| 2008-06-04 16:52:25 | PLUMBING PLAN REVIEW: |
| | REVISION DENIED OF NON-NUMBERED LANDSCAPE AND |
| | IRRIGATION PLAN SHEETS: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE FOR THE |
| | NEWLY SUBMITTED NON-NUMBERED LANDSCAPE AND IRRIGATION |
| | PLAN. |
| | |
| | 1. THE NON-NUMBERED LANDSCAPE AND IRRIGATION PLAN |
| | SHEETS REQUIRE A TITLE BLOCK FROM THE LANDSCAPE |
| | ARCHITECT. |
| | FAC-61G1-16.004 TITLE BLOCK: |
| | A TITLE BLOCK MUST APPEAR ON ALL |
| | ARCHITECTURAL OR INTERIOR DESIGN |
| | DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK |
| | MUST, AT A MINIMUM, CONTAIN THE |
| | FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE |
| | NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED |
| | SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE |
| | PERSON SEALING THE DOCUMENT. |
| | NOTE: THE FOLLOWING INFORMATION IS MISSING FROM THE |
| | PLAN SHEETS (1), (2) AND (6). PLEASE COMPLY WITH THE |
| | REQUIRED INFORMATION ON THE REVISION RESUBMITTAL OF |
| | THESE SHEETS. |
| | |
| | 2. THE SUBMITTED IRRIGATION PLANS SHALL CLEARLY |
| | INDICATE THE FOLLOWING (NOTE: AN EQUIPMENT INDEX IS |
| | HELPFUL TO IDENTIFY ITEMS ON THE PLANS): |
| | |
| | A} CONTROL PANEL |
| | B} RAIN SENSOR |
| | C} TIME CLOCK |
| | D} WATER SOURCE |
| | A- IF ITS CITY WATER, PLEASE INDICATE SO ON PLANS |
| | ALONG WITH THE BACKFLOW PREVENTER LOCATION. |
| | B- IF ITS A WELL, PLEASE INDICATE SO ON THE PLANS |
| | ALONG WITH THE PUMP LOCATION. |
| | C- IF ITS PUMPED FROM A LAKE/CANAL, PLEASE INDICATE |
| | SO ON THE PLANS ALONG WITH THE PUMP LOCATION. |
| | |
| | 3. HAND WRITTEN CHANGES TO SIGNED AND SEALED PLANS IS |
| | UNACCEPTABLE. PER (W.P.B. AS AMENDED) SECTION 106.1.3 |
| | QUALITY OF BUILDING PLANS. THE BUILDING OFFICIAL MAY |
| | ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR |
| | PLANS AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| | CONFORMITY TO ITS RECORD RETENTION PROGRAM. THIS POLICY |
| | MAY INCLUDE SUCH THINGS AS MINIMUM SIZE, SHAPE, |
| | CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO RECORDS |
| | MANAGEMENT. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |