2007-04-24 15:43:31*****DENIED*****
  
  
  
 1.REPLACE THE K- RATED FIRE EXTINGUISHER SHOWN AT ONE
 OF THE TWO EXIT DOORS WITH THE APPROPIATE 2A10BC RATED
 EXTINGUISHER.FOR CONSISTENCY, SEE GENERAL NOTE #8 ON
 THE COVER SHEET.
  
 2.BE SPECIFIC IN IDENTIFYING THE MINIMUM INTERIOR
 FINISH CLASSIFICATION FOR THE WALLS AND CEILING IN THE
 EXIT, EXIT ACCESS CORRIDOR, AND OTHER SPACES AS CLASS
 A, CLASS B, OR CLASS C.
  
 3.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 COOKING HOOD INSTALLATION AND FOR THE COOKING HOOD
 SUPPRESSION SYSTEM.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW