| Plan Review Notes For Permit 07030722 |
| Permit Number |
07030722 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-06-13 09:52:57 | -----------------DENIED-------------------- | | | | | | A CALL WAS PLACED AND A MESSAGE LEFT FOR MR TWOMEY (ON | | | 6/7/07) TO ASK QUESTIONS REGARDING THE RESUBMITTAL BUT | | | NO RETURN CALL WAS RECEIVED. | | | | | | 1. PRODUCT APPROVAL INSTALLATION INSTRUCTIONS DO NOT | | | MATCH THOSE SHOWN ON PLAN. IF STANDS ARE TO BE | | | INSTALLED PER THEIR PRODUCT APPROVAL, PLEASE MAKE THE | | | PLAN MATCH THE INSTRUCTIONS. FBC 106.1.1. | | | | | | 2. RESPONSE TO PREVIOUS REVIEW COMMENTS STATES THAT THE | | | HOOD SYSTEM IS "NOT TO BE INSTALLLED AT THIS TIME." | | | THIS IS A COMMERCIAL KITCHEN AND WILL NOT BE CODE | | | COMPLIANT WITHOUT A COMMERCIAL KITCHEN HOOD VENTILATION | | | SYSTEM. FBC,M 507.2 | | | | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|