Plan Review Notes
Plan Review Notes For Permit 07030701
Permit Number 07030701
Review Stop B
Sequence Number 2
Notes
Date Text
2007-06-05 18:24:32 
  
 DENIED
  
 1)IN AN EXISTING BUILDING A DESIGN PROFESSIONAL MUST
 ELECT THE LEVEL OF ALTERATION PER 301.5 OF EXISTING
 BUILDING CODE AND STATE ALONG WITH THE TYPE OF
 CONSTRUCTION ON THE DRAWINGS
  
 2)THE WORK BEING PERMITTED IS A LEVEL 2 ALTERATION
 PER 304.1 FBC EXTG. PLEASE SEE ATTACHED COPIES OF
 CHAPTER 3 CLASSIFICATION OF WORK (SECTION 304) AND AS
 SUCH ARE REQUIRED TO COMPLY WITH 601.3 FBC EXTG. THE
 ONLY EXCEPTIONS FOR OPERABLE WINDOWS ARE FOR LIGHT,
 ENERGY AND VENTILATION NONE IS GIVEN FOR EMERGENCY
 EGRESS.
  
 3)SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL ***** 2ND REQUEST*****
  
 4)PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING THE NOTICE IS
 VOID PLEASE RERECORD NOC ******NOTE THIS ITEM MAY BE
 DONE AT TIME OF PERMIT PICKUP********
  
 5)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS
 OF NEW DRAWINGS AND INCLUDE 1 COPY OF THE OLD PAGES
 ONLY FOR REFERENCE
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  