| Plan Review Notes For Permit 07030701 |
| Permit Number |
07030701 |
|
| Review Stop |
M |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2008-02-22 08:56:51 | *** PROVISO *** | | | 1) PER 2004 FBC/R M1602 RETURN AIR, M1602.2 PROHIBITED | | | SOURCES. | | | OUTSIDE OR RETURN AIR FOR A FORCED-AIR HEATING OR | | | COOLING SYSTEM SHALL NOT BE TAKEN FROM THE FOLLOWING | | | LOCATIONS: | | | #5. A ROOM OR SPACE CONTAINING A FUEL-BURNING | | | APPLIANCE WHERE SUCH ROOM OR SPACE SERVES AS THE SOLE | | | SOURCE OF RETURN AIR. | | | | | | 2) PER 2004 FBC/R M2005.2 PROHIBITED LOCATIONS. | | | FUEL-FIRED WATER HEATERS SHALL NOT BE INSTALLED IN A | | | ROOM USED AS A STORAGE CLOSET. WATER HEATERS LOCATED IN | | | A BEDROOM OR BATHROOM SHALL BE INSTALLED IN A SEALED | | | ENCLOSURE SO THAT COMBUSTION AIR WILL NOT BE TAKEN FROM | | | THE LIVING SPACE. DIRECT-VENT WATER HEATERS ARE NOT | | | REQUIRED TO BE INSTALLED WITHIN AN ENCLOSURE. | | | | | | 3) GAS WATER HEATER SHALL COMPLY WITH 2004 FBC/R | | | G2407.1 COMBUSTION, VENTILATION AND DILUTION AIR. AND | | | G2407.4 MAKEUP AIR. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|