| 2007-03-31 14:01:34 | ****** UNSAT ***** |
| | |
| | ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 |
| | IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE |
| | ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY |
| | THE CITY OF WEST PALM BEACH. |
| | |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE OF FLORIDA |
| | BUILDING COMMISSION. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLANS NOW INDICATE THE 2002 NEC, ON THE ELECTRICAL |
| | SHEET. |
| | PLANS ARE TO REFLECT THE 2006 REVISIONS. |
| | PLEASE LIST THE FOLLOWING ON SHEETS FOR THIS REVIEWER |
| | AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE PLANS DO NOT CONTAIN ANY DESIGNER |
| | OF RECORD, PRINTED NAME , SIGNATURE, DATES SEALS?? |
| | PLEASE COMPLETE. FBC 106.3.5.4, 106.1.2 |
| | |
| | 3) NOTE: PLEASE CORRELATE PLANS WITH THE RISER. PLEASE |
| | SEE PLANS INDICATE PANEL OUTSIDE YET RISER MENTIONS IN |
| | GARAGE? PLANS DO NOT SHOW ANY GARAGE? |
| | 215.5, 110.26, 240.24 ETC. |
| | FBC 106.1.2 |
| | |
| | 4) NOTE: PLEASE INDICATE THE AIC RATING FOR THE MAIN |
| | CIRCUIT BREAKER. |
| | 110.9. (SHOWN FOR PANEL AND BRANCH BREAKERS, NOT FOR |
| | MAIN) |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE SEE MISSING KITCHEN COUNTER SPACE |
| | RECEPTACLES PER 210.52C1-5 |
| | |
| | 6) NOTE: PLEASE SEE PANEL SCHEDULE SHOWS DISPOSAL, YET |
| | PLANS DO NOT SHOW RECEPTACLE FOR THIS. |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE SEE MISSING GFI DESIGNATION FROM |
| | SEVERAL DEVICES. PLEASE SEE 210.8A1, A2, A3, A6 ETC. |
| | BATH(S), OUTSIDE, KITCHEN COUNTER SPACES ETC,, |
| | |
| | 8) NOTE: PLEASE SEE MISSING EGRESS LIGHTING CONTROL FOR |
| | INSIDE AND OUTSIDE STAIRS. (3-WAYS). |
| | PLEASE SEE 210.70, LS 101 7.8 |
| | |
| | 9) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.52 AND |
| | DINING ROOM RECEPTACLES WHICH ARE REQUIRED ON ONE OR |
| | MORE OF THE SMALL APPLIANCE CIRCUITS. |
| | |
| | 10) NOTE: PLEASE SEE THE LOAD CALCULATIONS DO NOT |
| | CORRELATE WITH THE CIRCUITS ON THE PANEL SCHEDULE, |
| | THERE ARE SEVERAL ITEMS WHICH ARE EITHER ON LOAD |
| | CALCULATIONS AND NOT ON PANEL SCHEDULE OR SEVERAL ITEMS |
| | ON THE PANEL SCHEDULE WHICH IS NOT IN LOAD |
| | CALCULATIONS. |
| | PLEASE SEE FOUR CIRCUITS SHOWN FOR *OVER FEAD DOORS* |
| | (MISSPELLED ON PLANS) YET THERE ARE NO OVER HEAD GARAGE |
| | DOORS OR EVEN A GARAGE ON PLANS. |
| | PLEASE SEE MISSING WATER HEATER, ICE MAKE, ETC ETC. |
| | FBC 106.1.2 |
| | NEC 408.4, 220 ETC |
| | |
| | 11) NOTE: PLEASE SEE MISSING AHU FROM PLANS. PLEASE SEE |
| | MISSING DISCONNECT. |
| | PLEASE SEE 440.11, 110.26, 240.24. |
| | |
| | 12) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER |
| | HEATER. |
| | 422.30, 31. |
| | |
| | 13) NOTE: PLEASE SEE CHANGE IN THE 2005 NEC FOR LOADS |
| | FOR WATER HEATERS PER 422.13. |
| | PLEASE SEE THE FOLLOWING TEXT EXTRACTED FORM THE NEC. |
| | |
| | *THE REVISION TO 422.13 SPECIFICALLY IDENTIFIES AN |
| | ELECTRIC WATER HEATER WITH A STORAGE CAPACITY OF 120 |
| | GAL OR LESS AS A CONTINUOUS LOAD. THIS REVISION |
| | REQUIRES THE BRANCH CIRCUIT OVERCURRENT DEVICE AND |
| | CONDUCTORS TO BE SIZED BASED ON 125 PERCENT OF THE |
| | WATER HEATER NAMEPLATE RATING UNLESS THE OVERCURRENT |
| | DEVICE AND THE ASSEMBLY IT IS INSTALLED IN ARE LISTED |
| | TO BE USED AT 100 PERCENT OF ITS CONTINUOUS CURRENT |
| | RATING. IN ADDITION, FEEDERS AND SERVICES THAT SUPPLY |
| | WATER HEATER BRANCH CIRCUITS ARE ALSO IMPACTED BY THE |
| | FACT THAT THIS TYPE OF EQUIPMENT IS CONSIDERED TO BE A |
| | CONTINUOUS LOAD.* |
| | |
| | 14) NOTE: PLEASE SEE THE LOAD CALCULATIONS INDICATE |
| | FOUR A/C SYSTEMS? |
| | PLEASE COORDINATE WITH PLANS AND PANEL SCHEDULE AS ONLY |
| | ONE SYSTEM IS SHOWN. |
| | FBC 106.1.2 |
| | |
| | 15) NOTE: PLEASE SEE NEC 220, AS THE LOAD CALCULATIONS |
| | INDICATE A LOAD OF 259AMPS?? |
| | PLEASE REVISE. |
| | |
| | 16) NOTE: PLEASE SEE MOST ROOMS INDICATE THE ENTIRE |
| | RECEPTACLE BEING SWITCHED, THIS IS OK, HOWEVER THEN A |
| | RECEPTACLE WOULD BE REQUIRED FOR GENERAL PURPOSE (HOT |
| | ALL THE TIME). |
| | IF THIS IS INDEED A HALF-SWITCHED OUTLET THEN PLEASE |
| | SHOW AS THIS. |
| | |
| | 17) NOTE: PLEASE SEE 408.4 WHICH REQUIRE ALL CIRCUITS |
| | TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED. |
| | THE USE OF *GEN LTS AND GEN RECEPTS* IS NOT PERMITTED. |
| | PLEASE SEE THE FOLLOWING TECT TAKEN FROM THE NEC. |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |