| 2007-05-23 09:24:42 | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | A SEPARATE PERMIT IS REQUIRED FOR THE GENERATOR, SEE |
| | ATTACHED REQUIREMENTS FOR THAT PERMIT. |
| | |
| | 1} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE |
| | EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS |
| | PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT |
| | TO THAT CODE. PLEASE CORRECT ALL NOTES TO REFLECT THIS |
| | CHANGE. |
| | |
| | 2} INDICATE IF THE SERVICE RISER ON THE PLAN IS PART OF |
| | THIS APPLICATION OR EXISTING. |
| | |
| | 3} IF THE SERVICE IS NEW: PER 110.9 AND 110.10: OBTAIN |
| | THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 4} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI |
| | PROTECTED PER 210.8(A) (1). INDICATE BATH CIRCUIT IN |
| | THE PANEL SCHEDULE. THE MASTER BATH NEEDS ANOTHER |
| | RECEPTACLE TO MEET SPACING PER 210.52(D). |
| | |
| | 5} ONE RECEPTACLE NEEDS TO BE ADDED IN THE MASTER |
| | BEDROOM PER 210.52(A)(2). |
| | |
| | 6} PER R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS |
| | REQUIRED IN NEW DWELLINGS AND WHEN REPAIRS OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR. SEE ARTICLE FOR COMPLETE |
| | TEXT.ALSO SEE THE DEFINITION OF "SMOKE DETECTORS" |
| | 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, |
| | TO AVOID CONFUSION IN THE FIELD. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |