Plan Review Notes
Plan Review Notes For Permit 07030860
Permit Number 07030860
Review Stop B
Sequence Number 2
Notes
Date Text
2007-08-18 14:46:33 
  
  
 MC DONALD?S 9835 OKEECHOBEE BLVD
 2ND REVIEW
  
 BUILDING PLAN REVIEW
 PERMIT: 07030860
 ADD: 9835 OKEECHOBEE BLVD
 CONT: GIL HYATT CONSTRUCTION
 TEL: (954)772-2066
 ?THE CAPITAL CITY OF THE PALM BEACHES?
  
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. PLEASE REMOVE
 VOID SHEETS FROM PLAN AND LOOSELY LAY THEM ON TOP OF
 THE SET OF PLANS MARKED VOID. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENTIS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF,SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 3)FBC 1802.2.1 QUESTIONABLE SOILS, WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL
 IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE ISCLAIMED, THE BUILDING
 OFFICIAL SHALL REQUIRE THAT THE NECESSARY INVESTIGATION
 BE MADE. SUCH INVESTIGATION SHALL COMPLY WITH THE
 PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 4) BUILDING PROVISO:PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUCTION WITH BASE FLOOD
 ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL 6". LOCATED IN A A-O) FLOOD ZONE.
  
 5) COMPLIED.
  
 6)COMPLIED.
  
 7)BUILDING PROVISO: BILCO (ROOF HATCHES) IS CURRENTLY
 UNDER GOING TESTING WITH MIAMI-DADE AND REPORTS WILL BE
 OUT THE SECOND HALF OF 2007. THE CONTRACTOR WILL BE
 REQUIRED TO SUBMIT PRODUCT APPROVALS THAT HAVE
 ACCEPTANCE TO THIS OFFICE BEFORE A CERTIFICATE OF
 OCCUPANCY WILL BE ISSUED. IF AT TIME OF C.O. EITHER AN
 APPROVAL FROM A STATE LISTED AGENCY WILL BE REQUIRED OR
 THE CONTRACTOR SHALL APPLY FOR A LOCAL PRODUCT APPROVAL
 WITH THE CITY OF WEST PALM BEACH WITH THE SAME 10
 CRITERIA AS THE STATE APPROVALS BEFORE A CERTIFICATE OF
 OCCUPANCY WILL BE ISSUED. STATE REQUIREMENTS FOR
 STRUCTURAL COMPONENTS AS PER RULE
 9B-72.010(28), FLORIDA ADMINISTRATIVE CODE AND IS
 SUBJECT TO THE REQUIREMENTS FOR PRODUCT APPROVAL..
  
 8) COMPLIED.
  
 9) 2ND REQUEST, SHEET A5.0- A5.3 ALL SHOW VARIOUS
 DETAILS INDICATING AN ASSEMBLY TYPE 1 OR 2.SOME OF
 THESE WALLS ARE BUILT OUT BUT THE FOUNDATIONS ARE NOT
 NOR IS THERE AN INSPECTION AREA LEFT OPEN.
 IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM). EXCEPTIONS:
 1.PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS
 THAN 5 / 8 INCH (17.1 MM) THICK ADHERED DIRECTLY TO THE
 MASONRY FOUNDATION SIDEWALL.
 2.ACCESS OR VEHICLE RAMPS WHICH RISE TO THE
 INTERIOR FINISH FLOOR ELEVATION FOR THE WIDTH OF SUCH
 RAMPS ONLY.
 3.A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO
 AND GARAGE SLABS AND ENTRY AREAS.
 4.IF THE PATIO HAS BEEN SOIL TREATED FOR TERMITES
 , THE FINISH ELEVATION MAY MATCH THE BUILDING INTERIOR
 FINISH FLOOR ELEVATIONS ON MASONRY CONSTRUCTION ONLY.
 5.MASONRY VENEERS.
  
 DETAIL 2 SHEET A5.3 DOESN?T SHOW A SIDEWALK IN PLACE,
 PLEASE PROVIDE THE DETAIL OF A SIDEWALK AND THE 6?
 SPACE FOR TERMITE INSPECTIONS.
  
 10) COMPLIED WITH PREVIOUS COMMENT. SHEET A5.0 WALL
 SYSTEM 2 INDICATES THE USE OF EXTERIOR PLYWOOD,PLEASE
 REMEMBER THE 6? AIR SPACE REQUIRED FOR THE TERMITE
 INSPECTION, AND THE REQUIREMENT FOR PRESSURE TREATED
 SHEATHING WITHIN 6? OF GRADE.2304.11.2.5 CLEARANCE
 BETWEEN WOOD SIDING AND EARTH ON THE EXTERIOR OF A
 BUILDING SHALL NOT BE LESS THAN 6 INCHES (152 MM)
 EXCEPT WHERE SIDING, SHEATHING AND WALL FRAMING ARE OF
 NATURALLY DURABLE OR PRESERVATIVE-TREATED WOOD.
  
 11) COMPLIED.
  
 12)2ND REQUEST, RESPONSE COMMENCE INDICATE THERE WERE
 PRODUCT APPROVALS SUBMITTED FOR REFRIGERATORS AND
 FREEZERS, COULD NOT LOCATE?
 A4.1 PLANS INDICATE THERE SHALL BE INSTALLED A WALK IN
 COOLER AND FREEZER, NO INFORMATION WAS
 SUBMITTED.2603.4.1.3 WALK-IN COOLERS.
 IN NON-SPRINKLED BUILDINGS, FOAM PLASTIC HAVING A
 THICKNESS THAT DOES NOT EXCEED 4 INCHES (102 MM) AND A
 MAXIMUM FLAME SPREAD INDEX OF 75 IS PERMITTED IN
 WALK-IN COOLERS OR FREEZER UNITS WHERE THE AGGREGATE
 FLOOR AREA DOES NOT EXCEED 400 SQUARE FEET (37 M 2 )
 AND THE FOAM PLASTIC IS COVERED BY A METAL FACING NOT
 LESS THAN 0.032-INCH-THICK (0.81 MM) ALUMINUM OR
 CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL
 THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO
 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A
 THERMAL BARRIER.
  
 13-14) COMPLIED.
  
 15A) THE PRODUCT APPROVALS SUBMITTED ARE UNDER THE 2001
 FBC PLEASE PROVIDE THE APPROVALS THAT ARE CURRENTLY
 UNDER THE 2004 FBC. FL BLD CODE 1609.1.4: COMPONENTS
 & CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS, MISSING REPORTS
 ARE AS FOLLOWS:
 A) OK-FIXED WINDOWS, STOREFRONT- PROVIDE SHUTTER
 REPORT MEETS COMPLIANCE
 B) OK-MULLIONS PROVIDED SHUTTER REPORTS MEETS
 COMPLIANCE
 C) OK- PASS THROUGH WINDOW
 D)OK-GLAZED DOORS PROVIDED SHUTTER REPORTS MEETS
 COMPLIANCE
 E)OK- HOLLOW CORE METAL DOORS
 F)BILCO ROOF HATCH SEE TECHNICAL ADVISORY FROM BCAB
 ? BUILDING PROVISO
 G) TRUSS ANCHORS DID NOT SEE REPORT
 H) STORM SHUTTERS WILL NEED ADDITIONAL INFORMATION
 LISTED BELOW
 I) ROOF ASSEMBLIES : FLAT ROOF ?OK
 ROOF TILE- SEE
 COMMENT# 20
 UNDERLAYMENT FOR ROOF
 TILE- NOT SUBMITTED
 J) PRE-MANUFACTURED A/C STANDS- NOT SUBMITTED SHEET
 M-2 BEVERAGE SYSTEMS CONDENSING
 UNIT
 K)OK- EFIS SYSTEMS WALL SYSTEMS, NOTHING FOR MOLDINGS
  
 15B) THE CONTRACTOR HAS ELECTED TO USE NON-IMPACT
 GLAZING IN THE EXTERIOR DOORS AND WINDOWS.SHEET A4.1
 AND 5.0 DO NOT INDICATE OR HAVE BACKING TO SUPPORT
 STORM PANELS
 THE CONTRACTOR ELECTED TO USE. NOTE THE PRODUCT
 APPROVAL TECHNICAL SHEETS (TYPES OF WALL)
 CONFIGURATIONS THAT STORM PANELS WERE TESTED TO UNDER
 THE LARGE MISSILE TESTING. BOTH THE PRODUCT APPROVAL
 AND WALL DETAILS WILL NEED TO BE CORRELATED, HIGHLIGHT
 THE PRODUCT APPROVAL WALL SECTIONS TO BE USED AND
 PROVIDE WALL DETAILS ON THE ARCHITECTURAL SHEETS THAT
 WILL REFLECT THESE SAME DETAILS. NOTE IF WOOD BACKING
 IS USED THE SHEETS 9-12 DEAL WITH WOOD TYPE BACKED
 STRUCTURES. A NOTE OF CAUTION, NONE OF THE PRODUCT
 APPROVALS WERE TESTED WITH A CRUSHABLE INSULATION
 BACKING!
  
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED FOR ALL
 NON-IMPACT GLAZING. FBC 1606.1.4.
  
 FL BLD CODE 2001 SECTION 103.6, 1606.1.4, 1707.4 &
 3401.7.2.4.PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK NUMBERS, UNIT
 SPANS/WIDTHS, UNIT STORM BAR REINFORCING REQUIREMENTS,
 WALL PRESSURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATIONTO FACILITATE
 PLAN REVIEW AND PERMIT ISSUANCE.
  
 INDICATE ON THE FLOOR PLAN THE LOCATION WHERE STORM
 SHUTTERS WILL BE SECURED & STORED. 106.1.2*
  
  
  
  
 16)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
 WWW.FLORIDABUILDING.ORG
  
 17) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 18-19) COMPLIED.
  
 20) 2ND REQUEST, FOR THE MISSION "S" ROOF TILE PLEASE
 CIRCLE WHICH FASTENING METHOD WILL BE USED TO CHECK
 UPLIFT FACTORS.
  
 21) PLEASE PROVIDE HIP AND RIDGE ATTACHMENT FOR THE
 MISSION "S" CONCRETE RIDGE TILE AND TYPE OF HIP OR
 RIDGE BOARD TO BE USED AND THE TYPE OF FASTENERS FOR
 THE HIP BOARD. 1507.3.7 ATTACHMENT.
 CLAY AND CONCRETE ROOF TILES SHALL BE FASTENED IN
 ACCORDANCE WITH SECTION 1609 OR IN ACCORDANCE WITH FRSA
 /RTI INSTALLATION MANUAL.
 1507.3.8 APPLICATION.
 TILE SHALL BE APPLIED ACCORDING TO THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS OR RECOMMENDATIONS OF THE
 FRSA /RTI 07320-05.
  
 22) 2ND REQUEST PLEASE PROVIDE EFIS MOLDING SYSTEM
 INFORMATION FOR ADHERING MOLDING TO THE WALL. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 23)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 24 ) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDESBUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATE FROM A LICENSED ENGINEER SHALL BE SUBMITTED
 TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE
 FINAL INSPECTION.
  
 25)109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER REMOVED FROM THE
 CONSTRUCTION SITE OR SECURED IN SUCH A MANNER AS TO
 MINIMIZE THE DANGER OF SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS CAUSING DAMAGE TO PERSONS OR
 PROPERTY FROM HIGH WINDS. ANY PERSONS WHO FAILS TO
 COMPLY TO REMOVE OR SECURE THE CONSTRUCTION MATERIALS
 EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO SECTION 113
 OF THIS CHAPTER.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  