Plan Review Notes
Plan Review Notes For Permit 07030701
Permit Number 07030701
Review Stop E
Sequence Number 2
Notes
Date Text
2007-05-23 09:24:42 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GENERATOR, SEE
 ATTACHED REQUIREMENTS FOR THAT PERMIT.
  
 1} THE 2005 NEC WAS ADOPTED BY THE FLORIDA LEGISLATURE
 EFFECTIVE 8 DECEMBER 2006. THE APPLICATION FOR THIS
 PROJECT WAS AFTER THAT DATE AND THE PLANS ARE SUBJECT
 TO THAT CODE. PLEASE CORRECT ALL NOTES TO REFLECT THIS
 CHANGE.
  
 2} INDICATE IF THE SERVICE RISER ON THE PLAN IS PART OF
 THIS APPLICATION OR EXISTING.
  
 3} IF THE SERVICE IS NEW: PER 110.9 AND 110.10: OBTAIN
 THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 4} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1). INDICATE BATH CIRCUIT IN
 THE PANEL SCHEDULE. THE MASTER BATH NEEDS ANOTHER
 RECEPTACLE TO MEET SPACING PER 210.52(D).
  
 5} ONE RECEPTACLE NEEDS TO BE ADDED IN THE MASTER
 BEDROOM PER 210.52(A)(2).
  
 6} PER R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS
 REQUIRED IN NEW DWELLINGS AND WHEN REPAIRS OR ADDITIONS
 REQUIRING A PERMIT OCCUR. SEE ARTICLE FOR COMPLETE
 TEXT.ALSO SEE THE DEFINITION OF "SMOKE DETECTORS"
 11.8.2.1 NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS,
 TO AVOID CONFUSION IN THE FIELD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718