Plan Review Notes
Plan Review Notes For Permit 07030860
Permit Number 07030860
Review Stop P
Sequence Number 1
Notes
Date Text
2007-05-04 16:58:08DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 WEST PALM BEACH MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT 1 OF 1 SHALL BE SIGNED, SEALED, & DATED PER
 SECTION 106.1 AND SHALL COMPLY WITH FAC 61G1-16.004 AS
 WELL AS FS 481.219 & 481.2055.
  
 2. SHT 2 OF 2 SHALL BE SIGNED, SEALED, & DATED PER
 SECTION 106.1 AND FS 472.025.
  
 3. SHT C-1 THE BUSINESS NUMBER IS REQUIRED IN THE TITLE
 BLOCK OF THE DESIGN PROFESSIONAL. (SEE ATTACHED SHEET).
 FAC 61G15-23.002 & FS 471.025.
  
 4. SHT C-1 SHEET INDEX INDICATES SHTS C-10, L-1, L-2,
 IRR-1 & S-3. THESE SHEETS HAVE NOT BEEN SUBMITTED.
 PLEASE CORRELATE THE SHEET INDEX WITH THE SHEETS
 SUBMITTED.
  
 5. SHTS C-1 THRU C-9B. THE ADDRESS IN THE TITLE BLOCK
 DOES NOT REFLECT THE ADDRESS OF RECORD ON FILE IN THE
 STATE DBPR WEBSITE. PLEASE UPDATE THE DBPR WEBSITE OR
 THE TITLE BLOCK. FAC 61G1-16.004(1). (SEE ATTACHED
 SHEET).
  
 6. SHT C-7 2-WAY CLEANOUTS ARE REQUIRED PRIOR TO,
 BETWEEN & AT THE EXIT OF EACH GREASE INTERCEPTOR.
 UTILITY STANDARD. (SEE ATTACHED SHEET).
  
 7.SHTS C-8, C-9, C-9A & C-9B ARE NOT SIGNED & SEALED.
 THE DATE THAT THE SEAL AND SIGNATURE ARE AFFIXED TO THE
 SHEETS SHALL BE ENTERED BELOW THE SIGNATURE. FAC
 61G1-15.002(1)(2) & FS 471.025.
  
 8. SHTS C-1 THRU C-7 THE SIGNATURE OF THE ENGINEER OF
 RECORD IS REQUIRED ON EACH SHEET. IT APPEARS THAT
 INITIALS HAVE BEEN USED. IF THIS IS INDEED THE LEGAL
 SIGNATURE OF THE ENGINEER, A SIGNED, SEALED, DATED,
 NOTORIZED LETTER SHALL BE SUBMITTED INDICATING THE
 LEGAL SIGNATURE OF THE ENGINEER FOR OUR FILE. FAC
 61G1-15.02(1)(2) & FS 471.025.
  
 9, SHT A1.4 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS & TABLES. SHOW THE SQUARE FOOTAGE OF EACH
 AREA TO BE DRAINED WITH 1/2 AREA OF ALL VERTICAL WALLS
 INCLUDING PARAPETS AS WELL AS ANY ROOF AREA THAT WILL
 BE DRAINED ON TO THE ROOF AREA FROM ABOVE.
  
 10. ROUTE PLANS TO THE DEPT. OF BUSINESS REGULATION,
 HOTEL AND RESTURANT DIVISION FOR REVIEW PRIOR TO
 RESUBMITTING TO THE CITY. ATTACH THE TWO PAGE
 "WORKSHEET" TO EACH SET OF PLANS STAMPED BY DBPR. PHONE
 NUMBER (850)487-1395. SECTION 102.2.1.
  
 11. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE
 ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE CONTACT RODNEY
 COMPO (561) 822-2272 OR CALVIN WILLIAMS (561) 822-2284.
 THEIR FAX NUMBER IS (561) 822-2287 AND THEIR E-MAILS
 ARE [email protected], OR [email protected].
  
 12. SHT A4.0 DETAIL #6 INDICATES THE TOILET PAPER
 DISPENSER AT 15" MINIMUM. THE MINIMUM TO THE CENTERLINE
 OF THE DISPENSER IS 19" PLEASE INDICATE ON THE PLAN.
 SEE FIG. 11-29B.
  
 13. SHT A4.0 THE LAV CALLS FOR A COMBINATION FAUCET.
 MORE INFORMATION IS REQUIRED. PLEASE SUBMIT MANUF.
 SPECIFICATION SHEETS FOR THE FAUCET SHOWING COMPLIANCE
 WITH SECTION 11-4.19.5.
  
 14. SHT P1.0PLUMBING KEY NOTE #8. CHANGE FROM FLOOR
 DRAIN TO FLOOR SINK. FLOOR DRAINS ARE NOT APPROVED
 INDIRECT WASTE RECEPTORS. SECTION 802.3.
  
 15. ALL MECHANICAL & PLUMBING SHEETS. THE SIGNATURE OF
 THE ENGINEER OF RECORD IS REQUIRED ON EACH SHEET. IT
 APPEARS THAT INITIALS HAVE BEEN USED. IF THIS IS INDEED
 THE LEGAL SIGNATURE OF THE ENGINEER, A SIGNED, SEALED,
 DATED, NOTORIZED LETTER SHALL BE SUBMITTED INDICATING
 THE LEGAL SIGNATURE OF THE ENGINEER FOR OUR FILE. FAC
 61G1-15.02(1)(2) & FS 471.025.
  
 16. SHT P2.0 INDICATES A FILTERED WATER SYSTEM. THE
 WATER FILTER SHALL COMPLY WITH SECTION 611.1 AND NSF
 42. PLEASE SUBMIT MANUF. SPECIFICATION SHEETS SHOWING
 COMPLIANCE.
  
 17. SHT P2.0 PLUMBING KEY NOTES #12. MORE INFORMATION
 IS REQUIRED. SECTION 106.1.2. PLEASE INDICATE HOW THE
 COLD WATER WILL BE TREATED. SUBMIT MANUF. SPECIFICATION
 SHEETS FOR THE PROCESS & SHOW COMPLIANCE WITH NSF. ALL
 POTABLE WATER LINES SHALL BE INSTALLED BY A LICENSED
 PLUMBER.
  
 18. SHT P2.0 AIR CHAMBERS ARE NOT APPROVED. DELETE
 REFERENCE. SECTION 604.9 & PDI-WH 210.
  
 19. SHT P4.0 THREE FD-1 FIXTURES ARE NOT APPROVED AS
 INDIRECT WASTE RECEPTORS SECTION 802.3. FLOOR SINKS
 SHALL BE USED FOR ALL EXCEPT A HUB DRAIN CAN BE USED
 FOR THE CONDENSATE DRAIN FOR THE FREEZER PER SECTION
 802.3.2.
  
 20. SHT P5.0 AIR CHAMBERS ARE NOT APPROVED. DELETE FROM
 THE RISER DIAGRAM. SECTION 604.9 & PDI-WH 201. WATER
 HAMMER ARRESTORS ARE REQUIRED AT QUICK CLOSING VALVES,
 (ICE MACHINE, DISH WASHER, WASH MACHINE). WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
  
 21. SHT P5.0 A FULL OPEN VALVE IS REQUIRED ON THE WATER
 SUPPLY PIPE TO THE WATER HEATER. SECTION 606.1(7).
  
 22. SHT P5.0 RISER DIAGRAM. PLEASE IDENTIFY THE SYMBOLS
 ON THE WATER SUPPLY LINES TO THE TRASH AREA AND TO THE
 HOSE BIBB ON THE ROOF. THE SYMBOL IS NOT INDICATED ON
 THE PLUMBING LEGEND SHT P1.0. SECTION 106.1.1.
  
 23. SHT P5.0 THE 2" WATER MAIN IS SHOWN REDUCED TO 1/2"
 AT THE TOP OF THE FIRST RISER DOWNSTREAM OF THE
 SUB-METER. PLEASE CLARIFY. SECTION 106.1.1.
  
 24. SHT P6.1 PLUMBING FIXTURE & PIPE SIZING SCHEDULE.
 FD-1 FUNNEL FLOOR DRAINS ARE NOT APPROVED FOR INDIRECT
 WASTE. PLEASE DELETE FROM THE SCHEDULE. SECTION 802.3.
  
 25, SUBMIT A STORM PIPING RISER DIAGRAM IN ISOMETRIC
 FORM. SECTION 106..3.5.1.3(7)(13).
  
 26. SHT P7.0 FLOOR SINK DETAIL. THE TOP OF THE FLOOR
 SINK SHALL BE 1" ABOVE FINISH FLOOR TO PREVENT THE
 FLOOR SINK BEING USED AS A FLOOR DRAIN.
  
 27. SHT P8.0 SEE ATTACHED SHEET FOR AN APPROVED UTILITY
 STANDARD FOR THE GREASE INTERCEPTOR.
  
 28. SHT P8.0 NOTE #1 CONCRETE GREASE INTERCEPTORS ARE
 REQUIRED. POLYETHYLENE TANKS ARE NOT APPROVED. CITY
 CODE SECTION 90-124(7)(F).
  
 29. SUBMIT A PLUMBING ROOF PLAN SHOWING ALL VENT
 LOCATIONS ON THE ROOF. SECTION 106.2.1
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 AND RESUBMITTING 1 SET OF PLANS FROM THE
 PREVIOUS REVIEW WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  