| Plan Review Notes For Permit 07030722 |
| Permit Number |
07030722 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-16 16:33:31 | -----------------DENIED-------------------- | | | | | | FBC 2004 W/2006 REVISIONS | | | FBC CH. 1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. EQUIPMENT STAND DETAIL: PRE-ENGINEERED EQUIPMENT | | | STANDS ARE STRUCTURAL ELEMENTS AS DEFINED IN FAC 9B-72 | | | AND AS SUCT, PRODUCT APPROVAL IS REQUIRED. | | | | | | 2. RTU MOUNTING DETAIL: PLEASE PROVIDE WIND LOAD | | | CALCULATIONS FOR RTU WITH ATTACHMENT DETAILS BY A | | | FLORIDA LICENSED STRUCTURAL ENGINEER IN SUFFICIENT | | | DETAIL. WHAT IS GAUGE OF STRAP? WHAT IS THICKNESS OF | | | 3X3 ANGLE? FBC 106.1.2. | | | | | | 3. SEPARATE PERMITS ARE REQUIRED FOR KITCHEN HOODS, | | | HOOD SUPPRESSION SYSTEMS AND WALK IN COOLERS/FREEZERS. | | | | | | REVIEWED BY: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | |
|