| 2007-04-21 09:28:00 | -----------------DENIED------------------- |
| | |
| | FBC 2004 CODE FAMILY W/2006 REVISIONS. |
| | FBC 2004 CH 1 AS AMENDED BY THE CITY OF WEST PALM |
| | BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE ORGANIZED BY PAGE # FOR |
| | REFERENCE. AREAS RELATED TO REVIEW COMMENTS HAVE BEEN |
| | MARKED ON PLAN (1 SET) WHEN PRACTICAL. |
| | |
| | 1. A1.4 NOTE #5: PLEASE REFERENCE CORRECT CODE BODY, |
| | FBC 2004, AND CODE SECTION, 1509.7. |
| | |
| | 2. A5.4 DETAIL #13: DETAIL SHOWS TOP OF KITCHEN EXHAUST |
| | FAN MIN. 40" ABOVE LOW SIDE OF PITCHED ROOF. THIS WOULD |
| | MEAN THE ELEVATION COULD BE LESS THAN 40" FROM THE HIGH |
| | SIDE OF THE ROOF. PLEASE SHOW MIN. 40" FROM THE HIGH |
| | SIDE TO SHOW COMPLIANCE WITH FBC,M 506.3.12.1. |
| | |
| | 3. A5.4 DETAIL #13: EXHAUST OUTLETS SHALL BE LOCATED |
| | NOT LESS THAN 10' HORIZONTALLY FROM PARTS OF THE SAME |
| | OR CONTIGUOUS BUILDINGS PER FBC,M 506.3.12.3. THE |
| | EXCEPTION UNDER 506.5.5 ALLOWS THE FAN TO BE WITHIN 2' |
| | OF PARAPET TYPE WALLS IF THE WALL IS NOT HIGHER THAN |
| | THE DISCHARGE OPENING. |
| | |
| | 4. M1.0 NOTE #2 AND MECH. GENERAL NOTE #22 (M3.0) AND |
| | CEILING DIFFUSER RUNOUT DETAIL (M3.0) ARE IN CONFLICT |
| | WITH MECH. GENERAL NOTE #18. PLEASE COORDINATE |
| | DRAWINGS. FBC 106.1.1. |
| | |
| | 5. M3.0 MECH. GENERAL NOTE #17: PLEASE PROVIDE DETAIL |
| | FOR SUPPORT OF DIFFUSERS, REGISTERS AND GRILLS IF THEY |
| | ARE NOT TO BE SUPPORTED BY CEILING AS SHOWN IN THE |
| | DIFFUSER RUNOUT DETAIL ON SAME PAGE. |
| | |
| | 6. M3.0 MECH. GENERAL NOTE #19: DOES THIS NOTE APPLY TO |
| | THE MAIN BRANCHES FROM SUPPLY PLENUMS ON RTU-1 AND |
| | RTU-3? |
| | |
| | 7. M3.0 ROOFTOP A/C UNIT NOTE #3: HOW WILL A 12" TALL |
| | FACTORY ROOF CURB ALL FOR MIN. *" ABOVE FINISHED ROOF |
| | WITH A BUILT-UP ROOF SYSTEM EXCEEDING 4" THICK AS |
| | INDICATED BY NOTES ON PG A1.4? |
| | |
| | 8. ARCHITECTURAL AND STRUCTURAL PLANS CONTAIN DIFFERENT |
| | DETAIL DRAWINGS FOR SECURING ROOFTOP EQUIPMENT AND |
| | CURBS. PLEASE COORDINATE DRAWINGS. PLEASE HAVE THE |
| | DESIGNER RESPONSIBLE FOR STRUCTURAL DESIGN SHOW |
| | COMPLIANCE WITH FBC,M 301.13 AND FBC CH 16, SHOWING |
| | ROOFTOP EQUIPMENT ATTACHMENTS TO BE DESIGNED TO MEET |
| | 140 MPH WIND LOADS. |
| | |
| | NOTE: SEPARATE PERMITS ARE REQUIRED FOR HOODS, HOOD |
| | SUPPRESSION SYSTEMS AND WALK-IN COOLERS/FREEZERS. |
| | |