Plan Review Notes
Plan Review Notes For Permit 07030722
Permit Number 07030722
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-25 11:58:07 
  
 ****** UNSAT*****
  
 ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1
 IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE
 ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY
 THE CITY OF WEST PALM BEACH.
  
  
 1) NOTE:PLEASE INDICATE THE AIC RATING FOR SERVICE
 EQUIPMENT.THE RATING IS SHOWN FOR PANEL BUT NOT ON
 NEW TENANT DISCONNECT.
 110.9.
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE THAT THE METER SHALL CONTAIN A
 *FLOATING NEUTRAL* KIT, PLEASE NOT ON PLANS/RISER.
 250.6, 240.24
  
 3) NOTE: PLEASE SEE THE PLANS AND ENERGY CALCULATIONS
 BOTH CONTAIN *WHITE OUT* IN SEPARATE AREAS FOR THE
 ADDRESS AND SUITE/UNIT NUMBER.PLANS AND DOCUMENTS MAY
 NOT CONTAIN *WHITE-OUT* IN ANY FASHION. PLEASE KNOW
 PLANS WILL ROUTED TO ADDRESSING REVIEWER AND THE
 UNIT/SUITE NUMBER WILL BE ASSIGNED. PLEASE BE SURE TO
 WAIT TO REVISE PLANS ONCE A NUMBER HAS BEEN
 DETERMINED.
 FS 471.025
  
 4) NOTE: PLEASE SEE THE MAXIMUM OCCUPANCY SENSOR OVER
 RIDE TIMES IS 30MINS BASED ON 13-415.1.ABC.1.1,.1.2.
 PLANS INDICATE 1HR WHICH IS ONLY OK, IF USING TIMER
 TYPE DEVICES WHICH PERMITS UP TO 4HRS.
  
 5) NOTE: PLEASE CLARIFY ALL LIGHTING ON PLANS AND
 ENERGY CALCULATIONS. THE WATTAGE BEING SHOWN, IS THIS
 BASED ON FIXTURE BALLAST ALLOWANCE? DEPENDING ON THE
 FIXTURE THE WATTAGE OF BALLAST MAY ACTUALLY BE LOWER
 THAN THE WATTAGE OF BULBS? PLEASE INCLUDE THE BATH LT
 FIXTURE ON FIXTURE LEGEND. IS THIS A FAN/LT COMBO?
 PLEASE CLARIFY. 13-415.1.AB.1.1
 THIS TENANT SPACE IS USING THE METHOD A FOR WHOLE
 BUILDING.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved