2007-04-21 09:28:00-----------------DENIED-------------------
  
 FBC 2004 CODE FAMILY W/2006 REVISIONS.
 FBC 2004 CH 1 AS AMENDED BY THE CITY OF WEST PALM
 BEACH
  
 THE FOLLOWING COMMENTS ARE ORGANIZED BY PAGE # FOR
 REFERENCE. AREAS RELATED TO REVIEW COMMENTS HAVE BEEN
 MARKED ON PLAN (1 SET) WHEN PRACTICAL.
  
 1. A1.4 NOTE #5: PLEASE REFERENCE CORRECT CODE BODY,
 FBC 2004, AND CODE SECTION, 1509.7.
  
 2. A5.4 DETAIL #13: DETAIL SHOWS TOP OF KITCHEN EXHAUST
 FAN MIN. 40" ABOVE LOW SIDE OF PITCHED ROOF. THIS WOULD
 MEAN THE ELEVATION COULD BE LESS THAN 40" FROM THE HIGH
 SIDE OF THE ROOF. PLEASE SHOW MIN. 40" FROM THE HIGH
 SIDE TO SHOW COMPLIANCE WITH FBC,M 506.3.12.1.
  
 3. A5.4 DETAIL #13: EXHAUST OUTLETS SHALL BE LOCATED
 NOT LESS THAN 10' HORIZONTALLY FROM PARTS OF THE SAME
 OR CONTIGUOUS BUILDINGS PER FBC,M 506.3.12.3. THE
 EXCEPTION UNDER 506.5.5 ALLOWS THE FAN TO BE WITHIN 2'
 OF PARAPET TYPE WALLS IF THE WALL IS NOT HIGHER THAN
 THE DISCHARGE OPENING.
  
 4. M1.0 NOTE #2 AND MECH. GENERAL NOTE #22 (M3.0) AND
 CEILING DIFFUSER RUNOUT DETAIL (M3.0) ARE IN CONFLICT
 WITH MECH. GENERAL NOTE #18. PLEASE COORDINATE
 DRAWINGS. FBC 106.1.1.
  
 5. M3.0 MECH. GENERAL NOTE #17: PLEASE PROVIDE DETAIL
 FOR SUPPORT OF DIFFUSERS, REGISTERS AND GRILLS IF THEY
 ARE NOT TO BE SUPPORTED BY CEILING AS SHOWN IN THE
 DIFFUSER RUNOUT DETAIL ON SAME PAGE.
  
 6. M3.0 MECH. GENERAL NOTE #19: DOES THIS NOTE APPLY TO
 THE MAIN BRANCHES FROM SUPPLY PLENUMS ON RTU-1 AND
 RTU-3?
  
 7. M3.0 ROOFTOP A/C UNIT NOTE #3: HOW WILL A 12" TALL
 FACTORY ROOF CURB ALL FOR MIN. *" ABOVE FINISHED ROOF
 WITH A BUILT-UP ROOF SYSTEM EXCEEDING 4" THICK AS
 INDICATED BY NOTES ON PG A1.4?
  
 8. ARCHITECTURAL AND STRUCTURAL PLANS CONTAIN DIFFERENT
 DETAIL DRAWINGS FOR SECURING ROOFTOP EQUIPMENT AND
 CURBS. PLEASE COORDINATE DRAWINGS. PLEASE HAVE THE
 DESIGNER RESPONSIBLE FOR STRUCTURAL DESIGN SHOW
 COMPLIANCE WITH FBC,M 301.13 AND FBC CH 16, SHOWING
 ROOFTOP EQUIPMENT ATTACHMENTS TO BE DESIGNED TO MEET
 140 MPH WIND LOADS.
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR HOODS, HOOD
 SUPPRESSION SYSTEMS AND WALK-IN COOLERS/FREEZERS.
  