| Plan Review Notes For Permit 07030789 |
| Permit Number |
07030789 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-12 08:45:02 | 1. ENTIRE PARKING GARAGE IS TO BE COMPLETELY FIRE | | | SPRINKLER PROTECTED EXCEPT FOR THE FPL VAULT. | | | | | | 2. THE FIRST FLOOR MECHANICAL ROOM MUST ALSO BE FIRE | | | SPRINKLER PROTECTED. PLANS DO NOT ILLUSTRATE FIRE | | | SPRINKLER HEADS IN THIS ROOM OR ELECTRICAL ROOM B1.111. | | | PRE-ACTION FIRE SPRINKLER SYSTEM NOTED TO BE PLANNED IN | | | THE MAIN ELECTRICAL ROOM ACCORDING TO THE NOTES. | | | | | | 3. STANDPIPE SYSTEM FIRE HOSE VALVES SHALL BE EQUIPPED | | | WITH 2 1/2 TO 1 1/2 REDUCERS. | | | | | | 4. SPARE SPRINKLER HEADS AND A WRENCH SHALL BE PROVIDED | | | FOR THE FIRE SPRINKLER SYSTEM. | | | | | | 5. FIRE DEPARTMENT CONNECTIONS SHALL BE PROVIDED WITH | | | KNOX-BOX LOCKING CAPRS. | | | | | | 6. FIRE SPRINKLER SYSTEM TO BE INSTALLED IN ACCORDANCE | | | WITH NFPA 13. | | | | | | 7. STANDPIPE SYSTEM SHALL BE INSTALLED IN ACCORDANCE | | | WITH NFPA 14. | | | | | | 8. FIRE PUMP TO BE INSTALLED IN ACCORDANCE WITH NFPA | | | 20. | | | | | | 9. FIRE SPRINKLER HEADS THAT ARE INSTALLED OUTSIDE | | | SHALL BE WAX COATED OR CORROSION RESISTANT. | | | | | | 10. CUT SHEETS NEEDED FOR THE FIRE PUMP, BACKFLOW | | | PREVENTION DEVICE, FIRE SPRINKLER HEADS, AND ALL OTHER | | | APPURTENANT EQUIPMENT. | | | | | | 11. TEMPORARY STANDPIPE SYSTEMS SHALL BE REQUIRED WHEN | | | EACH BUILDING REACHES THREE STORIES OR THIRTY FEET IN | | | HEIGHT. | | | | | | MIKE CARSILLO, BATTALION CHIEF OF FIRE PREVENTION | | | 804-4709 PHONE | | | 804-4774 FAX |
|