| Plan Review Notes For Permit 07030674 |
| Permit Number |
07030674 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-04-10 16:07:59 | DENIED | | | REFERENCE: | | | ** FBC-2004 FUEL GAS. | | | ** THE CITY OF WEST PALM BEACH GAS AND GEN/RES PERMIT | | | APPLICATION REQUIREMENTS. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: | | | | | | 1. PLEASE PROVIDE MANUFACTURER'S SPECIFICATIONS | | | INDICATING RECOMMENDED SETBACKS TO STRUCTURES AND | | | NATURAL GAS BTU LOAD VERIFICATIONS OF GENERATOR. PLEASE | | | PROVIDE INFORMATION THAT GENERATOR IS LISTED BY A | | | NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL). | | | | | | 2. PLEASE PROVIDE TWO COPIES OF A SITE PLAN OR SURVEY | | | THAT CLEARLY MARKS THE LOCATION OF THE PROPOSED | | | GENERATOR INDICATING ALL DIMENSIONS FROM PROPERTY LINES | | | AND DISTANCES FROM ADJACENT STRUCTURES. | | | | | | 3.A GAS PERMIT CAN NOT BE ISSUED UNTIL | | | A GEN/RES PERMIT APPLICATION HAS BEEN | | | APPLIED FOR AND APPROVED BY ZONING FOR | | | THE GENERATOR LOCATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561) 805-6721 |
|