| Plan Review Notes For Permit 07030722 |
| Permit Number |
07030722 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-06-18 15:47:04 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | 1. SHT 3.0P GAS RISER DIAGRAM. MINIMUM 1" REQUIRED TO | | | THE WATER HEATER. TABLE 402.4(2). SHOW MINIMUM VALVE | | | SIZES FOR EACH GAS EQUIPMENT CONNECTING TO THE 1.5" GAS | | | HEADER PER TABLE 402.4.2. | | | ****RESPONSE NOTED, BUT THE PIPE & VALVE SIZES SHALL BE | | | INDICATED ON THE RISER DIAGRAM. THE SIZE FOR THE WATER | | | HEATER IS INDICATED AS 3/4" IN THE LOAD CALCULATIONS | | | AND THE OVEN IS INDICATED AS 1/2" IN THE LOAD | | | CALCULATIONS. THE OVEN IS REQUIRED TO BE 1-1/4" IF THE | | | LOAD CALCULATION IS 375,000 BTU'S AS SHOWN, BUT THE NEW | | | SPECIFICATION SHEET FOR EXCALIBER OVEN INDICATES THAT | | | THE BTU LOAD IS 225,000 BTU'S. IF THE LATTER IS USED, | | | THEN A MINIMUM 1" VALVE IS REQUIRED. | | | | | | 2. OK | | | | | | | | | 3. THE MANUF. SPECIFICATION SHEETS FOR THE HOBART | | | DOUBLE OVEN SHOWS A BTU RATING OF 318,000 BTU'S, BUT | | | THE RISER DIAGRAM INDICATES 375,000BTU'S. PLEASE | | | CLARIFY. SECTION 106.1.1. | | | ****RESPONSE NOTED, BUT THE NEW OVEN, (EXCALIBER), BTU | | | LOAD DOES NOT REFLECT THE LOAD CALCULATIONS ON SHT | | | 3.0P. PLEASE CORRELATE INFORMATION FROM THE MANUF. AND | | | THE LOAD CALCULATION. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|