| 2007-04-03 10:32:24 | ** UNSAT** |
| | |
| | PROPOSED MCDONALDS |
| | 9835 OKEECHOBEE BLVD. |
| | |
| | 1) NOTE: PLEASE BE SURE ONCE THE ADDRESSED IS VERIFIED |
| | THAT THE TITLE BLOCKS ON PLANS ARE CORRECTED TO INCLUDE |
| | THE ADDRESS LOCATION. AT THIS TIME THE ADDRESS IN OUR |
| | SYSTEM IS BEING SHOWN AS 9835 OKEECHOBEE. ONE ANY SHEET |
| | OF PLANS WHICH DOES NOT HAVE TO HAVE CORRECTIONS MADE, |
| | THEN THE ADDRESS CAN BE ADDED TO THE EXISTING SHEET. |
| | THIS WOULD ONLY BE FOR ANY SHEETS WHICH DO NOT NEED TO |
| | BE CHANGED OR CORRECTED. |
| | 61G1-16.004, 61G15-23.002 |
| | |
| | 2) NOTE: PLEASE SEE THAT AS OF DECEMBER 8TH, 2006 THE |
| | STATE OF FLORIDA ADOPTED NEW CODES AS FOLLOWS. 2004 FBC |
| | W/2006 REVISIONS. |
| | 2005 NFPA-70 |
| | OTHER CODES RELEVANT AND TO BE PLACED ON PLANS. 2003 |
| | NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | ** PLEASE SEE PLANS AS THERE ARE LOCATIONS WHICH LIST A |
| | 2004 ELECTRICAL CODE. |
| | PLEASE SEE NUMEROUS LOCATIONS ON PLANS WHICH INDICATE |
| | THE 2002 NEC/NFPA-70. |
| | PLEASE SEE SEVERAL CODE SECTIONS AS REFLECTED ON PLANS |
| | FOR ARTICLES FROM THE 2002 NEC, WHERE THE CODE SECTIONS |
| | HAVE CHANGED IN THE 2005 NEC. |
| | *EXAMPLE, SEE LOAD CALCULATIONS, GROUNDING DETAILS, |
| | ETC. |
| | |
| | 3) NOTE: PLEASE SEE THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER FOR ENGINEERING FIRM *DIAMONDBACK ENGINEERING* |
| | IS CURRENTLY DELINQUENT WITH THE STATE OF FLORIDA. THIS |
| | HAS BEEN PRINTED AND IS ATTACHED TO NOTES AS OF |
| | 4/2/07. |
| | PLEASE KNOW THIS IS ALSO KNOWN AS THE EB/ ENGINEERING |
| | BUSINESS LICENSE NUMBER. |
| | FS 471.023, FAC 61G15-23.002 |
| | |
| | 4) NOTE: PLEASE SEE 2004 FBC W/ 2006 REVISION FOR |
| | CHAPTER 13. PLEASE SEE 13-415.1.AB.1.1, 13-415.2 AS THE |
| | ENERGY CALCULATIONS DO NOT COORDINATE WITH THE |
| | ELECTRICAL PLANS FOR THE FIXTURES, AMOUNT OF FIXTURES, |
| | ETC. |
| | PLEASE SEE PLANS INDICATE OVER 100PLUS FIXTURES, AND |
| | CALCULATIONS ONLY INDICATE 30? |
| | PLEASE SEE NO INFORMATION ENTERED FOR EXTERIOR |
| | LIGHTING, YET PLANS INDICATE NUMEROUS EXTERIOR LIGHTS? |
| | PLEASE SEE THE WATTAGE AND FIXTURES DO NOT CORRELATE. |
| | ** THERE ARE SEVERAL ITEMS NOT LISTED AND A COMPLETE |
| | REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT THIS |
| | TIME. |
| | |
| | 5) NOTE: PLEASE SEE 2005 NEC 210.8B3 FOR ALL 15/20AMP, |
| | 120V RECEPTACLES IN KITCHEN/FOOD PREPARATION AREAS TO |
| | BE GFI/GFI PROTECTED. |
| | PLEASE SEE THE SECTION OF CODE NOTED ON PLANS IS NOT |
| | COMPLETE WITH THE SECTION AS NOTED. |
| | PLEASE ALSO SEE THAT NOT ALL CIRCUITS AS REQUIRED |
| | INDICATE THE PROTECTION. |
| | PLEASE SEE SOME CIRCUITS INDICATE PROTECTION WHERE NOT |
| | REQUIRED? |
| | PLEASE COORDINATE. |
| | |
| | 6) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF |
| | WORK FOR THIS NEW BUILDING SHALL INCLUDE ALL LABOR AND |
| | MATERIALS. PLEASE KNOW THAT EVEN EQUIPMENT SUCH AS |
| | KITCHEN, A/C ETC WHICH MAY BE OWNER SUPPLIED IS TO BE |
| | INCLUDED IN VALUE. |
| | FBC 108.3. |
| | |
| | 7) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS FOR ALL |
| | EMERGENCY LIGHTS AND EXIT LIGHTS. |
| | PLEASE SEE 700.12E AS THE EM/EXT LIGHTS SHALL BE |
| | CIRCUITED TO THE LOCAL LIGHTING IN ANY ONE AREA. PLEASE |
| | COMPLETE ON PLANS. |
| | THE NOTE ON E-3 FOR EMERGENCY NOTES #1 DOES NOT MEET |
| | THE CODE AND SECTION AS NOTED. |
| | PLEASE ADJUST PLANS AND NOTES. |
| | |
| | 8) NOTE: PLEASE 422.13 AS THE CHANGES IN THE 2005 NEC |
| | REQUIRES THE WATER HEATER LOAD TO BE FIGURED IN THE |
| | CALCULATIONS AT 125%. |
| | PLEASE ADJUST CALCULATIONS. |
| | |
| | 9) NOTE: PLEASE PROVIDE MORE DETAIL ON THE LOAD SUMMARY |
| | FOR THE LOAD CALCULATIONS. |
| | PLEASE SEE NOTE ABOVE AS THIS WILL ALSO AFFECT THE |
| | LOAD. |
| | PLEASE KNOW AT THIS TIME THE LOADS ARE NOT CLEAR AS NOT |
| | ALL LOADS ARE FIGURED IN WITH KITCHEN EQUIPMENT AND NOT |
| | SURE WHERE AND HOW THE OTHER LOADS ARE BEING DONE OR |
| | FIGURED. |
| | FBC 106.1.3.5.1.2, 106.1.2. NEC 220. |
| | |
| | 10) NOTE: PLEASE KNOW THAT ANY LOCK ON/OFF DEVICES WILL |
| | BE REQUIRED TO HAVE THE DEVICE BE AN INTEGRAL PART OF |
| | THE BREAKER. THE DEVICES WHICH *SNAP/CLIP* ON TO |
| | BREAKERS AND ARE READILY REMOVED OR FALL OF WHEN PANEL |
| | COVERS ARE REMOVED ARE NOT APPROVED BY THIS AHJ. PLEASE |
| | ADJUST NOTE TO STATE *THE DEVICE SHALL BE AN INTEGRAL |
| | PART OF THE BREAKER* OR WORDS TO THAT AFFECT. 110.3, |
| | 90.4. |
| | |
| | 11) NOTE: PLEASE CLARIFY THE PHASING AS SHOWN ON PANEL |
| | SCHEDULES. SOME SHOW A AND C PHASE ONLY YET PANEL IS A |
| | THREE PHASE PANEL? SOME ONLY SHOW A AND C PHASES WITH A |
| | BLANK FOR B PHASEYET CIRCUITS ARE SHOWN ON THIS |
| | PHASE? |
| | PLEASE CLARIFY THE PANELS. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 12) NOTE: PLEASE SEE THE ADA STALLS WILL BE REQUIRED TO |
| | CONTAIN A BATTERY BACK UP FIXTURE OF SOME TYPE IF WALLS |
| | ARE ALL THE WAY UP TO THE CEILING. |
| | PLEASE SEE LS 101 7.8, 7.9. |
| | |
| | |
| | *** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |