Plan Review Notes
Plan Review Notes For Permit 07030722
Permit Number 07030722
Review Stop P
Sequence Number 2
Notes
Date Text
2007-06-18 15:37:43DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 WPB MUNICIPAL CODE
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
  
 3. SHT 3.0P GAS RISER DIAGRAM. MINIMUM 1" REQUIRED TO
 THE WATER HEATER. TABLE 402.4(2). SHOW MINIMUM VALVE
 SIZES FOR EACH GAS EQUIPMENT CONNECTING TO THE 1.5" GAS
 HEADER PER TABLE 402.4.2.
 ****RESPONSE NOTED, BUT THE PIPE & VALVE SIZES SHALL BE
 INDICATED ON THE RISER DIAGRAM. THE SIZE FOR THE WATER
 HEATER IS INDICATED AS 3/4" IN THE LOAD CALCULATIONS
 AND THE OVEN IS INDICATED AS 1/2" IN THE LOAD
 CALCULATIONS. THE OVEN IS REQUIRED TO BE 1-1/4" IF THE
 LOAD CALCULATION IS 375,000 BTU'S AS SHOWN, BUT THE NEW
 SPECIFICATION SHEET FOR EXCALIBER OVEN INDICATES THAT
 THE BTU LOAD IS 225,000 BTU'S. IF THE LATTER IS USED,
 THEN A MINIMUM 1" VALVE IS REQUIRED.
  
 4. OK
  
  
 5. THE MANUF. SPECIFICATION SHEETS FOR THE HOBART
 DOUBLE OVEN SHOWS A BTU RATING OF 318,000 BTU'S, BUT
 THE RISER DIAGRAM INDICATES 375,000BTU'S. PLEASE
 CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE NEW OVEN, (EXCALIBER), BTU
 LOAD DOES NOT REFLECT THE LOAD CALCULATIONS ON SHT
 3.0P. PLEASE CORRELATE INFORMATION FROM THE MANUF. AND
 THE LOAD CALCULATION.
  
 6. OK
 7. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy