| Plan Review Notes For Permit 07030763 |
| Permit Number |
07030763 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-10 10:38:44 | DENIED | | | REFERENCE: | | | ** FBC-2004 SECTIONS 424.2 OR R4101 SWIMMING POOLS. ** | | | FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | | | | THE FOLLOWING CORRECTIONS/INFORMATIONREQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. PER FBC-2004 CHAPTER 1, SECTION 106.1.1: | | | INFORMATION ON CONSTRUCTION | | | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL | | | BE OF SUFFICIENT CLARITY TO INDICATE THE | | | LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE | | | AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, | | | AS DETERMINED BY THE | | | BUILDING OFFICIAL. | | | NOTE: PLANS ARE NOT LEGIBLE, THEY ARE HARD TO READ DUE | | | TO THE INK RUNNING TOGETHER. PLEASE CORRECT AND | | | RESUBMIT. | | | | | | 2. PLEASE CORRELATE THE MAIN DRAIN VENT PIPE SIZE ON | | | THE RESUBMITTAL. | | | A} MAIN DRAIN DETAIL INDICATES AN 1-1/2" VENT PIPE. | | | B} PIPING SCHEMATIC INDICATES A 1" VENT. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|