| 2007-05-16 09:24:29 | BUILDING PLAN REVIEW |
| | PERMIT: 07030852 |
| | ADD: 651 OKEECHOBEE BLVD# 100 |
| | CONT: RCC ASSOCIATES, INC |
| | TEL: (954)691-5385 |
| | FBC = 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| | THE COURT. |
| | NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| | NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, |
| | SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)THE |
| | POSTING OF THE |
| | NOTICE OF COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE |
| | THE |
| | FIRST INSPECTION. |
| | |
| | 3) SHEET T-101, APPLICABLE CODES- THE 2001 |
| | ACCESSIBILITY CODE IS THE WRONG CODE PLEASE CORRECT TO |
| | THE 2004 FBC CHAPTER 11FLORIDA ACCESSIBILITY CODE |
| | |
| | 4) SHEET T-101, APPLICABLE CODES- PREVIOUS OCCUPANCY |
| | WAS ALSO A RESTAURANT: A2 OCCUPANCY |
| | |
| | 5) SHEET T-101, CONSTRUCTION TYPE: THIS IS A HIGH RISE |
| | BUILDING REQUIRING TYPE IA CONSTRUCTION. |
| | |
| | 6) IN THE SEET OF PLANSREVIEWED THE DESIGNER OF |
| | RECORD MISSED SIGNING AND SEALING THE T, LS ANDQUITE |
| | A FEW A SHEETS. |
| | PLANS, SPECIFICATIONS, REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND |
| | BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 7)VOA ASSOCIATES INCORP. DOESN'T INDICATE THEIR |
| | CERTIFICATE OF AUTHORIZATION. |
| | 481.219 F.S.CERTIFICATE OF |
| | AUTHORIZATION.THE TITLE BLOCK FOR ANY |
| | SHEET BEARING THE NAME OF AN ARCHITECT |
| | PRACTICING UNDER A FICTITIOUS NAME, A |
| | CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL |
| | SERVICES, SHALL INCLUDE |
| | THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER.ADD THE NUMBER TO EACH SHEET. |
| | THIS MAY BE ADDED BY HAND. |
| | |
| | 8)ON SHEET A101 THIS SHEET INDICATES A KITHEN BUT NO |
| | FREEZERS NOR WALK IN COOLERS ARE SHOWN, |
| | WILL THIS BE UNDER A SEPERATE PERMIT? PLEASE SHOW |
| | LOCATION. 106.1.2* ADD INFO REQUIRED. |
| | |
| | 9) SHEET A102 MEZANINE LEVEL IT APPEARS OVER THE 2ND |
| | FLOOR RESTROOMS IT APPEARSTO BE A VOID SPACE OR ROOM, |
| | WITH THE EXISTINGWALL HAVING A WALL TYPE MARKER # 3 |
| | AND A NEW WALL WITH NO WALL TYPE DESIGNATION, PLEASE |
| | EXPLAIN THIS AREA? 106.1.2* ADD INFO REQUIRED. |
| | |
| | 10) SHEET A201- A205 INDICATE TYPE OF WALL FINISHES, |
| | THEY INCLUDE WALL COVERINGS, GLASS, METAL LAMINATES, |
| | PANEL FABRIC, WALL PANEL & WOOD VENEERS, PLEASE PROVIDE |
| | THE FLAME SPREADINDEX AND SMOKE DEVELOPMENT INDEX FOR |
| | EACH OF THE MATERIALS TO BE INSTALLED. SEE TABLE 803.5 |
| | PLEASE TAKE NOTE OF FOOTNOTES A, B, AND C. |
| | |
| | 11) TEXTILES;803.6 TEXTILES. WHERE USED AS INTERIOR |
| | WALL OR CEILING FINISH MATERIALS, TEXTILES, INCLUDING |
| | MATERIALS HAVING WOVEN OR NONWOVEN, NAPPED, TUFTED, |
| | LOOPED OR SIMILAR SURFACE, SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THIS SECTION. |
| | |
| | 803.6.1 TEXTILE WALL COVERINGS. |
| | TEXTILE WALL COVERINGS SHALL HAVE A CLASS A FLAME |
| | SPREAD INDEX IN ACCORDANCE WITH ASTM E 84 AND BE |
| | PROTECTED BY AUTOMATIC SPRINKLERS INSTALLED IN |
| | ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2 OR THE |
| | COVERING SHALL MEET THE CRITERIA OF SECTION 803.6.1.1 |
| | OR 803.6.1.2 WHEN TESTED IN THE MANNER INTENDED FOR USE |
| | IN ACCORDANCE WITH NFPA 265 USING THE PRODUCT MOUNTING |
| | SYSTEM, INCLUDING ADHESIVE. |
| | |
| | 803.6.1.1 METHOD A TEST PROTOCOL. |
| | DURING THE METHOD A PROTOCOL, FLAME SHALL NOT SPREAD TO |
| | THE CEILING DURING THE 40 KW EXPOSURE. DURING THE 150 |
| | KW EXPOSURE, THE TEXTILE WALL COVERING SHALL COMPLY |
| | WITH ALL OF THE FOLLOWING: |
| | 1.FLAME SHALL NOT SPREAD TO THE OUTER EXTREMITY OF |
| | THE SAMPLE ON THE 8-FOOT BY 12-FOOT (203 MM BY 305 MM) |
| | WALL. |
| | 2.THE SPECIMEN SHALL NOT BURN TO THE OUTER |
| | EXTREMITY OF THE 2-FOOT-WIDE (610 MM) SAMPLES MOUNTED |
| | IN THE CORNER OF THE ROOM. |
| | 3.BURNING DROPLETS DEEMED CAPABLE OF IGNITING |
| | TEXTILE WALL COVERINGS OR THAT BURN FOR 30 SECONDS OR |
| | MORE SHALL NOT FORM. |
| | 4.FLASHOVER, AS DEFINED IN NFPA 265, SHALL NOT |
| | OCCUR. |
| | 5.THE MAXIMUM NET INSTANTANEOUS PEAK HEAT RELEASE |
| | RATE, DETERMINED BY SUBTRACTING THE BURNER OUTPUT FROM |
| | THE MAXIMUM HEAT RELEASE RATE, DOES NOT EXCEED 300 KW. |
| | |
| | |
| | 803.6.1.2 METHOD B TEST PROTOCOL. |
| | DURING THE METHOD B PROTOCOL, FLAMES SHALL NOT SPREAD |
| | TO THE CEILING AT ANY TIME DURING THE 40 KW EXPOSURE. |
| | DURING THE 150 KW EXPOSURE, THE TEXTILE WALL COVERING |
| | SHALL COMPLY WITH THE FOLLOWING: |
| | 1.FLAME SHALL NOT SPREAD TO THE OUTER EXTREMITIES |
| | OF THE SAMPLES ON THE 8-FOOT BY 12-FOOT (203 MM BY 305 |
| | MM) WALLS. |
| | 2.FLASHOVER, AS DESCRIBED IN NFPA 265, SHALL NOT |
| | OCCUR. |
| | |
| | 803.6.2 TEXTILE CEILING FINISH. |
| | WHERE USED AS A CEILING FINISH, CARPET AND SIMILAR |
| | TEXTILE MATERIALS SHALL HAVE A CLASS A FLAME SPREAD |
| | INDEX IN ACCORDANCE WITH ASTM E 84 AND BE PROTECTED BY |
| | AUTOMATIC SPRINKLERS. |
| | |
| | 12) THE MATERIALS LIST ON SHEETS A201-A205 INCLUDE |
| | GLASS IS THIS TRUELY GLASS OR LIGHT TRANSMITTING |
| | PLASTICS?IF GLASS PROVIDE HOW IT WILL BE SECURED AND |
| | THE TYPE OF GLASS? IF PLASTICS |
| | PLEASE PROVIDE THE SPEC IN ACCORDANCE WITH 2606.4. |
| | |
| | 13) DECORATIONS AND TRIM:805.1 GENERAL. |
| | IN OCCUPANCIES OF GROUPS A, E, I, R-1 AND DORMITORIES |
| | IN GROUP R-2, CURTAINS, DRAPERIES, HANGINGS AND OTHER |
| | DECORATIVE MATERIALS SUSPENDED FROM WALLS OR CEILINGS |
| | SHALL BE FLAME RESISTANT IN ACCORDANCE WITH SECTION |
| | 805.2 AND NFPA 701 OR NONCOMBUSTIBLE. |
| | IN GROUPS I-1 AND I-2, COMBUSTIBLE DECORATIONS SHALL BE |
| | FLAME RETARDANT UNLESS THE DECORATIONS, SUCH AS |
| | PHOTOGRAPHS AND PAINTINGS, ARE OF SUCH LIMITED |
| | QUANTITIES THAT A HAZARD OF FIRE DEVELOPMENT OR SPREAD |
| | IS NOT PRESENT. IN GROUP I-3, COMBUSTIBLE DECORATIONS |
| | ARE PROHIBITED. |
| | |
| | 805.1.1 NONCOMBUSTIBLE MATERIALS. |
| | THE PERMISSIBLE AMOUNT OF NONCOMBUSTIBLE DECORATIVE |
| | MATERIAL SHALL NOT BE LIMITED. |
| | |
| | 805.1.2 FLAME-RESISTANT MATERIALS. |
| | THE PERMISSIBLE AMOUNT OF FLAME-RESISTANT DECORATIVE |
| | MATERIALS SHALL NOT EXCEED 10 PERCENT OF THE AGGREGATE |
| | AREA OF WALLS AND CEILINGS. |
| | EXCEPTION: IN AUDITORIUMS OF GROUP A, THE PERMISSIBLE |
| | AMOUNT OF FLAME-RESISTANT DECORATIVE MATERIAL SHALL NOT |
| | EXCEED 50 PERCENT OF THE AGGREGATE AREA OF WALLS AND |
| | CEILING WHERE THE BUILDING IS EQUIPPED THROUGHOUT WITH |
| | AN AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| | SECTION 903.3.1.1 AND THE MATERIAL IS INSTALLED IN |
| | ACCORDANCE WITH SECTION 803.3 . |
| | |
| | 805.2 ACCEPTANCE CRITERIA AND REPORTS. |
| | WHERE REQUIRED TO BE FLAME RESISTANT, DECORATIVE |
| | MATERIALS SHALL BE TESTED BY AN APPROVED AGENCY AND |
| | PASS TEST 1 OR 2, AS APPROPRIATE, DESCRIBED IN NFPA 701 |
| | OR SUCH MATERIALS SHALL BE NONCOMBUSTIBLE. REPORTS OF |
| | TEST RESULTS SHALL BE PREPARED IN ACCORDANCE WITH NFPA |
| | 701 AND FURNISHED TO THE CODE OFFICIAL UPON REQUEST. |
| | PLASTIC |
| | 805.3 FOAM PLASTIC . |
| | FOAM PLASTIC USED AS TRIM IN ANY OCCUPANCY SHALL COMPLY |
| | WITH SECTION 2604.2 . |
| | PLASTIC |
| | 805.4 PYROXYLIN PLASTIC . |
| | IMITATION LEATHER OR OTHER MATERIAL CONSISTING OF OR |
| | COATED WITH A PYROXYLIN OR SIMILARLY HAZARDOUS BASE |
| | SHALL NOT BE USED IN GROUP A OCCUPANCIES. |
| | |
| | 805.5 TRIM. |
| | MATERIAL USED AS INTERIOR TRIM SHALL HAVE A MINIMUM |
| | CLASS C FLAME SPREAD INDEX AND SMOKE-DEVELOPED INDEX. |
| | COMBUSTIBLE TRIM, EXCLUDING HANDRAILS AND GUARDRAILS, |
| | SHALL NOT EXCEED 10 PERCENT OF THE AGGREGATE WALL OR |
| | CEILING AREA IN WHICH IT IS LOCATED. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL |
| | INFORMATION REQUESTED ADDITIONAL COMMENTS MAY APPEAR |
| | THAT WERE NOT PART OF THIS REVIEW. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | ) |