Plan Review Notes
Plan Review Notes For Permit 07030860
Permit Number 07030860
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-05-21 16:46:54*****DENIED*****
  
  
 01.THE ACTUAL NUMERICAL ADDRESS OF THE PROJECT SITE
 SHALL BE IN TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 02.NFPA 101, 2003 EDITION AND THE FLORIDA FIRE
 PREVENTION CODE 2004 EDITION SHALL BE REFERENCED.
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 04.PLEASE SHOW LOCATION OF THE NEAREST FIRE
 HYDRANT(S) TO THIS PROJECT.
  
 05.ON THE APPROPIATE EXTERIOR ELEVATION (SHEET A2.0},
 DISPLAY THE NUMERICAL ADDRESS.AS PER WEST PALM BEACH
 CODE, ADDRESS NUMBERS SHALL BE NO LESS THAN 6" IN
 HEIGHT AND NO LESS THAN 1" IN WIDTH.
  
 06.BASED UPON THE NEW ASSEMBLY OCCUPANCY
 CLASSIFICATION, DECLARE THE INTERIOR FINISH MATERIAL
 CLASSIFICATION FOR WALLS AND CEILINGS IN THE EXITS,
 EXIT ACCESS CORRIDORS, AND ALL OTHER AREAS.BE
 SPECIFIC AS TO CLASS A, CLASS B, OR CLASS C.
  
 07.COOKING EQUIPMENT SHALL BE PROTECTED IN ACCORDANCE
 WITH NFPA 96 2001 EDITION.
  
 08.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 INSTALLATION OF THE COOKING HOOD AND THE COOKING HOOD'S
 SUPPRESSION SYSTEM.
  
 09.SHOW LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFIES THE 75' TRAVEL
 DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722