| Plan Review Notes For Permit 07030852 |
| Permit Number |
07030852 |
|
| Review Stop |
G |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-08-21 10:20:08 | | | | | | | | | | | | | | | | PASSED/PROVISO | | | | | | | | | PER SECTION 409.5 EACH APPLIANCE SHALL BE PROVIDED WITH | | | A SHUT OFF VALVE. THERE ARE TWO FRYERS INDICATED BUT | | | ONLY ONE SHUT OFF VALVE. THERE ARE TWO CONVECTION OVENS | | | INDICATED BUT ONLY ONE SHUT OFF VALVE. ALSO 1" IS | | | REQUIRED FOR EACH TANKLESS WATER HEATER PER TABLE | | | 402.4(2). 3/4" IS SHOWN FOR EACH. A REVISION IS | | | REQUIRED PRIOR TO FIRST GAS INSPECTION TO CORRECT THESE | | | ITEMS LISTED ON THE PROVISO.--GAS VALVES SHALL BE | | | ACCESSIBLE PER SECTION 409.1.3. | | | | | | | | | | | | | | | | | | | | | . |
|