2007-09-24 16:49:45PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS REQUESTED IN LAST REVIEW 5-25-07 NOTE #2. PLEASE
 SUBMIT COOLING LOAD CALCULATIONS, SEE FBC/R M1401.3.
 (THE HISTORICAL EXEMPTION IS FOR ENERGY CALCULATIONS
 NOT COOLING LOAD CALCULATIONS).
  
 2) THE AIR HANDLER HAS A 8" X 12" DUCT FEEDING TWO 12"
 DUCTS THIS WOULD APPEAR TO BE A RESTRICTION OF AIR,
 PLEASE SUBMIT MANUAL D CALCULATIONS FOR RESIDENTIAL
 DUCT DESIGN OR ANOTHER APPROVED METHOD, PER 2004 FBC/R
 M1601.1.
  