PLANS FOR ALL EMERGENCY
 LIGHTS AND EXIT LIGHTS.
 PLEASE SEE 700.12F AS THE EM/EXT LIGHTS SHALL BE
 CIRCUITED TO THE LOCAL LIGHTING IN ANY ONE AREA. PLEASE
 COMPLETE ON PLANS.
 THE NOTE ON E-3 FOR EMERGENCY NOTES #1 DOES NOT MEET
 THE CODE AND SECTION AS NOTED.
 PLEASE ADJUST PLANS AND NOTES.
  
 6) NOTE: PLEASE SEE PREVIOUS NOTE #8 WHICH REQUESTED
 ADJUSTMENT FOR WATER HEATER. PLEASE SEE THE RESPONSE
 MENTIONS THE BRANCH CIRCUIT IS SIZED FOR 125% (TYPED AS
 12% IN RESPONSE)(MISPRINT). PLEASE SEE THE NEC CHANGED
 AND THIS INCLUDE THE LOADS IN LOAD CALCULATIONS TO ALSO
 BE SHOWN AND FIGURED AT 125%. THE WATER HEATER LOAD IS
 SHOWN AS 18KW, (ENERGY CALCULATIONS DOES NOT CORRELATE)
 AND THE LOAD SUMMARY DOES NOT INDICATE IF THIS IS THE
 125%. PLEASE SEE FOLLOWING TEXT WHICH HAS BEEN
 EXTRACTED FROM THE NEC COMMENTARY.
 **THE REVISION TO 422.13 SPECIFICALLY IDENTIFIES AN
 ELECTRIC WATER HEATER WITH A STORAGE CAPACITY OF 120
 GAL OR LESS AS A CONTINUOUS LOAD. THIS REVISION
 REQUIRES THE BRANCH CIRCUIT OVERCURRENT DEVICE AND
 CONDUCTORS TO BE SIZED BASED ON 125 PERCENT OF THE
 WATER HEATER NAMEPLATE RATING UNLESS THE OVERCURRENT
 DEVICE AND THE ASSEMBLY IT IS INSTALLED IN ARE LISTED
 TO BE USED AT 100 PERCENT OF ITS CONTINUOUS CURRENT
 RATING. IN ADDITION, FEEDERS AND SERVICES THAT SUPPLY
 WATER HEATER BRANCH CIRCUITS ARE ALSO IMPACTED BY THE
 FACT THAT THIS TYPE OF EQUIPMENT IS CONSIDERED TO BE A
 CONTINUOUS LOAD.**
  
 PLEASE 422.13 AS THE CHANGES IN THE 2005 NEC REQUIRES
 THE WATER HEATER LOAD TO BE FIGURED IN THE CALCULATIONS
 AT 125%.
 PLEASE ADJUST CALCULATIONS.
  
 7) NOTE:THIS NOTE REMAINS AS LOADS AND INFORMATION
 FOR NOTES ABOVE WILL NEED TO BE ADJUSTED.
 PLEASE SEE NO LOAD SUMMARY WAS SUBMITTED INDICATING HOW
 LOADS WERE DERIVED.
 EX: 12 RECEPTS AT 180VA ETC
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE MORE DETAIL ON THE LOAD SUMMARY FOR THE
 LOAD CALCULATIONS.
 PLEASE SEE NOTE ABOVE AS THIS WILL ALSO AFFECT THE
 LOAD.
 PLEASE KNOW AT THIS TIME THE LOADS ARE NOT CLEAR AS NOT
 ALL LOADS ARE FIGURED IN WITH KITCHEN EQUIPMENT AND NOT
 SURE WHERE AND HOW THE OTHER LOADS ARE BEING DONE OR
 FIGURED.
 FBC 106.1.3.5.1.2, 106.1.2. NEC 220.
  
 8) NOTE:SAME NOTE AS NOTE #10 ON PREVIOUS REVIEW. NO
 RESPONSE TO THIS NOTE OR CHANGES TO NOTES ON
 PLANS/PANEL SCHEDULES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW THAT ANY LOCK ON/OFF DEVICES WILL BE
 REQUIRED TO HAVE THE DEVICE BE AN INTEGRAL PART OF THE
 BREAKER. THE DEVICES WHICH *SNAP/CLIP* ON TO BREAKERS
 AND ARE READILY REMOVED OR FALL OF WHEN PANEL COVERS
 ARE REMOVED ARE NOT APPROVED BY THIS AHJ. PLEASE ADJUST
 NOTE TO STATE *THE DEVICE SHALL BE AN INTEGRAL PART OF
 THE BREAKER* OR WORDS TO THAT AFFECT. 110.3, 90.4.
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS. THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
 ONE SET OF ELECTRICAL PLANS AND ENERGY CALCULATIONS ARE
 BEING RETAINED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-07-04 10:44:442007-07-04 10:44:44
 PLANS REMOVED FROM INCOMING. PLANS WILL BE RETURNED TO
 INCOMING WAITING FOR COMM BOARD ONCE ELECTRICLA REVIEW
 IS COMPLETED.