Plan Review Notes
Plan Review Notes For Permit 07030860
Permit Number 07030860
Review Stop B
Sequence Number 1
Notes
Date Text
2007-05-08 16:55:19 
  
 BUILDING PLAN REVIEW
 PERMIT: 07030860
 ADD: 9835 OKEECHOBEE BLVD
 CONT: GIL HYATT CONSTRUCTION
 TEL: (954)772-2066
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT.PLEASE REMOVE VOID
 SHEETS FROM PLAN AND LOOSLEY LAY THEM ON TOP OF THE SET
 OF PLANS MARKED VOID. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2 ) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT
 IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF,
 SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)THE
 POSTING OF THE NOTICE
 OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE
 FIRST INSPECTION.
  
 3)FBC 1802.2.1 QUESTIONABLE SOILS,
 1802.2.1 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING
 POWER OF THE SOIL
 IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN
 THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL
 REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS
 OF SECTIONS 1802.4 THROUGH 1802.6 .
  
 4)PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, CITY CODE REQUIRES
 AN ADDITIONAL 6". LOCATED IN A A-) FLOOD ZONE.
  
 5) SHEET C-5INDICATES AN ASSUMED LEASE LINE, SINCE
 LOCATED THIS WAY THIS WILL ALSO BE THE ASSUMED PROPERTY
 LINE BETWEEN THE TWO BUILDINGS. PLEASE PROVIDE THE
 ACTUAL DISTANCE BOTH BUILDINGS ARE LOCATED FROM THE
 ASSUMED LEASE LINE FOR TABLE 602 & TABLE 704.8.
  
 6)SHEET A1.4 NOTE# 5 REFERENCES ROOF TOP MECHANICAL
 EQUIPMENT REQUIREMENTS THE WRONG FLORIDA CODE IS
 REFERENCED AND TABLE OR ARTICLE NUMBER, PLEASE
 CORRECT.
  
 7) SHEET A1.4 INDICATES THE USE OF A BILCO ROOF HATCH,
 CURRENTLY THERE IS NO PRODUCTS ON THE MARKET THAT MEET
 THE STATE REQUIREMENTS FOR STRUCTURAL COMPONENTSAS PER
 RULE 9B-72.010(28), FLORIDA ADMINISTRATIVE CODE AND IS
 SUBJECT TO THE REQUIREMENTS FOR PRODUCT APPROVAL. SEE
 ATTACHMENT.
  
 8) SHEET A2.0 & A2.1THE PLAN INDICATES A DESIGN
 OPENING PRESSURE SCHEDULE FOR OPENINGS, ALL PRESSURES
 ARE LOW FOR POSITIVE AND NEGATIVE VALUES FOR A "B"
 ZONE
  
 LOCATION. SEE TABLE 1609.6.2.1(2) SEE BLUE SHEETS OR
 2006 CODE REVISIONS!!!
  
 9)SHEET A5.0- A5.3 ALL SHOW VARIOUS DETAILS
 INDICATING AN ASSEMBLY TYPE 1 OR 2.SOME OF THESE
 WALLS ARE BUILT OUT BUT THE FOUNDATIONS ARE NOT NOR IS
 THERE AN INSPECTION AREA LEFT OPEN.
 IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM). EXCEPTIONS:
 1.PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS
 THAN 5 / 8 INCH (17.1 MM) THICK ADHERED DIRECTLY TO THE
 MASONRY FOUNDATION SIDEWALL.
 2.ACCESS OR VEHICLE RAMPS WHICH RISE TO THE
 INTERIOR FINISH FLOOR ELEVATION FOR THE WIDTH OF SUCH
 RAMPS ONLY.
 3.A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO
 AND GARAGE SLABS AND ENTRY AREAS.
 4.IF THE PATIO HAS BEEN SOIL TREATED FOR TERMITES
 , THE FINISH ELEVATION MAY MATCH THE BUILDING INTERIOR
 FINISH FLOOR ELEVATIONS ON MASONRY CONSTRUCTION ONLY.
 5.MASONRY VENEERS.
  
 10) SHEET A5.0 WALL ASSEMBLY# 2 ALSO INDICATES THAT
 ALUCOBOND MAY ALSO BE USED, PLEASE PROVIDE THE PRODUCT
 APPROVAL FOR SAID PRODUCT. THE BACKING OF SAID WALLS
 INDICATES FOAM.2603.4.1.4 EXTERIOR WALLS?ONE-STORY
 BUILDINGS.
 FOR ONE-STORY BUILDINGS, FOAM PLASTIC HAVING A FLAME
 SPREAD INDEX OF 25 OR LESS, AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 450, SHALL BE PERMITTED WITHOUT
 THERMAL BARRIERS IN OR ON EXTERIOR WALLS IN A THICKNESS
 NOT MORE THAN 4 INCHES (102 MM) WHERE THE FOAM PLASTIC
 IS COVERED BY A THICKNESS OF NOT LESS THAN
 0.032-INCH-THICK (0.81 MM) ALUMINUM OR
 CORROSION-RESISTANT STEEL HAVING A BASE METAL THICKNESS
 OF 0.0160 INCH (0.41 MM) AND THE BUILDING IS EQUIPPED
 THROUGHOUT WITH AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.3.1.1 .
  
  
  
 11)NOTE: SHEET A2.0 & A2.1 BOTH INDICATE THE USE OF
 METAL AWNINGS, PLANS INDICATE THEY ARE TO BE UNDER
 SEPERATE PERMIT, TO BE REVIEWED UNDER A SEPERATE
 PERMIT.
  
 12) A4.1 PLANS INDICATE THERE SHALL BE INSTALLED A WALK
 IN COOLER AND FREEZER, NO INFORMATION WAS
 SUBMITTED.2603.4.1.3 WALK-IN COOLERS.
 IN NONSPRINKLERED BUILDINGS, FOAM PLASTIC HAVING A
 THICKNESS THAT DOES NOT EXCEED 4 INCHES (102 MM) AND A
 MAXIMUM FLAME SPREAD INDEX OF 75 IS PERMITTED IN
 WALK-IN COOLERS OR FREEZER UNITS WHERE THE AGGREGATE
 FLOOR AREA DOES NOT EXCEED 400 SQUARE FEET (37 M 2 )
 AND THE FOAM PLASTIC IS COVERED BY A METAL FACING NOT
 LESS THAN 0.032-INCH-THICK (0.81 MM) ALUMINUM OR
 CORROSION-RESISTANT STEEL HAVING A MINIMUM BASE METAL
 THICKNESS OF 0.016 INCH (0.41 MM). A THICKNESS OF UP TO
 10 INCHES (254 MM) IS PERMITTED WHERE PROTECTED BY A
 THERMAL BARRIER.
  
 13)S0.1 GOVERNING CODE NOTEA FLORIDA 2004 FBC WITH
 2006 REVISIONS, PLEASE CORRECT.
  
 14) S0.2 WIND PRESSURES ARE LOW IN WALL ZONE (4)
 NEGATIVE PRESSURES) SEE BLUE SHEETS 2005 REVISIONS.
 TABLE 1609.6.2.1(2)
  
 15) THE PRODUCT APPROVALS SUBMITTED ARE UNDER THE 2001
 FBC PLEASE PROVIDE THE APPROVALS THAT ARE CURRENTLY
 UNDER THE 2004 FBC. FL BLD CODE 1609.1.4: COMPONENTS
 & CLADDING, PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT
 INSPECTOR) OF PRODUCT TESTING REPORTS,MISSING REPORTS
 ARE AS FOLLOWS:
 A) FIXED WINDOWS, STOREFRONT
 B) MULLIONS
 C) OPERABLE WINDOWS
 D) GLAZED DOORS PASS THROUGHS
 E)HOLLOW CORE METAL DOORS
 F)BILCO ROOF HATCH SEE TECHNICAL ADVISORY FROM BCAB
 G) TRUSS ANCHORS
 H) STORM SHUTTERS (POSSIBLY)
 I) ROOF ASSEMBLIES
 J) PRE-MANUFACTURED A/C STANDS
 K) EFIS SYSTEMS
  
 16)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 17)
 ) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 18)1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
  
 19)) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
 _X__ CONTRACTOR DID NOT PROVIDE THE MEAN
 ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF
 PITCH.
  
 _X__ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 _X__ THE SYSTEM PROVIDED HAS A LOW
 PRESSURE FOR ZONE 2& 3___ .
  
 _X__ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PLEASE PROVIDE
 THE RAS 117 CALCULATION.
  
 _X__THE SYSTEM PROVIDED INDICATES
 LIMITATION# 9, NO ENHANCED
 FASTENING ALLOWED.
  
 20)FOR THE MISSION "S" ROOF TILE PLEASE CIRCLE WHICH
 FASTENING METHOD WILL BE USED
 TO CHECK UPLIFT FACTORS.
  
 21) PLEASE PROVIDE HIP AND RIDGE ATTACHMENT FOR THE
 MISSION "S" CONCRETE RIDGE TILE AND TYPE OF HIP OR
 RIDGE BOARD TO BE USED AND THE TYPE OF FASTENERS FOR
 THE HIP BOAAD. 1507.3.7 ATTACHMENT.
 CLAY AND CONCRETE ROOF TILES SHALL BE FASTENED IN
 ACCORDANCE WITH SECTION 1609 OR IN ACCORDANCE WITH FRSA
 /RTI INSTALLATION MANUAL.
 1507.3.8 APPLICATION.
 TILE SHALL BE APPLIED ACCORDING TO THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS OR RECOMMENDATIONS OF THE
 FRSA /RTI 07320-05.
  
 22)PLEASE PROVIDE EFIS MOLDING SYSTEM INFORMATION FOR
 ADHERRING MOLDING TO THE WALL. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 23)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 24 ) 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERMORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER.THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING
 ADJACENT PROPERTIES, & MAY REQUIRE
 SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS,
 AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR
 ITEMS, ON EXISTING PROPERTIES RESULTING
 IN A DECREASE IN EXCESS OF 800SQ FT OF
 PERMEABLE LAND AREA ON ANY PARCELL SHALL
 AS A PERMIT CONDITION, PROVIDE A
 PROFESSIONALLY PREPARED DRAINAGE PLAN
 CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 25)109.3.10.1 HURICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH
 WINDS.
 ANY PERSONS WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  