| Date |
Text |
| 2007-03-25 11:58:07 | |
| | |
| | ****** UNSAT***** |
| | |
| | ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 |
| | IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE |
| | ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY |
| | THE CITY OF WEST PALM BEACH. |
| | |
| | |
| | 1) NOTE:PLEASE INDICATE THE AIC RATING FOR SERVICE |
| | EQUIPMENT.THE RATING IS SHOWN FOR PANEL BUT NOT ON |
| | NEW TENANT DISCONNECT. |
| | 110.9. |
| | FBC 106.1.2 |
| | |
| | 2) NOTE: PLEASE SEE THAT THE METER SHALL CONTAIN A |
| | *FLOATING NEUTRAL* KIT, PLEASE NOT ON PLANS/RISER. |
| | 250.6, 240.24 |
| | |
| | 3) NOTE: PLEASE SEE THE PLANS AND ENERGY CALCULATIONS |
| | BOTH CONTAIN *WHITE OUT* IN SEPARATE AREAS FOR THE |
| | ADDRESS AND SUITE/UNIT NUMBER.PLANS AND DOCUMENTS MAY |
| | NOT CONTAIN *WHITE-OUT* IN ANY FASHION. PLEASE KNOW |
| | PLANS WILL ROUTED TO ADDRESSING REVIEWER AND THE |
| | UNIT/SUITE NUMBER WILL BE ASSIGNED. PLEASE BE SURE TO |
| | WAIT TO REVISE PLANS ONCE A NUMBER HAS BEEN |
| | DETERMINED. |
| | FS 471.025 |
| | |
| | 4) NOTE: PLEASE SEE THE MAXIMUM OCCUPANCY SENSOR OVER |
| | RIDE TIMES IS 30MINS BASED ON 13-415.1.ABC.1.1,.1.2. |
| | PLANS INDICATE 1HR WHICH IS ONLY OK, IF USING TIMER |
| | TYPE DEVICES WHICH PERMITS UP TO 4HRS. |
| | |
| | 5) NOTE: PLEASE CLARIFY ALL LIGHTING ON PLANS AND |
| | ENERGY CALCULATIONS. THE WATTAGE BEING SHOWN, IS THIS |
| | BASED ON FIXTURE BALLAST ALLOWANCE? DEPENDING ON THE |
| | FIXTURE THE WATTAGE OF BALLAST MAY ACTUALLY BE LOWER |
| | THAN THE WATTAGE OF BULBS? PLEASE INCLUDE THE BATH LT |
| | FIXTURE ON FIXTURE LEGEND. IS THIS A FAN/LT COMBO? |
| | PLEASE CLARIFY. 13-415.1.AB.1.1 |
| | THIS TENANT SPACE IS USING THE METHOD A FOR WHOLE |
| | BUILDING. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |