| Date |
Text |
| 2007-05-25 13:03:47 | DENIED 2ND TIME |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SHEET A-3 SANITARY RISER: PER FBC-2004 CHAPTER 1, |
| | SECTION 106.3.5.4 RESIDENTIAL (ONE AND TWO-FAMILY) |
| | PLEASE SUBMIT A PLUMBING SANITARY ISOMETRIC RISER |
| | DIAGRAM INDICATING ALL WASTE, VENTS, TRAPS AND SIZES |
| | WITH CLEANOUT LOCATIONS. |
| | NOTE: NOT ALL WASTE, VENTS, AND TRAPS ARE SIZED. PLEASE |
| | CORRECT THIS ON THE RESUBMITTAL. |
| | |
| | 2. SHEET A-3 SANITARY RISER: THE WASHING MACHINE NEEDS |
| | TO DISCHARGE DOWNSTREAM OF THE EXISTING WET VENTED BATH |
| | 2 BATHROOM GROUP. |
| | NOTE: PER FBC-2004, PLUMBING, SECTION 909.1 |
| | WET VENT PERMITTED: ONLY THE FIXTURES |
| | WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| | TO THE WET-VENTED HORIZONTAL BRANCH |
| | DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| | DISCHARGE DOWNSTREAM OF THE WET VENT. |
| | |
| | 3. SHEET A-3 SANITARY RISER: THE WASHING MACHINE |
| | BRANCH DRAIN AND STACK ARE SIZED WRONG. PLEASE CORRECT |
| | THE FOLLOWING FOR THE WASHING MACHINE PER FBC-2004 |
| | PLUMBING |
| | |
| | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. PLEASE CORRECT THE SIZING ON THE |
| | RESUBMITTAL. |
| | |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| | TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. PLEASE INDICATE THE WASHING MACHINE |
| | STANDPIPE ON THE RESUBMITTAL. |
| | |
| | (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| | BE THE SAME NOMINAL SIZE AS THE PIPE |
| | THEY SERVE UP TO 4 INCHES (102MM) |
| | NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE THREE |
| | INCH (3"). PLEASE INDICATE THIS ON THE RESUBMITTAL. |
| | |
| | (D) 708.9 ACCESS. ACCESS SHALL BE |
| | PROVIDED TO ALL CLEANOUTS. |
| | NOTE: PLEASE INDICATE THE WASHING MACHINE CLEANOUT AT |
| | FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.). |
| | |
| | 4. SHEET A-3 SANITARY RISER: |
| | FBC-2004 PLUMBING |
| | (A) 708.3.5 BUILDING DRAIN AND BUILDING |
| | SEWER JUNCTION. THERE SHALL BE AN |
| | APPROVED TWO-WAY CLEANOUT NEAR THE JUNCTION OF THE |
| | BUILDING DRAIN AND THE BUILDING SEWER. |
| | |
| | 5. SHEET A-3 SANITARY RISER: TRAPS ARE REQUIRED FOR |
| | THE PROPOSED SHOWER IN BATH 2 AND THE MASTER BATH |
| | SHOWER PER FBC-2004 PLUMBING, SECTION 1002.1. |
| | |
| | 6. SHEET A-3 SANITARY RISER: THE DISHWASHER DRAIN IS |
| | INDICATED WRONG. |
| | (A) 802.2 DISHWASHER SHALL DISCHARGE INTO A |
| | WYE-BRANCH FITTING ON THE TAILPIECE OF THE KITCHEN SINK |
| | OR THE DISHWASHER CONNECTION OF A FOOD WASTE GRINDER. |
| | PLEASE CORRECT THIS ON THE RESUBMITTAL. |
| | |
| | 7. SHEET A-3 SAINTARY RISER: PLEASE INDICATE THE |
| | PIPING TO THE WATER CLOSETS WITH QUARTER BENDS ON THE |
| | RESUBMITTAL. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561) 805-6721 |