| Plan Review Notes For Permit 07030722 |
| Permit Number |
07030722 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-24 15:43:31 | *****DENIED***** | | | | | | | | | | | | 1.REPLACE THE K- RATED FIRE EXTINGUISHER SHOWN AT ONE | | | OF THE TWO EXIT DOORS WITH THE APPROPIATE 2A10BC RATED | | | EXTINGUISHER.FOR CONSISTENCY, SEE GENERAL NOTE #8 ON | | | THE COVER SHEET. | | | | | | 2.BE SPECIFIC IN IDENTIFYING THE MINIMUM INTERIOR | | | FINISH CLASSIFICATION FOR THE WALLS AND CEILING IN THE | | | EXIT, EXIT ACCESS CORRIDOR, AND OTHER SPACES AS CLASS | | | A, CLASS B, OR CLASS C. | | | | | | 3.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE | | | COOKING HOOD INSTALLATION AND FOR THE COOKING HOOD | | | SUPPRESSION SYSTEM. | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-6722 |
|