| Date |
Text |
| 2007-05-04 16:58:08 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | WEST PALM BEACH MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT 1 OF 1 SHALL BE SIGNED, SEALED, & DATED PER |
| | SECTION 106.1 AND SHALL COMPLY WITH FAC 61G1-16.004 AS |
| | WELL AS FS 481.219 & 481.2055. |
| | |
| | 2. SHT 2 OF 2 SHALL BE SIGNED, SEALED, & DATED PER |
| | SECTION 106.1 AND FS 472.025. |
| | |
| | 3. SHT C-1 THE BUSINESS NUMBER IS REQUIRED IN THE TITLE |
| | BLOCK OF THE DESIGN PROFESSIONAL. (SEE ATTACHED SHEET). |
| | FAC 61G15-23.002 & FS 471.025. |
| | |
| | 4. SHT C-1 SHEET INDEX INDICATES SHTS C-10, L-1, L-2, |
| | IRR-1 & S-3. THESE SHEETS HAVE NOT BEEN SUBMITTED. |
| | PLEASE CORRELATE THE SHEET INDEX WITH THE SHEETS |
| | SUBMITTED. |
| | |
| | 5. SHTS C-1 THRU C-9B. THE ADDRESS IN THE TITLE BLOCK |
| | DOES NOT REFLECT THE ADDRESS OF RECORD ON FILE IN THE |
| | STATE DBPR WEBSITE. PLEASE UPDATE THE DBPR WEBSITE OR |
| | THE TITLE BLOCK. FAC 61G1-16.004(1). (SEE ATTACHED |
| | SHEET). |
| | |
| | 6. SHT C-7 2-WAY CLEANOUTS ARE REQUIRED PRIOR TO, |
| | BETWEEN & AT THE EXIT OF EACH GREASE INTERCEPTOR. |
| | UTILITY STANDARD. (SEE ATTACHED SHEET). |
| | |
| | 7.SHTS C-8, C-9, C-9A & C-9B ARE NOT SIGNED & SEALED. |
| | THE DATE THAT THE SEAL AND SIGNATURE ARE AFFIXED TO THE |
| | SHEETS SHALL BE ENTERED BELOW THE SIGNATURE. FAC |
| | 61G1-15.002(1)(2) & FS 471.025. |
| | |
| | 8. SHTS C-1 THRU C-7 THE SIGNATURE OF THE ENGINEER OF |
| | RECORD IS REQUIRED ON EACH SHEET. IT APPEARS THAT |
| | INITIALS HAVE BEEN USED. IF THIS IS INDEED THE LEGAL |
| | SIGNATURE OF THE ENGINEER, A SIGNED, SEALED, DATED, |
| | NOTORIZED LETTER SHALL BE SUBMITTED INDICATING THE |
| | LEGAL SIGNATURE OF THE ENGINEER FOR OUR FILE. FAC |
| | 61G1-15.02(1)(2) & FS 471.025. |
| | |
| | 9, SHT A1.4 SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS & TABLES. SHOW THE SQUARE FOOTAGE OF EACH |
| | AREA TO BE DRAINED WITH 1/2 AREA OF ALL VERTICAL WALLS |
| | INCLUDING PARAPETS AS WELL AS ANY ROOF AREA THAT WILL |
| | BE DRAINED ON TO THE ROOF AREA FROM ABOVE. |
| | |
| | 10. ROUTE PLANS TO THE DEPT. OF BUSINESS REGULATION, |
| | HOTEL AND RESTURANT DIVISION FOR REVIEW PRIOR TO |
| | RESUBMITTING TO THE CITY. ATTACH THE TWO PAGE |
| | "WORKSHEET" TO EACH SET OF PLANS STAMPED BY DBPR. PHONE |
| | NUMBER (850)487-1395. SECTION 102.2.1. |
| | |
| | 11. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE |
| | ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE CONTACT RODNEY |
| | COMPO (561) 822-2272 OR CALVIN WILLIAMS (561) 822-2284. |
| | THEIR FAX NUMBER IS (561) 822-2287 AND THEIR E-MAILS |
| | ARE [email protected], OR [email protected]. |
| | |
| | 12. SHT A4.0 DETAIL #6 INDICATES THE TOILET PAPER |
| | DISPENSER AT 15" MINIMUM. THE MINIMUM TO THE CENTERLINE |
| | OF THE DISPENSER IS 19" PLEASE INDICATE ON THE PLAN. |
| | SEE FIG. 11-29B. |
| | |
| | 13. SHT A4.0 THE LAV CALLS FOR A COMBINATION FAUCET. |
| | MORE INFORMATION IS REQUIRED. PLEASE SUBMIT MANUF. |
| | SPECIFICATION SHEETS FOR THE FAUCET SHOWING COMPLIANCE |
| | WITH SECTION 11-4.19.5. |
| | |
| | 14. SHT P1.0PLUMBING KEY NOTE #8. CHANGE FROM FLOOR |
| | DRAIN TO FLOOR SINK. FLOOR DRAINS ARE NOT APPROVED |
| | INDIRECT WASTE RECEPTORS. SECTION 802.3. |
| | |
| | 15. ALL MECHANICAL & PLUMBING SHEETS. THE SIGNATURE OF |
| | THE ENGINEER OF RECORD IS REQUIRED ON EACH SHEET. IT |
| | APPEARS THAT INITIALS HAVE BEEN USED. IF THIS IS INDEED |
| | THE LEGAL SIGNATURE OF THE ENGINEER, A SIGNED, SEALED, |
| | DATED, NOTORIZED LETTER SHALL BE SUBMITTED INDICATING |
| | THE LEGAL SIGNATURE OF THE ENGINEER FOR OUR FILE. FAC |
| | 61G1-15.02(1)(2) & FS 471.025. |
| | |
| | 16. SHT P2.0 INDICATES A FILTERED WATER SYSTEM. THE |
| | WATER FILTER SHALL COMPLY WITH SECTION 611.1 AND NSF |
| | 42. PLEASE SUBMIT MANUF. SPECIFICATION SHEETS SHOWING |
| | COMPLIANCE. |
| | |
| | 17. SHT P2.0 PLUMBING KEY NOTES #12. MORE INFORMATION |
| | IS REQUIRED. SECTION 106.1.2. PLEASE INDICATE HOW THE |
| | COLD WATER WILL BE TREATED. SUBMIT MANUF. SPECIFICATION |
| | SHEETS FOR THE PROCESS & SHOW COMPLIANCE WITH NSF. ALL |
| | POTABLE WATER LINES SHALL BE INSTALLED BY A LICENSED |
| | PLUMBER. |
| | |
| | 18. SHT P2.0 AIR CHAMBERS ARE NOT APPROVED. DELETE |
| | REFERENCE. SECTION 604.9 & PDI-WH 210. |
| | |
| | 19. SHT P4.0 THREE FD-1 FIXTURES ARE NOT APPROVED AS |
| | INDIRECT WASTE RECEPTORS SECTION 802.3. FLOOR SINKS |
| | SHALL BE USED FOR ALL EXCEPT A HUB DRAIN CAN BE USED |
| | FOR THE CONDENSATE DRAIN FOR THE FREEZER PER SECTION |
| | 802.3.2. |
| | |
| | 20. SHT P5.0 AIR CHAMBERS ARE NOT APPROVED. DELETE FROM |
| | THE RISER DIAGRAM. SECTION 604.9 & PDI-WH 201. WATER |
| | HAMMER ARRESTORS ARE REQUIRED AT QUICK CLOSING VALVES, |
| | (ICE MACHINE, DISH WASHER, WASH MACHINE). WATER HAMMER |
| | ARRESTORS SHALL BE LOCATED NEAR THE FIXTURE IN AN |
| | "EFFECTIVE RANGE" NOT IN THE CEILING. PDI-WH 201 AND |
| | MANUF. INSTALLATION INSTRUCTIONS. |
| | |
| | 21. SHT P5.0 A FULL OPEN VALVE IS REQUIRED ON THE WATER |
| | SUPPLY PIPE TO THE WATER HEATER. SECTION 606.1(7). |
| | |
| | 22. SHT P5.0 RISER DIAGRAM. PLEASE IDENTIFY THE SYMBOLS |
| | ON THE WATER SUPPLY LINES TO THE TRASH AREA AND TO THE |
| | HOSE BIBB ON THE ROOF. THE SYMBOL IS NOT INDICATED ON |
| | THE PLUMBING LEGEND SHT P1.0. SECTION 106.1.1. |
| | |
| | 23. SHT P5.0 THE 2" WATER MAIN IS SHOWN REDUCED TO 1/2" |
| | AT THE TOP OF THE FIRST RISER DOWNSTREAM OF THE |
| | SUB-METER. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 24. SHT P6.1 PLUMBING FIXTURE & PIPE SIZING SCHEDULE. |
| | FD-1 FUNNEL FLOOR DRAINS ARE NOT APPROVED FOR INDIRECT |
| | WASTE. PLEASE DELETE FROM THE SCHEDULE. SECTION 802.3. |
| | |
| | 25, SUBMIT A STORM PIPING RISER DIAGRAM IN ISOMETRIC |
| | FORM. SECTION 106..3.5.1.3(7)(13). |
| | |
| | 26. SHT P7.0 FLOOR SINK DETAIL. THE TOP OF THE FLOOR |
| | SINK SHALL BE 1" ABOVE FINISH FLOOR TO PREVENT THE |
| | FLOOR SINK BEING USED AS A FLOOR DRAIN. |
| | |
| | 27. SHT P8.0 SEE ATTACHED SHEET FOR AN APPROVED UTILITY |
| | STANDARD FOR THE GREASE INTERCEPTOR. |
| | |
| | 28. SHT P8.0 NOTE #1 CONCRETE GREASE INTERCEPTORS ARE |
| | REQUIRED. POLYETHYLENE TANKS ARE NOT APPROVED. CITY |
| | CODE SECTION 90-124(7)(F). |
| | |
| | 29. SUBMIT A PLUMBING ROOF PLAN SHOWING ALL VENT |
| | LOCATIONS ON THE ROOF. SECTION 106.2.1 |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | AND RESUBMITTING 1 SET OF PLANS FROM THE |
| | PREVIOUS REVIEW WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |