Plan Review Notes
Plan Review Notes For Permit 07030722
Permit Number 07030722
Review Stop G
Sequence Number 1
Notes
Date Text
2007-06-18 15:42:02DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT 3.0P GAS RISER DIAGRAM. MINIMUM 1" REQUIRED TO
 THE WATER HEATER. TABLE 402.4(2). SHOW MINIMUM VALVE
 SIZES FOR EACH GAS EQUIPMENT CONNECTING TO THE 1.5" GAS
 HEADER PER TABLE 402.4.2.
  
 2. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE GAS
 WATER HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND THE FBC-2004 FUEL GAS CODE SEC 402.2.
  
  
 3. THE MANUF. SPECIFICATION SHEETS FOR THE HOBART
 DOUBLE OVEN SHOWS A BTU RATING OF 318,000 BTU'S, BUT
 THE RISER DIAGRAM INDICATES 375,000BTU'S. PLEASE
 CLARIFY. SECTION 106.1.1.
  
  
 REVIEW BY KEN STEVENS