| Date |
Text |
| 2007-08-10 08:16:52 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | |
| | ******FROM PREVIOUS REVIEW: |
| | ****FROM PREVIOUS REVIEWS: |
| | |
| | |
| | 1. SHT P402 THE FOLLOWING IS REQUIRED FOR THE GAS |
| | PERMIT APPROVAL: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ******RESPONSE NOTED, BUT A CLARIFICATION IS REQUIRED |
| | ON THE DROP WITH THE SOLENOID VALVE. THE TOTAL LENGTH |
| | IS INDICATED AS 3'0", (1'0" +2'0"). |
| | ****RESPONSE NOTED, BUT THE PIPE SIZING THRU THE SHUT |
| | OFF VALVE FOR EACH GAS APPLIANCE SHALL BE FULL SIZE PER |
| | TABLE 402.4(2) AND INDICATED ON THE ISOMETRIC. ALSO |
| | EACH APPLIANCE SHALL PROVIDED WITH A SHUT OFF VALVE PER |
| | SECTION 409.5. ONLY ONE SUPPLY LINE WITH ONE SHUT OFF |
| | VALVE IS INDICATED FOR TWO FRYERS. PLEASE CORRECT THE |
| | GAS RISER DIAGRAM. |
| | |
| | B. OK |
| | C. OK |
| | D. OK |
| | E. OK |
| | |
| | 2. OK |
| | |
| | 36. TO HELP EXPEDITE PLAN REVIEW, PLEASE RESUBMIT THE |
| | MARKED UP PLUMBING PLANS ALONG WITH THE NEW PLANS. |
| | *******NO RESPONSE, NOT ADDRESSED. |
| | ****RESPONSE NOTED, BUT NO MARKED UP PLUMBING PLANS |
| | FOUND. |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. IT APPEARS THAT NEW SHEETS WERE INSERTED INTO THE |
| | OLD PLANS. PLEASE MAKE SURE THE NEWEST REVISED SHEETS |
| | ARE SUBMITTED IN THE NEW SETS OF PLANS FOR REVIEW. |
| | SECTION 106.1.1. |
| | |
| | 2B. SHT FS-5 PLUMBING/GAS SCHEDULE GK113 INDICATES QTY |
| | AS "LOT" BUT MANUF SPECIFICATION SHEET COVER SHEET |
| | INDICATES QUANTITY AS TWO FRYERS. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |