| Date |
Text |
| 2007-06-07 17:29:14 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | WPB MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ******FROM PREVIOUS REVIEW: |
| | |
| | 1. ROUTE PLANS TO THE DEPARTMENT OF BUSINESS |
| | REGULATION, HOTEL & RESTAURANT DIVISION FOR PLAN |
| | REVIEW. A MINIMUM OF TWO SETS OF PLANS WITH STAMPED |
| | SHEETS FROM DBPR WITH THE TWO PAGE "WORKSHEETS" |
| | ATTACHED TO THE STAMPED SHEET SHALL BE RESUBMITTED FOR |
| | REVIEW. SECTION 102.2.1. |
| | ******NO RESPONSE/NOT ADDRESSED |
| | |
| | 2. GREASE INTERCEPTORS SHALL BE SIZED AND INSPECTED BY |
| | ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO |
| | (561) 822-2272 OR CALVIN WILLIAMS(561) 822-2284. |
| | THEIR FAX NUMBER IS (561) 822-2287. E-MAIL |
| | [email protected]@WPB.ORG. PLEASE INDICATE |
| | THEIR RESPONSE. ARTICLE III 90-124(7). ******WAITING |
| | FOR REPLY FROM C. WILLIAMS. WILL TRY TO ADDRESS ISSUE |
| | AT THIS END. |
| | |
| | 3. OK |
| | 4. OK |
| | 5. OK |
| | |
| | 6. SHT A400 DETAILS 1 & 2 GRAB BARS FOR THE WATER |
| | CLOSETS AT THE SIDE SHALL BE 42". SEE FIG 11-30E.-- |
| | DETAIL 4 SHOW THE WATER CLOSET TO BE 1'7" OFF THE WALL |
| | TO THE CENTERLINE OF THE FIXTURE. 1'6" IS REQUIRED. SEE |
| | FIG 11-30E.7. |
| | ******RESPONSE NOTED, NOT ADDRESSED |
| | |
| | 7. SHT A400 SHOW COMPLIANCE WITH THE FOLLOWING: __FOR |
| | URINAL |
| | A. OK |
| | B. OK |
| | C. 11-4.18.4 FLUSH CONTROLS |
| | ******NOT ADDRESSED |
| | __FOR LAVS |
| | A MINIMUM 1 LAV OUTSIDE THE ACCESSIBLE STALL SHALL |
| | COMPLY WITH SECTION 11-4.19 AND ALL SUBSECTIONS. |
| | FORWARD APPROACH REQUIRED AND SHALL EXTEND UNDERNEATH |
| | THE LAV A MINIMUM 19" PLEASE SUBMIT A DETAIL FOR THE |
| | ACCESSIBLE LAV OUTSIDE THE ACCESSIBLE STALL. |
| | ******RESPONSE NOTED, BUT PER SECTION 11-4.19.1 ALL |
| | LAVS SHALL BE ACCESSIBLE. |
| | |
| | 8. SHT A401 DETAILS 1 & 2 FORWARD APPROACH REQUIRED FOR |
| | THE CLEAR FLOOR SPACE FOR AT LEAST ONE LAV OUTSIDE THE |
| | ACCESSIBLE STALL PER SECTION 11-419.3. ******RESPONSE |
| | NOTED, BUT PER SECTION 11-4.19.1 ALL LAVS SHALL BE |
| | ACCESSIBLE. |
| | |
| | 9.OK |
| | 10. OK |
| | 11. OK |
| | 12. OK |
| | |
| | 13. ALL MECHANICAL & PLUMBING SHEETS. THE ENGINEERS |
| | SIGNATURE IS REQUIRED ON EACH SHEET. IT APPEARS THAT |
| | INITIALS HAVE BEEN USED. IF INDEED THIS IS THE LEGAL |
| | SIGNATURE, A SIGNED, SEALED, NOTORIZED LETTER |
| | INDICATING THE LEGAL SIGNATURE SHALL BE SUBMITTED FOR |
| | OUR FILES. FAC 61G15-23.002(1)(2) & FS 471.025. |
| | ******RESPONSE NOTED. THIS WILL BE REQUIRED PRIOR TO |
| | PERMIT BEING ISSUED. |
| | |
| | 14. OK |
| | 15. OK |
| | 16. OK |
| | |
| | 17. SHT P301 PLUMBING/WASTE SCHEDULE. SHOW ALL MARK |
| | DESIGNATIONS ON THE ENLARGED KITCHEN WASTE PLAN THAT |
| | CORRELATES WITH THE SCHEDULE. AT THIS POINT THE KITCHEN |
| | EQUIPMENT CAN NOT BE IDENTIFIED WITHOUT MARK |
| | DESIGNATIONS. SECTION 106.1.1. |
| | ******RESPONSE NOTED, BUT THE FOLLOWING ITEMS WERE NOT |
| | LOCATED ON THE FLOOR PLAN. P6A, P16, P11, P12A, P13A, |
| | P14, P14.1, P14A, P14B, P15A, P17A P47B, P150 & P150A. |
| | PLEASE CORRELATE FLOOR PLAN WITH PLUMBING/WASTE |
| | SCHEDULE. |
| | |
| | 18. OK |
| | |
| | 19. SHT P301 PLUMBING/WATER SCHEDULE ITEMS P31-C & |
| | P39-F INDICATE A WATER FILTER. WATER FILTERS MUST MEET |
| | THE REQUIREMENTS OF NSF 42. PLEASE SUBMIT MANUF |
| | SPECIFICATION SHEETS SHOWING COMPLIANCE. SECTION |
| | 611.1. |
| | ******RESPONSE NOTED, BUT NOT ADDRESSED |
| | |
| | 20. SHT P301 PLUMBING/WATER SCHEDULE. MARK P33-F |
| | INDICATES QTY 4, BUT ONLY 2 WERE FOUND. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | ******RESPONSE NOTED, BUT SCHEDULE NOT CHANGED. |
| | |
| | 21. OK |
| | |
| | 22. SHT P302 IDENTIFY ALL FIXURES/APPLIANCES TO REFLECT |
| | THE MARK NUMBERS INDICATED ON THE PLUMBING/WASTE |
| | SCHEDULE. MORE INFORMATION IS REQUIRED SECTION |
| | 106.2.1. |
| | ******RESPONSE NOTED, BUT SOME MARK NUMBER ARE NOT |
| | INDICATED ON THE FLOOR PLANS. (SEE COMMENT 17). |
| | |
| | 23. OK |
| | 24. OK |
| | |
| | 25. SHT P401. DOMESTIC WATER RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN FOR FIXTURES P88-C, P36-C - |
| | P36-H, (BY P98) & P55-H. PLEASE CORRELATE THE RISER AND |
| | FLOOR PLAN INFORMATIONS. SECTION 106.1.1. |
| | ******RESPONSE NOTED, BUT FIXTURE P88-C PIPING ON THE |
| | RISER DIAGRAM STILL DOES NOT REFLECT THE FLOOR PLAN. |
| | |
| | 26. OK |
| | 27. OK |
| | 28. OK |
| | 29. OK |
| | |
| | 30. SHT P402 THE FOLLOWING IS REQUIRED FOR THE GAS |
| | PERMIT APPROVAL: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | ******RESPONSE NOTED, BUT A CLARIFICATION IS REQUIRED |
| | ON THE DROP WITH THE SOLENOID VALVE. THE TOTAL LENGTH |
| | IS INDICATED AS 3'0", (1'0" +2'0"). |
| | |
| | B. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ******RESPONSE NOTED, BUT DISTANCE SHALL BE VERIFIED |
| | WHEN COMMENT "A" CLARIFIED. |
| | |
| | C. OK |
| | |
| | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ******RESPONSE NOTED, NOT ADDRESSED. |
| | |
| | E. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | ******RESPONSE NOTED, BUT NOT COMPLETLY ADDRESSED. NO |
| | MANUAL SHUT OFF VALVE UPSTREAM OF THE SOLENOID VALVE |
| | AND NO UNION INDICATED. |
| | |
| | 31. OK |
| | 32. OK |
| | 33. OK |
| | 34. OK |
| | 35. OK |
| | |
| | 36. TO HELP EXPEDITE PLAN REVIEW, PLEASE RESUBMIT THE |
| | MARKED UP PLUMBING PLANS ALONG WITH THE NEW PLANS. |
| | *******NO RESPONSE, NOT ADDRESSED |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |