| 2007-05-09 12:25:36 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | WPB MUNICIPAL CODE |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ROUTE PLANS TO THE DEPARTMENT OF BUSINESS |
| | REGULATION, HOTEL & RESTAURANT DIVISION FOR PLAN |
| | REVIEW. A MINIMUM OF TWO SETS OF PLANS WITH STAMPED |
| | SHEETS FROM DBPR WITH THE TWO PAGE "WORKSHEETS" |
| | ATTACHED TO THE STAMPED SHEET SHALL BE RESUBMITTED FOR |
| | REVIEW. SECTION 102.2.1. |
| | |
| | 2. GREASE INTERCEPTORS SHALL BE SIZED AND INSPECTED BY |
| | ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO |
| | (561) 822-2272 OR CALVIN WILLIAMS(561) 822-2284. |
| | THEIR FAX NUMBER IS (561) 822-2287. E-MAIL |
| | [email protected]@WPB.ORG. PLEASE INDICATE |
| | THEIR RESPONSE. ARTICLE III 90-124(7). |
| | |
| | 3. ALL SHEETS WITH AOA ASSOCIATES TITLE BLOCK. THE |
| | ARCHITECTS BUSINESS NUMBER, (CERTIFICATE OF |
| | AUTHORIZATION), IS REQUIRED IN THE TITLE BLOCK OF EACH |
| | SHEET. FAC 61G1-16.004(2) & FS 481.219, 481.2055. |
| | |
| | 4. SHT T101 INDEX OF DRAWINGS DOES NOT REFLECT THE |
| | SHEETS SUBMITTED. SHEETS M101 & P402 ARE NOT SHOWN ON |
| | THE INDEX. SHTS M102, M301, M302, M303 & E100 ARE SHOWN |
| | ON THE INDEX BUT NOT SUBMITTED. PLEASE CORRELATE THE |
| | INDEX WITH SHEETS SUBMITTED. SECTION 106.1.1. |
| | |
| | 5. SHT T101 APPLICABLE CODES ACCESSIBILITY INDICATES |
| | 2001. WE HAVE SINCE ADPOTED THE FBC-2004 ACCESSIBLITY |
| | CODE. (CHAPTER 11). PLEASE CHANGE CODE REFERENCE. |
| | |
| | 6. SHT A400 DETAILS 1 & 2 GRAB BARS FOR THE WATER |
| | CLOSETS AT THE SIDE SHALL BE 42". SEE FIG 11-30E.-- |
| | DETAIL 4 SHOW THE WATER CLOSET TO BE 1'7" OFF THE WALL |
| | TO THE CENTERLINE OF THE FIXTURE. 1'6" IS REQUIRED. SEE |
| | FIG 11-30E.7. |
| | |
| | 7. SHT A400 SHOW COMPLIANCE WITH THE FOLLOWING: __FOR |
| | URINAL |
| | A. 11-4.18.2 HEIGHT |
| | B. 11-4.18.3 CLEAR FLOOR SPACE |
| | C. 11-4.18.4 FLUSH CONTROLS |
| | __FOR LAVS |
| | A MINIMUM 1 LAV OUTSIDE THE ACCESSIBLE STALL SHALL |
| | COMPLY WITH SECTION 11-4.19 AND ALL SUBSECTIONS. |
| | FORWARD APPROACH REQUIRED AND SHALL EXTEND UNDERNEATH |
| | THE LAV A MINIMUM 19" PLEASE SUBMIT A DETAIL FOR THE |
| | ACCESSIBLE LAV OUTSIDE THE ACCESSIBLE STALL. |
| | |
| | 8. SHT A401 DETAILS 1 & 2 FORWARD APPROACH REQUIRED FOR |
| | THE CLEAR FLOOR SPACE FOR AT LEAST ONE LAV OUTSIDE THE |
| | ACCESSIBLE STALL PER SECTION 11-419.3. |
| | |
| | 9. SHT A600 ROOM 113 EMPLOYEES RESTROOM CALLS FOR BCT-1 |
| | FOR THE FLOOR. THE FINISH KEY SHT A602 DOES NOT |
| | INDICATE WHAT BCT-1 REPRESENTS. PLEASE CLARIFY. |
| | SECTIONS 106.1.1 & 1210.1. |
| | |
| | 10. SHT A600 FINISH SCHEDULE FOR ROOMS 110 & 111 STATE |
| | "SEE EL" FOR THE BASE, BUT THE BASE FOR THE WALLS BY |
| | THE W/C'S & URINALS DO NOT INDICATE THE MATERIAL FOR |
| | THE BASE. PLEASE CLARIFY. SECTIONS 106.1.1 & 1210.1. |
| | |
| | 11. SHT A600 WALLS FOR THE W/C'S AND URINALS IN ROOMS |
| | 110 & 111 INDICATE CT-3 ON THE ELEVATIONS, BUT CT-3 IS |
| | NOT INDICATED ON THE FINISH SCHEDULE. PLEASE CLARIFY. |
| | SECTIONS 106.1.1. & 1210.2. |
| | |
| | 12. SHT A600 ROOM 113 WALLS CALL FOR PT-1B. SECTION |
| | 1210.2 CALLS FOR A SMOOTH, HARD, NONABSORBENT SURFACE |
| | WITHIN 2' OF THE W/C. PAINT DOES NOT COMPLYWITH |
| | REQUIREMENT FOR A HARD SURFACE. PLEASE SHOW |
| | COMPLIANCE. |
| | |
| | 13. ALL MECHANICAL & PLUMBING SHEETS. THE ENGINEERS |
| | SIGNATURE IS REQUIRED ON EACH SHEET. IT APPEARS THAT |
| | INITIALS HAVE BEEN USED. IF INDEED THIS IS THE LEGAL |
| | SIGNATURE, A SIGNED, SEALED, NOTORIZED LETTER |
| | INDICATING THE LEGAL SIGNATURE SHALL BE SUBMITTED FOR |
| | OUR FILES. FAC 61G15-23.002(1)(2) & FS 471.025. |
| | |
| | 14. SHT P001 GENERAL NOTES #3. THE SANITARY PIPING |
| | SHALL BE INSTALLED PER TABLE 704.1. ALL PIPE 2-1/2" AND |
| | SMALLER SHALL BE SLOPED 1/4"/FT. PLEASE ADJUST NOTE TO |
| | REFLECT THIS REQUIREMENT. |
| | |
| | 15. SHT P001 GENERAL NOTES #30. DIELECTRIC UNIONS ARE |
| | MANUF. FOR GAS SYSTEMS ONLY. FOR USE IN A WATER SYSTEM |
| | A DIELECTRIC COUPLING SHALL BE USED. PLEASE ADJUST NOTE |
| | TO REFLECT THIS REQUIREMENT. |
| | |
| | 16. SUBMIT A SANITARY RISER DIAGRAM FOR THE PIPING TO |
| | THE SECOND FLOOR MECHANICAL ROOM. SECTION |
| | 106.3.5.1.3(4)(6)(13). |
| | |
| | 17. SHT P301 PLUMBING/WASTE SCHEDULE. SHOW ALL MARK |
| | DESIGNATIONS ON THE ENLARGED KITCHEN WASTE PLAN THAT |
| | CORRELATES WITH THE SCHEDULE. AT THIS POINT THE KITCHEN |
| | EQUIPMENT CAN NOT BE IDENTIFIED WITHOUT MARK |
| | DESIGNATIONS. SECTION 106.1.1. |
| | |
| | 18. SHT P301. PLUMBING/WASTE SCHEDULE. P36-C & P36-H |
| | INDICATES QTY 6, BUT ONLY 5 WERE FOUND.PLEASE |
| | CORRELATE. SECTION 106.1.1. |
| | |
| | 19. SHT P301 PLUMBING/WATER SCHEDULE ITEMS P31-C & |
| | P39-F INDICATE A WATER FILTER. WATER FILTERS MUST MEET |
| | THE REQUIREMENTS OF NSF 42. PLEASE SUBMIT MANUF |
| | SPECIFICATION SHEETS SHOWING COMPLIANCE. SECTION |
| | 611.1. |
| | |
| | 20. SHT P301 PLUMBING/WATER SCHEDULE. MARK P33-F |
| | INDICATES QTY 4, BUT ONLY 2 WERE FOUND. PLEASE CLARIFY. |
| | SECTION 106.1.1. |
| | |
| | 21. SHT P301 PLUMBING/GAS SCHEDULE. PK104 DESCRIPTION & |
| | REMARKS INDICATED A GAS DROP BY THE GENERAL CONTRACTOR. |
| | ALL GAS WORK SHALL BE BY THE PLUMBING CONTRACTOR. |
| | PLEASE CHANGE REFERENCE. FS 489.105(M). |
| | |
| | 22. SHT P302 IDENTIFY ALL FIXURES/APPLIANCES TO REFLECT |
| | THE MARK NUMBERS INDICATED ON THE PLUMBING/WASTE |
| | SCHEDULE. MORE INFORMATION IS REQUIRED SECTION |
| | 106.2.1. |
| | |
| | 23. SHT P302 THE DISHWASHER, (ITEM 55 ON SHT P301), |
| | SHALL CONNECT TO THE SANITARY SYSTEM, NOT THE GREASE |
| | SYSTEM. CITY CODE ARTICLE III SECTION 90-124(7)(B). |
| | PLEASE CHANGE FLOOR PLAN PIPING. |
| | |
| | 24. SHT P304 BAR SANITARY/WASTE PLAN. DRY HORIZONTAL |
| | VENTS ARE PROHIBITED. SECTION 905.3. EVERY DRY VENT |
| | CONNECTING TO A HORIZONTAL DRAIN SHALL CONNECT ABOVE |
| | THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE. ALSO SEE |
| | SECTION 905.4. |
| | |
| | 25. SHT P401. DOMESTIC WATER RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN FOR FIXTURES P88-C, P36-C - |
| | P36-H, (BY P98) & P55-H. PLEASE CORRELATE THE RISER AND |
| | FLOOR PLAN INFORMATIONS. SECTION 106.1.1. |
| | |
| | 26. SHT P401 FULL OPEN VALVES ARE REQUIRED ON THE WATER |
| | SUPPLY PIPE TO EVERY W/H. SECTION 606.1(7). |
| | |
| | 27. SHT P401 A WATER HAMMER ARRESTOR IS REQUIRED ON THE |
| | WATER SUPPLY TO P55-H WHEN DRAWN ON THE RISER DIAGRAM. |
| | SECTION 604.9. |
| | |
| | 28. SHT P402 KITCHEN WASTE& VENT RISER DIAGRAM. THE |
| | FLOOR SINK FOR THE DISH WASHER SHALL CONNECT TO THE |
| | SANITARY SYSTEM, NOT THE GREASE SYSTEM. ARTICLE III |
| | SECTION 90-124(7)(B). PLEASE CHANGE RISER DIAGRAM. |
| | |
| | 29. SHT P402. BAR WASTE AND VENT RISER DIAGRAM. DRY |
| | HORIZONTAL VENTS ARE PROHIBITED. SECTION 905.3. EVERY |
| | DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL CONNECT |
| | ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE. ALSO |
| | SEE SECTION 905.4. |
| | |
| | 30. SHT P402 THE FOLLOWING IS REQUIRED FOR THE GAS |
| | PERMIT APPROVAL: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | |
| | B. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | C. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | D. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | E. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | |
| | 31. SHT P501 GAS INSTANT WATER HEATER PIPING SCHEMATIC. |
| | THE DIRT LEGS SHALL BE DOWNSTREAM OF THE GAS SHUT OFF |
| | VALVES. SECTION 408.4. |
| | |
| | 32. SHT P501 FLOOR SINK DETAIL. THE AIR GAP SHALL BE A |
| | MINIMUM OF TWICE THE EFFECTIVE OPENING OF THE INDIRECT |
| | WASTE PIPE. SECTION 802.2.1.-- THE FLOOR SINK SHALL |
| | BE SET 1" ABOVE THE FINISHED FLOOR AS IT IS FOR |
| | INDIRECT WASTE ONLY, NOT A FLOOR DRAIN.PLEASE ADJUST |
| | THE FLOOR SINK DETAIL. |
| | |
| | 33. SHT PD201 GENERAL NOTES #2 DEAD ENDS ARE |
| | PROHIBITED. ALL DEMO'D & CAPPED PIPING SHALL BE LEFT |
| | UNCOVERED UNTIL FIELD INSPECTOR'S APPROVAL. SECTION |
| | 704.5. |
| | |
| | 34. SHT PD201 GENERAL NOTES #3 & #10 HAVE NOT BEEN |
| | LOCATED. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 35. SHT PD202 GENERAL NOTES #1 DEAD ENDS ARE |
| | PROHIBITED. ALL DEMO'D & CAPPED PIPING SHALL BE LEFT |
| | UNCOVERED UNTIL FIELD INSPECTOR'S APPROVAL. SECTION |
| | 704.5. |
| | |
| | 36. TO HELP EXPEDITE PLAN REVIEW, PLEASE RESUBMIT THE |
| | MARKED UP PLUMBING PLANS ALONG WITH THE NEW PLANS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |