Plan Review Notes
Plan Review Notes For Permit 07030701
Permit Number 07030701
Review Stop P
Sequence Number 6
Notes
Date Text
2008-04-07 16:20:44PLUMBING PLAN REVIEW:
 PRODUCT APPROVAL DENIED:
  
 PLAN REVIEW (PRODUCT APPROVAL) UNDER THE 2004 FLORIDA
 BUILDING CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 1. THE SUBMITTED PRODUCT APPROVAL FOR THE SHOWER PAN
 LINER HAS BEEN DENIED. THE SUBMITTED PRODUCT APPROVAL
 FOR THE SHOWER PAN LINER IS NOT COMPLIANT WITH FBC
 PLUMBING THE FOLLOWING SECTIONS.
  
 417.5.2 SHOWER LINING.
 FLOORS UNDER SHOWER COMPARTMENTS, EXCEPT WHERE
 PREFABRICATED RECEPTORS HAVE BEEN PROVIDED, SHALL BE
 LINED AND MADE WATER TIGHT UTILIZING MATERIAL COMPLYING
 WITH SECTIONS 417.5.2.1 THROUGH 417.5.2.4 . SUCH LINERS
 SHALL TURN UP ON ALL SIDES AT LEAST 2 INCHES (51 MM)
 ABOVE THE FINISHED THRESHOLD LEVEL. LINERS SHALL BE
 RECESSED AND FASTENED TO AN APPROVED BACKING SO AS NOT
 TO OCCUPY THE SPACE REQUIRED FOR WALL COVERING, AND
 SHALL NOT BE NAILED OR PERFORATED AT ANY POINT LESS
 THAN 1 INCH (25 MM) ABOVE THE FINISHED THRESHOLD.
 LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12
 UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED
 TOWARD THE FIXTURE DRAINS AND BE SECURELY FASTENED TO
 THE WASTE OUTLET AT THE SEEPAGE ENTRANCE, MAKING A
 WATER-TIGHT JOINT BETWEEN THE LINER AND THE OUTLET.
  
 417.5.2.1 PVC SHEETS.
 PLASTICIZED POLYVINYL CHLORIDE (PVC) SHEETS SHALL BE A
 MINIMUM OF 0.040 INCH (1.02 MM) THICK, AND SHALL MEET
 THE REQUIREMENTS OF ASTM D 4551. SHEETS SHALL BE JOINED
 BY SOLVENT WELDING IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS.
  
 417.5.2.2 CHLORINATED POLYETHYLENE (CPE) SHEETS.
 NONPLASTICIZED CHLORINATED POLYETHYLENE SHEET SHALL BE
 A MINIMUM 0.040 INCH (1.02 MM) THICK, AND SHALL MEET
 THE REQUIREMENTS OF ASTM D 4068. THE LINER SHALL BE
 JOINED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS.
  
 417.5.2.3 SHEET LEAD.
 SHEET LEAD SHALL NOT WEIGH LESS THAN 4 POUNDS PER
 SQUARE FOOT (19.5 KG/M 2 ) COATED WITH AN ASPHALT PAINT
 OR OTHER APPROVED COATING. THE LEAD SHEET SHALL BE
 INSULATED FROM CONDUCTING SUBSTANCES OTHER THAN THE
 CONNECTING DRAIN BY 15-POUND (6.80 KG) ASPHALT FELT OR
 ITS EQUIVALENT. SHEET LEAD SHALL BE JOINED BY BURNING.
  
  
 417.5.2.4 SHEET COPPER.
 SHEET COPPER SHALL CONFORM TO ASTM B 152 AND SHALL NOT
 WEIGH LESS THAN 12 OUNCES PER SQUARE FOOT (3.7 KG/M 2
 ). THE COPPER SHEET SHALL BE INSULATED FROM CONDUCTING
 SUBSTANCES OTHER THAN THE CONNECTING DRAIN BY 15-POUND
 (6.80 KG) ASPHALT FELT OR ITS EQUIVALENT. SHEET COPPER
 SHALL BE JOINED BY BRAZING OR SOLDERING.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]