| 2007-03-31 17:00:41 | ** UNSAT ** |
| | |
| | *RUTH CHRIS* |
| | INTERIOR BUILD-OUT W/ SOME EXTERIOR WORK. |
| | PREVIOUS OCCUPANCY: BUSINESS. |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE SEE SOME AREAS WHICH STATE CODES WHICH ARE |
| | NOT YET ADOPTED BY THE STATE OR CODES WHICH ARE NO |
| | LONGER IN EFFECT. PLEASE GO OVER PLANS AS CODES AND |
| | SECTIONS ARE STATED FROM SEVERAL CODES. |
| | PLEASE SEE THE PLANS STATES THE 2001 FBC FOR ADA |
| | COMPLIANCE; HOWEVER THIS SHOULD BE THE 2004 W/ 2006 |
| | REVISIONS. THE 2004 FBC WENT INTO EFFECT ON OCT. 1ST, |
| | 2005. |
| | PLEASE SEE AREAS WHERE THE PLANS INDICATE THE 2007 |
| | NFPA-72 AND 2006 NFPA-101. SEE CODES ABOVE FOR RELEVANT |
| | ADOPTED CODES. |
| | PLEASE SEE OTHER REFERENCES TO ADA WHICH SHOULD BE |
| | NOTED TO THE 2004 FBC. |
| | |
| | 2) NOTE: PLEASE SEE MISSING FIRM LICENSE NUMBER FOR THE |
| | ARCHITECTURAL FIRM AS REQUIRED ON TITLE BLOCKS PER FAC |
| | 61G1-16.004 AND FS 481.219. |
| | PLEASE SEE THIS INFORMATION IS REQUIRED FOR ALL TRADES |
| | AND FOR ALL SHEETS WHICH CONTAIN THIS TITLE BLOCK |
| | WHETHER OR NOT COMMENT IS MADE BY ANY OTHER TRADE |
| | REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE SEE SEVERAL ARCHITECTURAL SHEETS IN THE |
| | PLANS ARE NOT SIGNED OR SEALED. PLEASE SEE SHEETS |
| | T-101, LS (BOTH) AND SHEET A-100 THRU A-205. PLEASE SEE |
| | FS 481.221. |
| | |
| | 4) NOTE: PLEASE SEE SHEETS FOR ARCHITECTURAL AND SOME |
| | ENGINEERING SHEETS APPEAR TO BE SIGNED WITH *INITIALS*, |
| | IF THESE ARE INDEED THE LEGAL SIGNATURES OF THESE |
| | DESIGNERS, PLEASE PROVIDE SIGNED, DATED AND SEALED |
| | LETTERS FOR SIGNATURE VERIFICATION. THESE WILL BE |
| | PLACED IN OUR SIGNATURE FILE FOR ANY NEED OF FUTURE |
| | PROJECTS OR REFERENCE. |
| | PLEASE BE SURE LETTERS ARE ALSO PROPERLY NOTARIZED PER |
| | FS 117.05. |
| | ** THIS COMMENT IS FOR MR. DOUGLAS AND MR. LIZASOAIN. |
| | |
| | 5) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) |
| | AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR |
| | ADA REQUIRED AREAS. DEVICES ARE BEING SHOWN ON |
| | PLANS/LEGEND. PLEASE CORRELATE WITH PLANS, AND FA |
| | SHEETS SUBMITTED. |
| | ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A |
| | SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS |
| | REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM |
| | SETS. |
| | FBC 106.3.5.1.2 |
| | |
| | 6) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC |
| | CHAPTER 13 FOR CONTROL OF LIGHTING PER 13-415.1ABC.1.1, |
| | .1.2 AND .1.3. PLEASE SEE LIGHTING DIMMING PANELS ARE |
| | SHOWN HOWEVER COMPLIANCE WITH THE 2004 FBC W/2006 |
| | REVISIONS IS NOT SHOWN AT THIS TIME. |
| | PLEASE SUBMIT LIGHTING POWER DENSITIES PER THE 2004 FBC |
| | W/ 2006 REVISION. PLEASE SEE 13-415.1.AB.1.1, 13-415.2 |
| | FOR LIGHTING PERFORMANCE CALCULATIONS WHICH ARE TO |
| | CORRELATE WITH THE ENERGY CALCULATIONS SUBMITTED. |
| | PLEASE SEE THE ENERGY CALCULATIONS DO NOT INDICATE ALL |
| | THE FIXTURES, TYPES AND WATTAGE PER FIXTURE AS |
| | REQUIRED. |
| | PLEASE SEE THAT THE FIXTURE SCHEDULE SHALL BE SPECIFIC |
| | FOR FIXTURES TO BE INSTALLED AND COORDINATION WITH THE |
| | LPD/CALCULATIONS TO BE REVIEWED FOR COMPLIANCE. PLEASE |
| | SUBMIT SCHEDULING IF A LIGHTING CONTROL SYSTEM IS |
| | INSTALLED. |
| | PLEASE INDICATE ALL OVER RIDE DEVICES AND LOCATIONS ON |
| | PLANS. |
| | PLEASE STATE ALL MAXIMUM OVER RIDE TIMES. |
| | PLEASE SEE MISSING EXTERIOR LIGHTING ALLOWANCES ON |
| | PLANS/ENERGY CALCULATIONS. |
| | PLEASE SEE THE ENERGY CALCULATIONS INDICATE *MANUAL |
| | ON/OFF* FOR METHOD OF LIGHTING CONTROL, HOW IS THIS |
| | POSSIBLE WHEN LIGHTING IS REQUIRED TO BE AUTOMATED. |
| | PLEASE BE SURE TO HAVE THE DESIGNER OF RECORD FOR THE |
| | ENERGY CALCULATIONS SIGN, DATE AND SEAL THESE AS |
| | REQUIRED PER 13-103.1.1.1 |
| | ** PLEASE KNOW THAT AS MUCH OF THIS INFORMATION HAS NOT |
| | YET BEEN SUBMITTED, MANY OF THESE THINGS CAN NOT YET BE |
| | REVIEWED FOR CODE COMPLIANCE. |
| | |
| | 7) NOTE: PLEASE SEE THE SQUARE FOOTAGE ON T-101 SHEET |
| | DOES NOT CORRELATE WITH THE SQ FT ON THE ENERGY |
| | CALCULATIONS. |
| | PLEASE CORRELATE. FBC 106.1.2 |
| | |
| | 8) NOTE: PLEASE KNOW THAT THE SIGNS AS SHOWN ON THE |
| | ELEVATIONS ON PLANS WILL BE UNDER SEPARATE PERMITS. |
| | THIS IS ONLY NOTED AND NO CHANGES NEED TO BE MADE. |
| | |
| | 9) NOTE: PLEASE INDICATE THE EXISTING OR NEW |
| | TRANSFORMER GROUND PER 250.20,250.30, 250.66. PLEASE |
| | INDICATE THE ATTACHMENT POINT. |
| | |
| | 10) NOTE: PLEASE CLARIFY RISER AS THE SERVICE IS BEING |
| | SHOWN AS ONE EXISTING SERVICE YET THIS BUILD OUT IS |
| | BEING DONE FROM WHAT USED TO BE TWO SEPARATE TENANTS. |
| | WHAT IS BEING DONE WITH THE SERVICE WHICH USED TO FEED |
| | THE PREVIOUS TENANT WHO IS BEING TAKEN OVER/EXPANDED? |
| | FBC 106.1.2 |
| | |
| | 11) NOTE: PLEASE SPECIFY THE SERVICE EQUIPMENT, |
| | ELECTRICAL PANELS, AND TRANSFORMER LOCATIONS. ARE THESE |
| | LOCATED IN AN ELECTRICAL ROOM? |
| | PLEASE PROVIDE ROOM AND AREA DESIGNATIONS FOR ALL AREAS |
| | AND ROOMS. |
| | 110.26, 240.24, 450.11, 450.13 ETC |
| | PLEASE INDICATE HOW THE TRANSFORMER IS MOUNTED. |
| | EXISTING FLOOR? |
| | |
| | 12) NOTE: PLEASE SEE THE LOAD CALCULATIONS SUBMITTED |
| | ARE NOT COMPLETED AT THIS TIME. PLEASE SEE THE LOAD |
| | SUMMARY WHICH DOES NOT SHOW ANY LIGHTING LOADS? PLEASE |
| | SHOW. 215.3, 230.42, 220.12, 220.14, 220.42, 220.43, |
| | 220.44, ETC. |
| | |
| | 13) NOTE: PLEASE SEE MISSING SIGN CIRCUIT PER 600.5, |
| | PLEASE INDICATE MINIMUM LOADS REQUIRED. |
| | PLEASE ALSO SEE 210.62 FOR MISSING WINDOW RECEPTACLES |
| | AND LOADS PER 220.43. |
| | |
| | 14) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS |
| | ON THE LIGHTING CONTROL PANELS. |
| | PLEASE SEE NOTE #6 AS ONLY DIMMING PANELS ARE BEING |
| | SHOWN. |
| | 110.3, 90.7. |
| | FBC 106.1.2 |
| | |
| | 15) NOTE: PLEASE SEE 2005 NEC 210.8B3 AS ALL 15/20AMP |
| | 120V RECEPTACLES IN KITCHEN AREAS AND THE LIKE SHALL BE |
| | GFI/GFI PROTECTED. PLEASE SEE PANEL SCHEDULE NOTES SOME |
| | OF THESE BUT NOT ALL. |
| | |
| | 16) NOTE: PLEASE PROVIDE SHUNT DETAIL FOR CONNECTION |
| | AND SHUT OFF OF ALL ELECTRICAL TO HOOD. NFPA-96. FBC |
| | 106.1.2 |
| | |
| | 17) NOTE: PLEASE CONFIRM TIMES ON EMERGENCY LIGHTING |
| | FIXTURES AS NOTED ON LEGEND. |
| | PLEASE SEE NFPA-101 7.8, 7.9 |
| | PLEASE ALSO SUBMIT PHOTO-METRICS FOR MINIMUM LEVELS OF |
| | LIGHTING FOR STAIRS AND EGRESS PATHS PER NFPA-101 |
| | 7.8.1.3, 7.9.2.2. |
| | THIS REQUIRES A MINIMUM OF 10FT CANDLES UNDER NORMAL |
| | FOR STAIRS AND IS PERMITTED TO DOWN TO 1FC UNDER |
| | EMERGENCY CONDITIONS. |
| | THIS IS REQUIRED FOR LIFE SAFETY AND TRIPPING HAZARDS. |
| | |
| | ** PLEASE KNOW AS THERE IS INFORMATION NOT YET |
| | SUBMITTED, THERE MAY NEW COMMENTS ON THE FOLLOWING |
| | REVIEW ONCE PLANS ARE COMPLETED FOR REVIEW. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |