| 2007-05-25 15:02:12 | *** DENIED *** |
| | 1) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC |
| | 13-101.2.3. |
| | |
| | 2) PLEASE SUBMITCOOLING LOAD CALCULATIONS, SEE 2004 |
| | FBC 13-607.1.ABC.1. |
| | |
| | 3) SHOW ON MECHANICAL PLANS THE LOCATION OF THE A/C |
| | CONDENSER UNIT AND THE CLOTHES DRYER VENT AND WERE IT |
| | WILL TERMINATE. BE ADVISED CLOTHES DRYER VENT |
| | TERMINATION MAY NOT BE NEAR THE A/C CONDENSER UNIT, SEE |
| | 2004 FBC/M 501.2 . |
| | |
| | 4) PLEASE SHOW ON THE MECHANICAL PLANS EQUIPMENT |
| | SCHEDULE, THE TOTAL AND SENSIBLE COOLING BTU'S. |
| | |
| | 5) SEE MECH. PLANS THE SUPPLY AIR DUCT FROM ONE MIXING |
| | BOX TO THE OTHER SHOWS 530 CFM BUT NO DUCT SIZE, PLEASE |
| | CORRECT. |
| | |
| | 6) SEE MECH. PLANS, THE 8X12 SUPPLY AIR DUCT LEAVING |
| | THE AIR HANDLER IS TO SMALL AS IT IS FEEDING TWO DUCTS |
| | 12" AND A 530 CFM?, PLEASE CORRECT. |
| | |
| | 7) SEE MECH. PLANS A 12' SUPPLY AIR DUCT IS FEEDING A |
| | 14X14 SUPPLY DUCT, THIS WOULD REDUCE THE AIR VELOCITY |
| | QUITE A BIT, PLEASE CHECK AND CORRECT. |
| | |
| | 8) THE RETURN AIR GRILL IN THE HALLWAY TO THE AIR |
| | HANDLER NEEDS TO BE SIZED. |
| | |
| | 9) THE 20X4 RETURN AIR TRANSFER GRILL TO THE MASTER |
| | SUITE IS TO SMALL, SEE 2004 FBC/R M1602.4 (B) AND (C) |
| | EXCEPT. PLEASE CORRECT. |
| | |
| | *** 2004 FBC/R M1602.4BALANCED RETURN AIR MAY BE |
| | ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE |
| | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS |
| | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR |
| | HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO |
| | ACHIEVE PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF |
| | GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND USING AN |
| | UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET |
| | THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR |
| | EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY |
| | ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE |
| | SHALL BE INCLUDED. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |
| | |