| 2007-04-09 09:58:47 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | WPB MUNICIPAL CODE |
| | |
| | 1. SHTS A1.1 & 1.1ANO WATER SUPPLY OR WASTE DRAIN |
| | SIZE INDICATED FORITEMS 1, 2, 8, 16 & 44. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | |
| | 2. GREASE INTERCEPTOR SHALL BE SIZED AND LOCATED BY |
| | ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO |
| | (561) 822-2272, FAX (561) 822-2287, OR [email protected]. |
| | MUNICIPAL CODE ARTICLE III SEWERS & SEWAGE DISPOSAL |
| | SECTION 90-124(7)(A) THRU (G). |
| | |
| | 3. SHT 3.0P GAS RISER DIAGRAM. MINIMUM 1" REQUIRED TO |
| | THE WATER HEATER. TABLE 402.4(2). SHOW MINIMUM VALVE |
| | SIZES FOR EACH GAS EQUIPMENT CONNECTING TO THE 1.5" GAS |
| | HEADER PER TABLE 402.4.2. |
| | |
| | 4. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE GAS |
| | WATER HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA |
| | 54, NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | |
| | 5. THE MANUF. SPECIFICATION SHEETS FOR THE HOBART |
| | DOUBLE OVEN SHOWS A BTU RATING OF 318,000 BTU'S, BUT |
| | THE RISER DIAGRAM INDICATES 375,000BTU'S. PLEASE |
| | CLARIFY. SECTION 106.1.1. |
| | |
| | 6. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. (FOR THE WATER HEATER). |
| | |
| | 7. SHT P3.0P SANITARY RISER DIAGRAM. SEPARATE DRAIN |
| | LINES ARE REQUIRED FOR THE ICE MAKER, AND THE ICE |
| | STORAGE BIN. SECTION 802. |
| | |