2008-02-22 08:56:51*** PROVISO ***
 1) PER 2004 FBC/R M1602 RETURN AIR, M1602.2 PROHIBITED
 SOURCES.
 OUTSIDE OR RETURN AIR FOR A FORCED-AIR HEATING OR
 COOLING SYSTEM SHALL NOT BE TAKEN FROM THE FOLLOWING
 LOCATIONS:
 #5. A ROOM OR SPACE CONTAINING A FUEL-BURNING
 APPLIANCE WHERE SUCH ROOM OR SPACE SERVES AS THE SOLE
 SOURCE OF RETURN AIR.
  
 2) PER 2004 FBC/R M2005.2 PROHIBITED LOCATIONS.
 FUEL-FIRED WATER HEATERS SHALL NOT BE INSTALLED IN A
 ROOM USED AS A STORAGE CLOSET. WATER HEATERS LOCATED IN
 A BEDROOM OR BATHROOM SHALL BE INSTALLED IN A SEALED
 ENCLOSURE SO THAT COMBUSTION AIR WILL NOT BE TAKEN FROM
 THE LIVING SPACE. DIRECT-VENT WATER HEATERS ARE NOT
 REQUIRED TO BE INSTALLED WITHIN AN ENCLOSURE.
  
 3) GAS WATER HEATER SHALL COMPLY WITH 2004 FBC/R
 G2407.1 COMBUSTION, VENTILATION AND DILUTION AIR. AND
 G2407.4 MAKEUP AIR.
  