| Plan Review Notes For Permit 07030701 |
| Permit Number |
07030701 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-09-24 14:29:32 | ****************PROVISO**************** | | | (A) 802.1.6 DOMESTIC DISHWASHING MACHINES SHALL | | | DISCHARGE INDIRECTLY THROUGH AN AIR GAP OR AIR BREAK | | | INTO A STANDPIPE OR WASTE RECEPTOR IN ACCORDANCE WITH | | | SECTION 802.2 OR DISCHARGE INTO A WYE-BRANCH FITTING ON | | | THE TAILPIECE OF THE KITCHEN SINK OR THE DISHWASHER | | | CONNECTION OF A FOOD WASTE GRINDER. | | | | | | ****************PROVISO**************** | | | PER FBC-2004 PLUMBING, SECTION 704.5 | | | DEAD ENDS: IN THE INSTALLATION OR | | | REMOVAL OF ANY PART OF A DRAINAGE | | | SYSTEM, DEAD ENDS SHALL BE PROHIBITED. | | | A PLUMBING PERMIT REQUIRED AND | | | INSPECTION REQUIRED OF DEMO WORK PRIOR | | | TO COVERING DEMO WORK WITH FINNISH | | | WALLS, CIELINGS, OR POURED CONCRETE | | | SLABS. | | | | | | REVIEW BY MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|