Plan Review Notes
Plan Review Notes For Permit 07030860
Permit Number 07030860
Review Stop E
Sequence Number 1
Notes
Date Text
2007-04-03 10:32:24** UNSAT**
  
 PROPOSED MCDONALDS
 9835 OKEECHOBEE BLVD.
  
 1) NOTE: PLEASE BE SURE ONCE THE ADDRESSED IS VERIFIED
 THAT THE TITLE BLOCKS ON PLANS ARE CORRECTED TO INCLUDE
 THE ADDRESS LOCATION. AT THIS TIME THE ADDRESS IN OUR
 SYSTEM IS BEING SHOWN AS 9835 OKEECHOBEE. ONE ANY SHEET
 OF PLANS WHICH DOES NOT HAVE TO HAVE CORRECTIONS MADE,
 THEN THE ADDRESS CAN BE ADDED TO THE EXISTING SHEET.
 THIS WOULD ONLY BE FOR ANY SHEETS WHICH DO NOT NEED TO
 BE CHANGED OR CORRECTED.
 61G1-16.004, 61G15-23.002
  
 2) NOTE: PLEASE SEE THAT AS OF DECEMBER 8TH, 2006 THE
 STATE OF FLORIDA ADOPTED NEW CODES AS FOLLOWS. 2004 FBC
 W/2006 REVISIONS.
 2005 NFPA-70
 OTHER CODES RELEVANT AND TO BE PLACED ON PLANS. 2003
 NFPA-101
 2002 NFPA-72
  
 ** PLEASE SEE PLANS AS THERE ARE LOCATIONS WHICH LIST A
 2004 ELECTRICAL CODE.
 PLEASE SEE NUMEROUS LOCATIONS ON PLANS WHICH INDICATE
 THE 2002 NEC/NFPA-70.
 PLEASE SEE SEVERAL CODE SECTIONS AS REFLECTED ON PLANS
 FOR ARTICLES FROM THE 2002 NEC, WHERE THE CODE SECTIONS
 HAVE CHANGED IN THE 2005 NEC.
 *EXAMPLE, SEE LOAD CALCULATIONS, GROUNDING DETAILS,
 ETC.
  
 3) NOTE: PLEASE SEE THE CERTIFICATE OF AUTHORIZATION
 NUMBER FOR ENGINEERING FIRM *DIAMONDBACK ENGINEERING*
 IS CURRENTLY DELINQUENT WITH THE STATE OF FLORIDA. THIS
 HAS BEEN PRINTED AND IS ATTACHED TO NOTES AS OF
 4/2/07.
 PLEASE KNOW THIS IS ALSO KNOWN AS THE EB/ ENGINEERING
 BUSINESS LICENSE NUMBER.
 FS 471.023, FAC 61G15-23.002
  
 4) NOTE: PLEASE SEE 2004 FBC W/ 2006 REVISION FOR
 CHAPTER 13. PLEASE SEE 13-415.1.AB.1.1, 13-415.2 AS THE
 ENERGY CALCULATIONS DO NOT COORDINATE WITH THE
 ELECTRICAL PLANS FOR THE FIXTURES, AMOUNT OF FIXTURES,
 ETC.
 PLEASE SEE PLANS INDICATE OVER 100PLUS FIXTURES, AND
 CALCULATIONS ONLY INDICATE 30?
 PLEASE SEE NO INFORMATION ENTERED FOR EXTERIOR
 LIGHTING, YET PLANS INDICATE NUMEROUS EXTERIOR LIGHTS?
 PLEASE SEE THE WATTAGE AND FIXTURES DO NOT CORRELATE.
 ** THERE ARE SEVERAL ITEMS NOT LISTED AND A COMPLETE
 REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT THIS
 TIME.
  
 5) NOTE: PLEASE SEE 2005 NEC 210.8B3 FOR ALL 15/20AMP,
 120V RECEPTACLES IN KITCHEN/FOOD PREPARATION AREAS TO
 BE GFI/GFI PROTECTED.
 PLEASE SEE THE SECTION OF CODE NOTED ON PLANS IS NOT
 COMPLETE WITH THE SECTION AS NOTED.
 PLEASE ALSO SEE THAT NOT ALL CIRCUITS AS REQUIRED
 INDICATE THE PROTECTION.
 PLEASE SEE SOME CIRCUITS INDICATE PROTECTION WHERE NOT
 REQUIRED?
 PLEASE COORDINATE.
  
 6) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK FOR THIS NEW BUILDING SHALL INCLUDE ALL LABOR AND
 MATERIALS. PLEASE KNOW THAT EVEN EQUIPMENT SUCH AS
 KITCHEN, A/C ETC WHICH MAY BE OWNER SUPPLIED IS TO BE
 INCLUDED IN VALUE.
 FBC 108.3.
  
 7) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS FOR ALL
 EMERGENCY LIGHTS AND EXIT LIGHTS.
 PLEASE SEE 700.12E AS THE EM/EXT LIGHTS SHALL BE
 CIRCUITED TO THE LOCAL LIGHTING IN ANY ONE AREA. PLEASE
 COMPLETE ON PLANS.
 THE NOTE ON E-3 FOR EMERGENCY NOTES #1 DOES NOT MEET
 THE CODE AND SECTION AS NOTED.
 PLEASE ADJUST PLANS AND NOTES.
  
 8) NOTE: PLEASE 422.13 AS THE CHANGES IN THE 2005 NEC
 REQUIRES THE WATER HEATER LOAD TO BE FIGURED IN THE
 CALCULATIONS AT 125%.
 PLEASE ADJUST CALCULATIONS.
  
 9) NOTE: PLEASE PROVIDE MORE DETAIL ON THE LOAD SUMMARY
 FOR THE LOAD CALCULATIONS.
 PLEASE SEE NOTE ABOVE AS THIS WILL ALSO AFFECT THE
 LOAD.
 PLEASE KNOW AT THIS TIME THE LOADS ARE NOT CLEAR AS NOT
 ALL LOADS ARE FIGURED IN WITH KITCHEN EQUIPMENT AND NOT
 SURE WHERE AND HOW THE OTHER LOADS ARE BEING DONE OR
 FIGURED.
 FBC 106.1.3.5.1.2, 106.1.2. NEC 220.
  
 10) NOTE: PLEASE KNOW THAT ANY LOCK ON/OFF DEVICES WILL
 BE REQUIRED TO HAVE THE DEVICE BE AN INTEGRAL PART OF
 THE BREAKER. THE DEVICES WHICH *SNAP/CLIP* ON TO
 BREAKERS AND ARE READILY REMOVED OR FALL OF WHEN PANEL
 COVERS ARE REMOVED ARE NOT APPROVED BY THIS AHJ. PLEASE
 ADJUST NOTE TO STATE *THE DEVICE SHALL BE AN INTEGRAL
 PART OF THE BREAKER* OR WORDS TO THAT AFFECT. 110.3,
 90.4.
  
 11) NOTE: PLEASE CLARIFY THE PHASING AS SHOWN ON PANEL
 SCHEDULES. SOME SHOW A AND C PHASE ONLY YET PANEL IS A
 THREE PHASE PANEL? SOME ONLY SHOW A AND C PHASES WITH A
 BLANK FOR B PHASEYET CIRCUITS ARE SHOWN ON THIS
 PHASE?
 PLEASE CLARIFY THE PANELS.
 FBC 106.1.2, 106.3.5.1.2
  
 12) NOTE: PLEASE SEE THE ADA STALLS WILL BE REQUIRED TO
 CONTAIN A BATTERY BACK UP FIXTURE OF SOME TYPE IF WALLS
 ARE ALL THE WAY UP TO THE CEILING.
 PLEASE SEE LS 101 7.8, 7.9.
  
  
 *** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717